EcoSolar Energy Conscious Design Limited
56
13.
Now press the right hand arrow, once CODE32 is displayed press the right hand
arrow and then press the up arrow. Then press the left hand arrow until T1 is displayed on
the screen. Now press the right hand arrow 5 times, ENTER
men
is displayed on the screen.
Press the down arrow Engl should be displayed, this is the language for the programming. If
Engl is not displayed, English should be selected, this is done by pressing the down arrow,
the Engl blinks, now use the left and right hand arrows to change the language and press the
up arrow to select the required language.
14.
Now press the right hand arrow, once CODE 0 is displayed, press the down arrow,
CODE0 blinks, increase the number to 64 by pressing the right hand arrow, then press the
up arrow to select the required code number.
15.
Now press the right hand arrow, SENSOR is displayed, this should not be changed
and should be displaying S1 KTY if the standard sensors have been supplied. If different
sensors are being installed these should be selected under this SENSOR menu screen.
16.
Now press the right hand arrow, SYS PF is displayed, press the down arrow. CET is
displayed. This is to protect the pump and will not turn the pump on if the water
temperature is too high. Press the down arrow, it should be switched ON, now press the
right hand arrow, this is the maximum collector temperature, the temperature at which the
pump will switch off. Leave set at 130
o
C for most cases, change if required using the down
arrow then right hand arrows then select using up arrow. Now press the right hand arrow,
this temperature is also to protect the pump, it is the temperature that the pump turns on
again after having been turned off due to the high temperature limit as described above,
leave set at 110
o
C, change if required using down arrow then right hand arrows then select
using up arrow.
17.
Now press the up arrow, CET is displayed, press the right hand arrow, FROST is
displayed, this is the freeze protection and needs to be initiated for direct systems. It will turn
the pump on at the lower temperature, heat up the collectors and turn the pump off at the
higher temperature. To initiate press the down arrow, OFF is displayed, press the down
arrow and the right arrow to turn on, then the up arrow to select, ON will stop flashing.
Generally set the on temperature to 4deg.C and the off temperature to 7deg.C. With ON
displayed press the right arrow, 2 is displayed, now press the right arrow again, 4 is displayed.
Press the down arrow and increase the number to 6
o
C by pressing the right hand arrow, then
press the up arrow to select the required temperature. Press the left hand arrow, 2 is
displayed, press the down arrow, now the right hand arrow to increase to 4deg.C. Now press
the up arrow to select the temperature.
18.
Now press the up arrow again, FROST is displayed, now press the up arrow again..
Now press the right hand arrow Start f is displayed, this is factory set to off and should
normally remain off
19.
Now press the right hand arrow ART is displayed, this is the after run time for the
pump and is normally is left at 0.