80
NOTICE
Perform regular service and maintenance by qualified
service agency at least once every 12 months to assure
safe, trouble free operation and maximum efficiency.
11 - GENERAL MAINTENANCE AND CLEANING
WARNING
Combustion chamber insulation in this product
contains ceramic fiber material. Ceramic fibers can
be converted to cristobalite in very high temperature
applications. The International Agency for Research
on Cancer (IARC) has concluded, Crystalline silica
inhaled in the form of quartz or cristobalite from
occupational sources is carcinogenic to humans
(Group1). Avoid breathing dust and contact with
skin and eyes. Use NIOSH certified dust respirator
(N95). This type of respirator is based on the OSHA
requirements for cristobalite at the time this document
was written. Other types of respirators may be
needed depending on the job site conditions. Current
NIOSH recommendations can be found on the NIOSH
website http://www.cdc.gov/niosh/homepage.html.
NIOSH approved respirators, manufacturers, and
phone numbers are also listed on this website. Wear
long-sleeved, loose fitting clothing, gloves, and eye
protection. Apply enough water to the combustion
chamber lining to prevent dust. Wash potentially
contaminated clothes separately from other clothing.
Rinse clothes washer thoroughly.
NIOSH stated First Aid. Eye: Irrigate immediately.
Breathing: Fresh air.
!
WARNING
Before servicing, turn off electrical power to boiler
at service switch. Close manual gas valve to turn
gas supply OFF to boiler. Test for gas leaks on any
gas carrying components after servicing. Service
not complete until appliance operation verified per
Installation, Operation & Maintenance Manual provided
with boiler.
!
WARNING
Following service procedures must be performed by
qualified service agent. Boiler owner shall not attempt
these steps. Failure to do so could result in death or
serious injury.
!
CAUTION
Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and
dangerous operation. Failure to follow these
instructions could result in minor or moderate injury.
!
11.2 Maintenance And Routine Servicing
Check and service boiler as necessary.
Frequency of servicing will depend upon installation conditions
and usage, manufacturer recommends minimum of annual
inspection or more if required.
•
Check flue terminal outside and ensure it is not blocked.
• Operate boiler. Check operation of boiler's controls.
•
Ensure all system connections and fittings are sound.
Correct any joints and fittings that maybe leaking.
• Follow safety valve manufacturer recommendations for
service.
To ensure boiler operates at peak efficiency, following checks
must be performed every year:
• check the appearance and tightness of the gas and
combustion circuit gaskets
• check the condition and position of the ignition and
flame sensing electrodes
• check the condition of the burner and its connection to
the aluminum front plate
• check for dirt in the combustion chamber, clean if
necessary. Use the vacuum cleaner for this cleaning
operation
• check the gas valve is calibrated correctly
• check that there is no dirt in condensate trap
• check the central heating system pressure
• check the expansion tank pressure
• check the vent system, clean if necessary
• if using glycol mixture, check glycol pH, replace if out
of range
• Check water cleanliness
• Clean dirt separator if used.
Record details and maintain a service history. Leave the
service records with the boiler and the homeowner.
PN 240012363 REV. A [08/31/2018]