1 - Dimensions ..............................................................................................................2
2 - Introduction .............................................................................................................3
3 - Important Safety Information .....................................................................................4
4 - Boiler Ratings & Capacities .........................................................................................5
5 - Before Installing The Boiler ........................................................................................6
6 - Locating The Boiler ...................................................................................................7
7 - Near Boiler Piping .....................................................................................................9
8 - Combustion Air And Vent Pipe .................................................................................. 12
9 - Gas Supply Piping ................................................................................................... 17
10 - Electrical Wiring .................................................................................................... 19
11 - Controls And Accessories ....................................................................................... 21
12 - Boiler Startup ....................................................................................................... 23
13 - Operating Instructions ........................................................................................... 24
14 - Maintenance And Cleaning ..................................................................................... 25
Appendix A - Boiler Piping And Wiring ............................................................................ 27
Appendix B - Water Quality, Water Treatment and Freeze Protection ................................... 45
2.1 Introduction
• Boiler is certifi ed in accordance with ANSI Z21.13
American National Standards Institute) and CSA
(Canadian Standards Association) 4.9.
• This appliance is a gas-fi red direct vent modulating cast
aluminum hot water boiler.
• Cast aluminum monoblock heat exchanger allows better
heat transfer and thermal storage than similarly sized
cast iron boilers resulting in higher effi ciency.
• The heating system water absorbs large amounts of
heat from the cast aluminum heat exchanger, cooling
fl ue gases and causing condensation.
• Sealed combustion, premix gas burner, and low fl ame
temperature means reduced CO and NOx emissions,
which contribute to cleaner and healthier environment.
• This appliance takes its combustion air directly from
outdoors (sealed combustion) and does not compete
with building occupants for fresh air.
2 - INTRODUCTION
• Sealed combustion (also known as “direct vent”)
is safest and best way to obtain plenty of clean
combustion air.
• Forced draft fan draws in outside combustion air, takes
cooler fl ue gases from boiler unit and provides positive
removal of fl ue gases from the building through readily
available PVC and CPVC pipes. Canada use ULC S636
Material.
• These low pressure gas-fi red hot water boilers are
design certifi ed by CSA International for use with
natural gas and propane gas.
• Boilers are constructed and hydrostatically tested
for maximum working pressure of 50 psig (pounds
per square inch gage) in accordance with A.S.M.E.
(American Society of Mechanical Engineers) Boiler and
Pressure Vessel Code Section IV Standards for heating
boilers.
3
Summary of Contents for Olsen OQ95M-200
Page 2: ...1 DIMENSIONS OPENING FOR SAFETY RELIEF VALVE DISCHARGE PIPE 30 785mm 39 1 1m 18 458mm 2 ...
Page 27: ...APPENDIX A BOILER PIPING AND WIRING Electrical Wiring Diagram 27 ...
Page 49: ...49 NOTES ...
Page 50: ...50 NOTES ...
Page 51: ...51 Company Address Phone Company Name Tech Initials Service Performed Date SERVICE RECORD ...
Page 52: ...ECR International 2201 Dwyer Avenue Utica NY 13501 web site www ecrinternational com ...