![ECR International Utica Boilers UB95M-200 Installation Manual Download Page 13](http://html1.mh-extra.com/html/ecr-international/utica-boilers-ub95m-200/utica-boilers-ub95m-200_installation-manual_2356166013.webp)
13
or below, electric meters, gas meters, regula-
tors, and relief equipment.
If multiple terminations are used, there must be
a minimum of 12” between the exhaust of one
termination and the air intake of the next termi-
nation. See Figures 1-3 for illustrations.
INSTALLATION
IMPORTANT:
When transitioning from CPVC to
PVC it is recommended to use Weld-On CPVC 724
or other cement approved for CPVC and PVC.
1. Attach combustion air intake piping to sup-
plied 2” PVC Intake Connector. Attach vent pip-
ing to furnished 2” CPVC vent pipe.
NOTE:
All pipe joints are to be water tight.
2. Working from the boiler to the outside, cut
pipe to required length(s).
3. Deburr inside and outside of pipe.
4. Chamfer outside edge of pipe for better distri-
bution of primer and cement.
5. Clean and dry all surfaces to be joined.
6. Check dry fit of pipe and mark insertion depth
on pipe.
NOTE:
It is recommended that all pipes be cut, prepared, and
pre-assembled before permanently cementing any joint.
7. After pipes have been cut and pre-assem-
bled, apply cement primer to pipe fitting socket
and end of pipe to insertion mark. Quickly apply
approved cement to end of pipe and fitting sock-
et (over primer). Apply cement in light, uniform
coat on the inside of socket to prevent buildup of
excess cement. Apply second coat.
NOTE:
Primer and cement will discolor jacket. Take pre-
cautions to protect jacket while cementing vent pipe.
8. While cement is still wet, insert pipe into sock-
et with a ¼ turn twist. Be sure pipe is fully in-
serted into fitting socket.
9. Wipe excess cement from joint. A continuous
bead of cement will be visible around perimeter
of a properly made joint.
10. Handle pipe joint carefully until cement sets.
11. Support combustion air and vent piping a
minimum of every 5’ using pre-formed metal
hanging straps. Support combustion air and
vent piping so no weight is resting on the boiler
jacket. Do not rigidly support pipes. Allow move-
ment due to expansion and contraction.
12. Slope combustion air and vent pipes toward
boiler a minimum of ¼” per linear foot with no
sags between hangers.
13. Use appropriate methods to seal open-
ings where vent and combustion air pipes pass
through roof or side wall.
IX - GAS SUPPLY PIPING
CHECK GAS SUPPLY
The gas pipe to your boiler must be the correct size
for the length of run and for the total BTU per hour
input of all gas utilization equipment connected to
it. See Table 4 at right for proper size. Be sure your
gas line complies with local codes and gas com-
pany requirements.
The boiler and its individual shutoff valve must be
disconnected from the gas supply piping system
during any pressure testing of that system at test
pressures in excess of ½ psig (3.5kPa).
The boiler must be isolated from the gas supply pip-
ing system by closing its individual manual shutoff
valve during any pressure testing of the gas supply
piping system at test pressures equal to or greater
than ½ psig (3.5kPa).
TABLE 4: GAS PIPING SIZES
Natural Gas
Pipe
Length
Pipe Capacity - BTU/Hr. Input Includes Fittings
½”
¾”
1”
1¼”
20’
92,000
190,000
350,000
625,000
40’
63,000
130,000
245,000
445,000
60’
50,000
105,000
195,000
365,000
LP Gas
Pipe
Length
Pipe Capacity - BTU/Hr. Input Includes Fittings
Copper Tubing (O.D.)
Iron Pipe
⅝”
¾”
½”
¾”
20’
131,000
216,000
189,000
393,000
40’
90,000
145,000
129,000
267,000
60’
72,000
121,000
103,000
217,000
The length of pipe or tubing should be measured from the gas
meter or propane second stage regulator.
Summary of Contents for Utica Boilers UB95M-200
Page 2: ......
Page 21: ...21 XIII BOILER WIRE DIAGRAM...
Page 22: ...22 XIV PIPING AND WIRING APPENDIX SINGLE ZONE SYSTEM WITH DOMESTIC HOT WATER PRIORITY...
Page 23: ...23 XIV PIPING AND WIRING APPENDIX SINGLE ZONE SYSTEM WITH DOMESTIC HOT WATER PRIORITY...
Page 36: ...36 XIV PIPING AND WIRING APPENDIX BYPASS PIPING AUTOMATIC MIXING VALVE...
Page 37: ...37 BYPASS PIPING FIXED LOW TEMP ONLY XIV PIPING AND WIRING APPENDIX...
Page 38: ...38 XIV PIPING AND WIRING APPENDIX BYPASS PIPING 4 WAY VALVE OPTION WITH CIRCULATOR ON SUPPLY...
Page 39: ......
Page 40: ......