Installation Manual and Owner’s Guide WHO-321064-NG, WHO-321064-LP
ECOHOT
TM
8 of 27
Gas Piping, Connections and Gas Regulator
Before connecting the gas supply, check the rating plate on the right side of the right front cover to
be sure that the heater is rated for the same gas to which it will be connected.
In the Applianceed States: The installation must conform with local codes or, in the absence of local
codes, the National Fuel Gas Code ANSIZ223.1/NFPA54.
In Canada: The installation should confirm with CGAB149 INSTALLATION CODES and/or local
installation codes.
Gas Line Sizing:
The gas supply piping should be sized according to the Applicable Plumbing Code for a maximum
draw of 218,000 BTU. First determine the effective length of the gas supply line by measuring the
actual length of piping, and then adding 5 ft. for every elbow or “T” to the actual length. Use the
charts below to determine the pipe diameter necessary to accommodate the BTU demand of the
appliance. If there is more gas drawing appliances on the line, size according to the maximum
amount of BTU demand.
Maximum
Natural Gas
Delivery Capacity in Cube Feet per Hour(0.60 Specific Gravity, 0.5”WC
Pressure Drop)
Pipe
Size
Length in Feet
10’
20’
30’
40’
50’
60’
70’
80’
90’
100’
125’
½”
174
119
96
82
73
66
61
56
53
50
44
¾”
363
249
200
171
152
138
127
18
111
104
93
1”
684
470
377
323
286
259
239
222
208
197
174
1 ¼”
1404
965
775
663
588
532
490
456
428
404
358
1 ½”
2103
1445
1161
993
880
798
734
683
641
605
536
2”
4050
2784
2235
1913
1696
1536
1413
1315
1234
1165
1033
2 ½”
6455
4437
3563
3049
2703
2449
2253
2096
1966
1857
1646
3”
11412 7843
6299
5391
4778
4329
3983
3705
3476
3284
2910
*Contact the Gas Supplier for Btu/Cubic Ft. of the Supplied Gas.
The formula for figuring the cubic feet per hour required is:
Gas Input of Water Heater(BTU/HR)
CFH = --------------------------------------------------
Heating Value of Gas(BTU/Cubic FT)
Maximum Liquified Petroleum(Undiluted) delivery Capacity in Thousand of Btuh(0.5” WC
Pressure Drop)
Pipe
Size
Length in Feet
10’
20’
30’
40’
50’
60’
70’
80’
90’
100’ 125’ 150’ 200’
½”
275
189
152
129
114
103
96
89
83
78
69
63
55
¾”
576
693
315
267
237
217
196
185
173
162
146
132
112
1”
1107
732
590
504
448
409
378
346
322
307
275
252
213
1 ¼”
1220
1149
1121
1103
913
834
771
724
677
630
567
511
440
1 ½”
1330
1229
1185
1155
1141
1127
1118
1108
1102
976
866
787
675
2”
1622
1433
1346
1299
1264
1239
1220
1204
1192
1811
1606
1496
1260
**For reference only. Please consult gas pipe manufacture for actual capacities.
This chart is only for Black Iron piping and is only for ECOHOT Water Heater at high fire
condition.
High Altitude Operation
For high altitude installations in Canada above 2,000 Ft to 4,500 Ft, this water heater's Gas Supply