![EcoSmart ECO-3Mini Instruction Manual Download Page 15](http://html.mh-extra.com/html/ecosmart/eco-3mini/eco-3mini_instruction-manual_2355326015.webp)
15
3-7
Temp. & Humidity Advance Setting
Temp. setting up/low range: “default:
±
0.5
°
C “ Set Temp. control range in the ECO-IR
setting screen.
For example, temp. setting up/low range is
±
0.5
°
C and temp. control setting is 27
°
C
in the ECO-IR setting screen. If ambient temp. have risen over 27.5
°
C, ECO-IR will turn
cool mode. If ambient temp. have dropped below 26.5
°
C, ECO-IR will turn fan mode.
Temp. / Humidity offset: Set temp. / humidity offset, if temp. / humidity have error
3-8
Temp. Control Power
According to ambient temp., ECO-IR turns A/C power on/ off automatically.
Step 1. Set up limit temp.: If ambient temp. higher than value, ECO-IR will turn A/C
power on automatically.
Step 2. Set low limit temp.: If ambient temp. lower than value, ECO-IR will turn A/C
power off automatically.
Step 3. Turn switch on