Ecolab GEOCENTER Installation And Operation Manual Download Page 10

6" MIN (uS)

30 cm (INT'L)

w

AT

ER FLOw

Visual Flow 

Indicator

1/8"  

TuBE

1" x 1/4" OD 

TuBE

TuBE CLAMP

INDICATOR TuBE

TuBE CLAMP

1" x 1/4" OD 

TuBE

1/8"  

TuBE

Figure 4-3

4.7  Geosystem rinse Dispenser

1.  Install the Geosystem Rinse Dispenser following the 

installation instructions provided for that unit.

4.8  rinse Injector connections

Identify the point at which rinse additive will be injected into 

the final rinse line, 

refer to Figure 4-3.

NOTE: The injection point has to be installed a minimum 

of 6" (15.2 cm.) below the vacuum breaker with the cabinet 

mounted at or below that point. In many International 

accounts the minimum distance beneath the vacuum 

breaker is 30 cm. (11.8"). Install fitting using Teflon tape 

or pipe sealant to prevent leakage.

4.9  Hydraulic  connections  and  Visual  flow 

Indicator

1.   Connect 1/8" product discharge tubing between the outlet 

of the pump squeeze tube and visual flow indicator, 

refer 

to Figure 4-3.

Note: The visual flow indicator is required for NSF 

listing.

2. 

Assemble the Visual Flow Indicator by inserting the 1/8" 

tube fully into one of the two 1" sections of 1/4" OD x 

1/8" ID PVC tubing provided.

3.  Insert this injection tubing assembly fully into the outlet 

end  of  the  Flow  Indicator  tube,  also  called  the  sight 

tube.

4.  Secure all connections with the clamps provided.
5.  Complete the outlet of the Visual Flow Indicator in the 

same manner and extend the 1/8 tubing to the check 

valve and injection fitting. 

Refer to Figure 4-3.

IMPORTANT: When the product is being injected into 

the final rinse line, movement of the product will be 

visible in the flow indicator tube. The dishmachine 

operator must be instructed to observe the Flow 

Indicator periodically to insure that product is in 

fact being dispensed.

6.   Trim and connect the 1/8" product pick-up tubing supplied 

with the rinse injector to the inlet side of the pump

.

7.   Connect 1/4" O.D. copper tubing from the water source to 

the inlet side of the solenoid valve located at the bottom 

on the GeoCenter cabinet, 

refer to Figure 4-4.

8.  Connect 1/4" O.D. copper tubing from the outlet side of the 

solenoid valve to the Geosystem Detergent Dispenser. 

Refer to the Installation and Operation Manual

 of the 

Geosystem  Detergent  Dispenser  used  to  determine 

wATER IN

SOLENOID

VALVE

TO GEOSYSTEM

DETERGENT

DISPENSER

VACuuM

BReAKeR

INJECTION

FITTING

CHeCK

VALVE

PRESSuRE

SWITCH

TO

GEOSYSTEM

RINSE

DISPENSER

Figure 4-4

Summary of Contents for GEOCENTER

Page 1: ...GEOCENTER Installation and Operation Manual Dispenser Complete 9223 1091 26392 0406 0409 Copyright Ecolab Inc 2009 9223 2610...

Page 2: ...This page intended to be blank...

Page 3: ...lation 5 4 6 VANGUARD Wash Max Installation 5 4 7 Geosystem Rinse Dispenser 6 4 8 Rinse Injector Connections 6 4 9 Hydraulic Connections and Visual Flow Indicator 6 5 0 ELECTRICAL CONNECTIONS 7 5 1 Tr...

Page 4: ...13 9 3 Unit does not feed Power Light on Feed Light not on 14 9 4 Feeds continuously Feed Light not on 14 9 5 Feeds continuously Feed Light on 14 9 6 Fluctuating titration 15 9 7 Excessive detergent c...

Page 5: ...ines will be suggested in reference to the preferred method of installation however the variety of equipment and the surrounding physical environment will dictate the actual installation of the GeoCen...

Page 6: ...ergent when wash tank concentration is near the desired control point Visual indicators signal concentration status of the wash tank A FEED light will illuminate when concentration is below the set le...

Page 7: ...a 440 volt installation IMPORTANT Make sure the power source is turned off 3 1 Dimensions Height H 7 5 8 19 4 cm Width W 11 3 8 28 9 cm Depth D 6 3 8 16 2 cm Weight 12 LB 5 4 kg 3 2 Access Requiremen...

Page 8: ...inimum 14 GA 600 volt insulated wire Wiring from the power source to the transformer must be enclosed in conduit seal tite or other housing approved for damp locations 3 5 Plumbing Requirements Water...

Page 9: ...er to Figure 4 1 Attach to plastic GeoCenter enclosure with 8 32 x 5 16 screw in kit bag Ground using green yellow wire 4 3 Mounting the GeoCenter 1 Mount the GeoCenter cabinet to the wall using the s...

Page 10: ...ID PVC tubing provided 3 Insert this injection tubing assembly fully into the outlet end of the Flow Indicator tube also called the sight tube 4 Secure all connections with the clamps provided 5 Comp...

Page 11: ...SOLID RINSE RESERVOIR RED BLACK GREEN WHITE HI S26 ON 10 11 12 13 14 15 16 17 18 19 20 21 22 23 OFF FEED ALARM VOLUME ALARM DELAY TITRATION ALARM 100 POWER LED LED JP2 FEED OFF FEED ADJUST 5 0 ELECTR...

Page 12: ...ductor cable between the GeoCenter and Detergent units At the GeoCenter Refer to Figure 5 1 on page 7 Wire nut the leads from the 2 conductor cable to the two WHITE wires provided with the wire nuts 5...

Page 13: ...8 16 32 64 APPROX STANDARD DROPS 1 2 4 8 16 32 When multiple positions are ON the detergent controller will add all positions together to achieve the desired tank concentration Example using Standard...

Page 14: ...ntrol the injection rate of the rinse additive can be controlled throughout the entire rinse cycle refer to Figure 6 2 Injection rate can also be adjusted by use of alternate sized squeeze tubes INJEC...

Page 15: ...limitations in sensor technology the thermistor in the S 2000 sensor responds slowly to changes in wash tank temperature Under certain conditions this slow response can cause the detergent controller...

Page 16: ...away from pump body until tubes slips over the rollers 4 Clean inside of pump body wiping to remove particle matter and accumulation of old lubricant 5 Inspect the roller assembly closely for signs o...

Page 17: ...at valve coil if present a Check for water to the valve b Disconnect the outlet tubing from the valve If water flowsthruthevalve checkforplugorrestrictionintubing to the reservoir or in the reservoir...

Page 18: ...lly increasing If not there is no detergent being delivered to the machine or the detergent is not feeding into the wash tank Check for proper water flow to the dispenser properoperationofthedispenser...

Page 19: ...wn wire from terminal 15 and readjust the titration according to section 7 4 If titrations stabilize use this setting for operation 3 Check for signs of moisture contamination on the de tergent contro...

Page 20: ...air leaks 2 Check for high rinse pressure optimum is 15 20 psig 1 1 4 BAR and cannot be over 35 psig 2 4 BAR 3 Check squeeze tube for wear and cracks etc 1 Lubricate use only silicon grease lubricate...

Page 21: ...ER W CELL PKD INJECTOR CONTROL BOARD 9217 0042 1 4 TO 1 8 REDUCING TUBE 1 5 9218 0884 SQUEEZE TUBE 1 4 cc 9217 0125 SQUEEZE TUBE 1 8 cc standard 9218 0892 SQUEEZE TUBE 1 2 cc 9218 0900 SQUEEZE TUBE 1...

Page 22: ...nse injector On these machines a constant power source L1 L2 is applied to the injector transformer and a rinse pressure switch will have to be installed The rinse injector will then be activated when...

Reviews: