9.10 De-Aeration Function
Used to eliminate air inside the heating circuit when
boiler is installed or after maintenance when water is
drained from primary circuit.
1.
Press buttons
together and hold for 6
seconds.
On
appears on display for a few seconds,
followed by program row
312
.
2.
The electronic board will activate pump on/off cycle
for 10 minutes. Function will automatically stop at
end of cycle.
3.
To manually exit this function, press
buttons together and hold for 6 seconds.
9.11 Changing The Type Of Gas
If change of gas type is required
after
first installation:
• Change parameter P02. See section 9.6
Commissioning
and
section 9.15
Parameter
Settings.
• Check minimum gas pressure is suitable for selected gas:
Minimum gas pressure is determined with boiler operating
at high fire and any other appliances connected to same fuel
source operational as well (whole house load)
Gas A (NG) = 3.5" (8.7 mbar)
Gas E (LPG) = 8.0" (19.9 mbar)
• Place supplied label with indication of gas type
close
to the data plate of boiler replacing the original.
• Perform Automatic Calibration Function -
Section 9.8.
•
Manufacturer recommends verification of CO2
concentration on the flue.
FIGURE 9-3 - Gas Inlet Tap - Pi
9 - START UP PROCEDURE
PI
PI = Gas Supply Inlet Pressure Tap
PI
IMPORTANT INFORMATION
A. If display shows fault
E118
(low pressure in
hydraulic circuit) open filling tap on appliance and
restore correct pressure.
B. If gas recognition function is interrupted due
to fault (e.g.:
E133
no gas) press
to
reset. Then press
and
(for at least
6 seconds) to restart the function again.
If gas recognition function is interrupted due to
overheating, restart function by pressing and
holding down together for at least 6 seconds.
C. Combustion of this appliance is factory default for
operation to Natural gas.
D. Type is being established.
9.9 Manual Calibration Function:
Manual Calibration phase starts at the end of the
Automatic Calibration.
The Display shows the boiler power and adjustment
of the CO2 value (parameter setting) during Manual
Calibration sequence.
The process begins at minimum power.
A. After Automatic Calibration sequence with
flashing together on the display, you can adjust
minimum power combustion by pressing
to
lower % CO
2
, and
to raise % CO
2
.
B. When minimum power combustion is in the
specified range, press
and then
to reach
ignition power.
C. Press
to adjust ignition power combustion.
Press
to lower % CO
2
, and
to raise % CO
2
.
D.
When ignition power combustion is in the specified
range, press
and then
to reach maximum
power.
E. Press
to adjust maximum power combustion.
Press
to lower % CO
2
, and
to raise % CO
2
.
F. When maximum power combustion is in the
specified range,
press
to exit Manual Calibration
Function.
ESC
is displayed on the screen.
240013503 REV A, [03/15/2022]
Summary of Contents for UTICA BOILERS MACF-115
Page 2: ...MACF 150...
Page 4: ...MAHF 125...
Page 77: ...73 A 1 MODEL 75 100 Heat Only APPENDIX A WIRING DIAGRAMS 240013503 REV A 03 15 2022...
Page 78: ...74 A 2 MODEL 125 Heat Only APPENDIX A WIRING DIAGRAMS 240013503 REV A 03 15 2022...
Page 79: ...75 APPENDIX A WIRING DIAGRAMS A 3 MODEL 165 Heat Only 240013503 REV A 03 15 2022...
Page 80: ...76 APPENDIX A WIRING DIAGRAMS A 4 MODEL 115 Combi 240013503 REV A 03 15 2022...
Page 81: ...77 A 5 MODEL 150 Combi APPENDIX A WIRING DIAGRAMS 240013503 REV A 03 15 2022...
Page 82: ...78 A 6 MODEL 205 Combi APPENDIX A WIRING DIAGRAMS 240013503 REV A 03 15 2022...
Page 117: ...33 PN 240012875 REV D 03 15 2022 MODEL 75 100 HEAT ONLY 75 100 HEAT ONLY WIRING DIAGRAM...
Page 118: ...34 PN 240012875 REV D 03 15 2022 MODEL 125 HEAT ONLY 125 HEAT ONLY WIRING DIAGRAM...
Page 119: ...35 PN 240012875 REV D 03 15 2022 MODEL 165 HEAT ONLY 165 HEAT ONLY WIRING DIAGRAM...
Page 120: ...36 PN 240012875 REV D 03 15 2022 115 COMBI WIRING DIAGRAM MODEL 115 COMBI...
Page 121: ...37 PN 240012875 REV D 03 15 2022 MODEL 150 COMBI 150 COMBI WIRING DIAGRAM...
Page 122: ...38 PN 240012875 REV D 03 15 2022 MODEL 205 COMBI 205 COMBI WIRING DIAGRAM...
Page 128: ...44 PN 240012875 REV D 03 15 2022 LOW WATER CUTOFF LOW WATER CUTOFF DETAIL NO NO YES...
Page 133: ...49 PN 240012875 REV D 03 15 2022 3 FAULT SOLUTION SECTIONS...