35
3.14.
In the event of a possible fire in the gas outlet, the boiler will turn itself off due to excess gas outlet
temperature. To prevent this situation, respect the indications that are marked in section 5 on the
installation of the gas outlet and regulations for boiler rooms, gas installations and fuel storage.
3.15.
The hydraulic circuit must always keep open a dissipation circuit greater than 30% of the total installation to
avoid overpressures and / or overtemperatures.
3.16.
For the project, the specific calculation for the placement of an expansion vessel must be carried out.
3.17.
Depending on the material used for the hydraulic circuit, consider using an electrolytic sleeve.
The equipment must be connected to the piping by means of flexible connections. The UNE 100153-88
standard is a good aid for the selection criteria of anti-vibration mounts.
3.18.
It is highly advisable to perform regular checks to assess the quality of the water in the system, especially if
more water is being added. If you use a water treatment product, make sure it is compatible with the
materials used in the heating installation. To do so, please contact the product’s manufacturer.
3.19.
The electronic management of the supply and return temperature of the hydraulic circuit prevents the
occurrence of condensation, making unnecessary the placement of anti condensation systems.
3.20.
As we are going to use an external fuel accumulation system, the manufacturer's installation regulations,
loading ports, safety distances, etc. must be respected, as well as local, national and / or European
regulations. in Spain for example the technical building regulations (RITE) in which the characteristics of said
tank are specified.
For further information on this assembly, see the manual for the pneumatic vacuum cleaner, as well as the
assembly in the installation section.
3.21.
All electrical connections, with the exception of the pellet vacuum cleaner, must be made at the electrical
connection strip. The correspondence of the nomenclatures is in the point of electrical diagram.
EN CASO DE INCENDIO EN LA SALIDA DE GASES:
Observe the boiler room regulations of the building and project regulations.
The stove will shut off automatically due to over-temperature gas output.
Call the fire department.
Consult your dealer before restarting the stove
HYDRAULIC.
3.22.
The appliance is intended to be permanently connected to water main with a normally closed valve; do not
use a hose-set.