Range 14 

– A2P 

Operating instructions

 

 

ECOSAFE | Date du document : 19/06/2019 – Version : 01 

 

It has to be lifted only by suitable equipment (suct

ion cup, strap…). It has to be carried in a vertical position, and it must not be lying.  

It is imperative not to tilt the cabinet when it is carried. Indeed it can cause damages that can alter the right functioning of the cabinet.  

On the other hand, if it has to be moved, the cabinet has to be placed on a pallet and strapped, as to avoid any fall.  

 

Commissioning 

 

After having unwrapped the cabinet, ensure that you also received a set of two keys.  

Your safety cabinet has to be installed, used and maintained as to guarantee the users protection.  

 

4.  INTERNAL EQUIPMENTS 

 

The cabinet is provided with 4 retention shelves and 2 retention tanks. The retention capacity per shelf is 7 liters and per retention tank 

25 liters.  

Take care not to exceed the loading capacity per shelf of 50 KG.  

The shelves must be fixed at the chosen height thanks to the rack and pinion. 

 

5.  STORAGE 

 

Your safety cabinet is exclusively destined to store low risk chemicals in laboratories, industries, schools

… in closed containers.  

It must not store high concentrated corrosive products or very flammable products.  

We remind  you  that  the  storage  of corrosives  can  alter  the  quality  of  your safety  equipment.  On  the  other  hand,  we  remind  you  that 

damages due to a bad use of the equipment and in particular to corrosion won

’t be covered by our warranty.  

 

6.  VENTILATION 

 

We highly recommend connecting your safety cabinet to a ventilation system, as to evacuate the eventual vapors contained in it.  

The air renewal has to be at least 10 times the volume of the cabinet, per hour. Moreover, ensure that the ventilation runs 24h/7.  

 

Connection to a ventilation system 

The air inlets are situated at the bottom, on the doors ; the outlet is situated on the top. See the schema below.  

Summary of Contents for A2P

Page 1: ...Range 14 A2P Operating instructions ECOSAFE Date du document 19 06 2019 Version 01 0 Instruction manual For safety cabinet Model A2P ...

Page 2: ...ONTENT 1 Description Use Page 2 2 Technical features Page 2 3 Installation and commissioning Page 2 4 Internal equipments Page 3 5 Storage Page 3 6 Ventilation Page 3 7 Safety controls Page 4 8 Spare parts Page 5 9 Recycling Page 5 10 Warranty Page 5 11 Control sheet for the user Page 7 ...

Page 3: ...s H 1825 x W 560 x D 545 mm Storage capacity 110 liters 2x 55L Retention capacity 70 liters 2x 35L Loading capacity 50 KG per shelf Weight 85 KG 3 INSTALLATION AND COMMISSIONING Installation The safety cabinet has to be installed on a flat surface that can bear its weight with the products inside Ensure that the safety cabinet is correctly wedged as for the cabinet not to topple The eventual block...

Page 4: ...n tank 25 liters Take care not to exceed the loading capacity per shelf of 50 KG The shelves must be fixed at the chosen height thanks to the rack and pinion 5 STORAGE Your safety cabinet is exclusively destined to store low risk chemicals in laboratories industries schools in closed containers It must not store high concentrated corrosive products or very flammable products We remind you that the...

Page 5: ... a healthy fashion Filtration boxes are delivered with the activated carbon filter that you need to renew once a year Running without any mechanic ventilation It is possible for your safety cabinet to run without mechanical ventilation However your cabinet has to be placed in a location that provides its own ventilation system at least 5 times the volume of the location per hour The cabinet itself...

Page 6: ...ous elements such as the steel can be recycled Ensure to respect the national and local waste disposal terms Those elements should not be mixed with household waste 10 WARRANTY Your equipment holds a 12 months warranty against every manufacturing defect limited to ordinary conditions of use from the date indicated on the delivery note Our warranty can be applied only in case of manufacturing defec...

Page 7: ...mal attrition of the equipment In case of a bad installation of the equipment In case of damage caused by the corrosion The activation of the warranty won t extend the term Our warranty stops if the customer has not notified us in a 7 days term after seeing the fault date that the customer has to prove ...

Page 8: ...cking system of the doors works correctly The mechanic ventilation system is running correctly if applicable The ventilation system is not obstructed The air inlets and outlet are clean The standardized pictogram on the door is in good condition and visible The door hinges are lubricated The locking system is lubricated The shelves and the retention tanks are clean Remarks Date By Signature ...

Reviews: