9.

 

CALIBRATIONS 

 

9.1

 

L

IMIT SWITCH

 

 

9.1.1

  The MPV valve is delivered by the factory in closed position. The limit switches 

are adjusted to reach the positions of closed valve and completely open valve. 

 

9.1.2

  For “OPEN” position adjustment, it is necessary to operate on cam “S2”. 

 

9.1.3

  For cam adjustment, use the proper “half-moon” key, supplied with the 

actuator and installed inside it. 

 

9.1.4

  Use the key from the right side, introducing the pin into one of the holes on 

the sides of the blue cam of the cam involved and lever it to required position.  

 

9.1.5

  If the blue cam is in a behind position, use at first the lever on its curved side 

to move the blue cam to a more suitable position to perform adjustment 
[picture 1]. 

 
 
 

 
 
 
 
 
 

 
 
 
 
 

 
 
                                                         Picture 1 
 

9.1.6

  To calibrate, refer to the mechanical position indicator disc; the valve is closed 

when the mechanical pointer is in the 0 position, the valve is completely open 
when the mechanical pointer is in the 90° position. 

 

9.1.7

  The cam adjustment is possible in both directions. 

 

9.1.8

  The lever roller operates the microswitch when it is on the bottom of the cam 

groove, stopping the motor rotation. 

 

9.1.9

  Remove the wrench before starting the actuator. 

 

9.1.10

 The movable crown can be driven also by a small screwdriver, acting on the 

suitable notches. 

 

9.1.11

 Avoid valve rotation over 90°, in order to prevent damage on the adjusting 

cylinder, and/or force the potentiometer shaft rotation. 

Summary of Contents for MPV Series

Page 1: ...IC CONNECTIONS 4 5 WIRING 5 5 1 WITHOUT MANUAL AUTOMATIC CONTROL STATION 5 5 2 WITH MANUAL AUTOMATIC CONTROL STATION 6 6 AUXILIARY MICROSWITCHES 7 7 POTENTIOMETER S 7 8 CONTROL STATION 7 9 CALIBRATION...

Page 2: ...g conditions interchangeable without removing he valve from the plant WARNING Installation wiring adjustment and maintenance of gear motors must be carried out exclusively by skilled and authorized se...

Page 3: ...ions 3 5 Remove the protection plugs installed on the valve body 3 6 The sealant must be applied only on the piping outer threading and not on the valve inner threading Use gas suitable sealants only...

Page 4: ...es must comply with local prescriptions and in any case their section must be ranging between 1 and 1 5 mm2 Connection piping recommended H07V U G1 5 mm2 4 6 Wiring diagrams are reported in the attach...

Page 5: ...ATION TERMINAL BOARD Terminal earthing Terminal N1 N neutral Terminal L2 by tension the valve closes Terminal 3 by tension the valve opens Terminal 4 for manual electric operation Terminal 16 answer s...

Page 6: ...0 common contact from the auxiliary microswitch S3 Terminal 21 normally open contact of the auxiliary microswitch S3 Terminal 22 normally closed contact of the auxiliary microswitch S3 Terminal 23 com...

Page 7: ...e does not correspond to the wished one proceed as indicated in paragraph 9 2 of chapter 9 CALIBRATIONS Absorbed power is 2 W for each potentiometer 8 CONTROL STATION 8 1 The control station enables t...

Page 8: ...rst the lever on its curved side to move the blue cam to a more suitable position to perform adjustment picture 1 Picture 1 9 1 6 To calibrate refer to the mechanical position indicator disc the valve...

Page 9: ...een terminals n 34 and 35 when the valve is closed picture 2 Picture 2 9 2 4 By rotating the potentiometer clockwise 3 the resistance value increases counter dock wise 4 the resistance value decreases...

Page 10: ...echanically 9 3 7 Select the AUTO position 9 3 8 Set the adjustment device on 6 mA or on 2 Vdc and wait up the servocontrol moves then take it back to 4 mA or on 0 Vdc and check it reaches 0 degrees 9...

Page 11: ...cock can be opened and the operating test can be carried out 11 MAINTENANCE AND CHECKS 11 1 The MPV valve does not require any special maintenance Both the valve body and the actuator do not need any...

Reviews: