54
9.14 Check Firing Rate
1.
Measure input, if a gas meter is installed in the
system.
•
Turn off gas to all other appliances.
• Activate some heating zones to dissipate heat.
•
Set boiler on high fire using Chimney Sweep
Function.
• Use ½, 1 or 2 cu ft dial on gas meter. Measure
time required for two or more complete
revolutions. Measure time
for one or more
minutes.
• Calculate input.
For Natural Gas :
Input (MBH)
=
3600 x cu ft
seconds
Example: Natural Gas - Gas flow from
Meter = 2 cu ft
Measured time = 72 seconds
=
3600 x 2 cu ft
= 100 MBH
72 seconds
For Propane (LP):
Input (MBH)
=
9160 x cu ft
seconds
For Metric formulas- See Glossary
2.
Compare measured input to table below. If
calculated input is not in range given in Table 9-2
check firing rate again after setting the combustion
following steps in section 9.12.
9 - START UP PROCEDURE
NOTICE
Important!
Record any changes made to
Parameters on chart found on Page 46 of the
Application Guide supplied with your boiler.
9.15 Parameter Settings
Program boiler electronic board parameters as follows:
• Press
and
together, hold them down
for 6 seconds until program “
P01
” appears on the
display alternated with the set value;
• Press
or
to scroll the list of parameters;
• Press
, value of selected parameter begins
flashing, press
to change the value;
• Press
to confirm the value or press
to
exit without saving.
Further information in regards to parameters listed in
the following table are supplied together with required
accessories if necessary.
Approximate Rate @
100% Fire (MBH)
Size
75
75
100
93.5
115
115
125
125
150
150
165
164
205
205
Table 9-2 Input Rate @ High Fire (MBH)
240013503 REV A, [03/15/2022]
Summary of Contents for UTICA BOILERS MACF-115
Page 2: ...MACF 150...
Page 4: ...MAHF 125...
Page 77: ...73 A 1 MODEL 75 100 Heat Only APPENDIX A WIRING DIAGRAMS 240013503 REV A 03 15 2022...
Page 78: ...74 A 2 MODEL 125 Heat Only APPENDIX A WIRING DIAGRAMS 240013503 REV A 03 15 2022...
Page 79: ...75 APPENDIX A WIRING DIAGRAMS A 3 MODEL 165 Heat Only 240013503 REV A 03 15 2022...
Page 80: ...76 APPENDIX A WIRING DIAGRAMS A 4 MODEL 115 Combi 240013503 REV A 03 15 2022...
Page 81: ...77 A 5 MODEL 150 Combi APPENDIX A WIRING DIAGRAMS 240013503 REV A 03 15 2022...
Page 82: ...78 A 6 MODEL 205 Combi APPENDIX A WIRING DIAGRAMS 240013503 REV A 03 15 2022...
Page 117: ...33 PN 240012875 REV D 03 15 2022 MODEL 75 100 HEAT ONLY 75 100 HEAT ONLY WIRING DIAGRAM...
Page 118: ...34 PN 240012875 REV D 03 15 2022 MODEL 125 HEAT ONLY 125 HEAT ONLY WIRING DIAGRAM...
Page 119: ...35 PN 240012875 REV D 03 15 2022 MODEL 165 HEAT ONLY 165 HEAT ONLY WIRING DIAGRAM...
Page 120: ...36 PN 240012875 REV D 03 15 2022 115 COMBI WIRING DIAGRAM MODEL 115 COMBI...
Page 121: ...37 PN 240012875 REV D 03 15 2022 MODEL 150 COMBI 150 COMBI WIRING DIAGRAM...
Page 122: ...38 PN 240012875 REV D 03 15 2022 MODEL 205 COMBI 205 COMBI WIRING DIAGRAM...
Page 128: ...44 PN 240012875 REV D 03 15 2022 LOW WATER CUTOFF LOW WATER CUTOFF DETAIL NO NO YES...
Page 133: ...49 PN 240012875 REV D 03 15 2022 3 FAULT SOLUTION SECTIONS...