background image

La ECOFLAM S.p.A si riserva il diritto di apportare ai prodotti quelle modifiche che riterrà necessarie o 
utili, senza pregiudicarne le caratteristiche principali.

Ecoflam S.p.A.
via Roma, 64 - 31023 RESANA (TV) - Italy - tel. 0423/715345 r.a.
telefax 0423-715444 (Italy 480009 - Export 480873, 715538).
http://www.ecoflam.it  -  e-mail: [email protected]

DESIGN AND SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE

Summary of Contents for OILFLAM 700.1 PR/MD

Page 1: ...techniques for energy saving MODEL HEAVY OIL BURNERS OILFLAM 700 1 PR MD OILFLAM 800 1 PR MD AIR DAMPER MOTOR 230 400 V 50 Hz LB 1312 03 02 2005...

Page 2: ...1 PR MD Thermal power max kcal h 6 250 000 7 327 500 kW 7 250 8 500 Thermal power min kcal h 2 096 270 2 385 100 kW 2 417 2 750 Oil capacity max kg h 638 748 Oil capacity min kg h 214 243 Max viscosit...

Page 3: ...660 820 455 1240 425 800 480 460 460 M20 D Short head D1 Long head LB1312 Oilflam 700 1 800 1 PR MD pag 3 OIL PUMP 1 Suction 2 Return 3 Bleed and pressure gauge port 4 Vacuum gauge port 5 Pressure adj...

Page 4: ...ent burner start up it is advisable to carry out the following checks Power line must be adequate to system s adsorbed load Fuses must be adequate to the system s load Boiler s thermostats must have b...

Page 5: ...r heavy fuel oil up to 50 E at 50 C Hot water Return hot water pipe hot water pipe oil pipe oil pipe heating cable insulation section 1 Burner 2 Tank 3 Heater 4 Safety operation thermostat 5 Level swi...

Page 6: ...the cyclic control programmer cutting in Once ignition has taken place and after the flame stabilisation period the system starts operating in modulating mode Before start up make sure that the pump a...

Page 7: ...pag 7 LB1312 Oilflam 700 1 800 1 PR MD...

Page 8: ...pag 8 LB1312 Oilflam 700 1 800 1 PR MD FLUIDICS NOZZLE...

Page 9: ...I H E G N A D F Q P PRE PURGING PHASE LEGEND A Solenoid valve N C D Regulator E Tank F Anti gas valve G Resistance of the preheather H Pipe filter I Oil pump N Manometr O Resistance of combustion hea...

Page 10: ...ower The temperatures are already properly Factory setted LANDIS SQM 50 481A2 Remove cover to gain access to the adjusting cams The cams are to be adjusted through the suitable key provided Descriptio...

Page 11: ...temperature press increase or decrease button after confirm the new value pressing again F if You need to modify an other temperature press again F untill You the relevant led flashes Please take care...

Page 12: ...OSE 1st Stage Increase power OPEN 2nd Stage Two stage operation Description of display and keys on the RWF 40 microprocessor regulator The figure shows the normal display indicating the actual value a...

Page 13: ...to access the parameters level To move from one parameter to the next press PGM PGM When HYS1 is displayed burner ignition differential stage II increase or decrease the value using the and keys Confi...

Page 14: ...1 Connection for probe QAE2 passive probe Water probe Configuration code C111 9XXX Connection for probe FT TP passive probe Degusa probe Configuration code C111 5XXX Connection for probe QBE620 P acti...

Page 15: ...faulty the regulator will not indicate the real value Situation The number 1999 blinks in the display as the actual value with SP E showing in the set point field Cause The external set point value is...

Page 16: ...relative opening in the electrical panel A Insert the fixing anchors and screws into the slots and secure the unit to the panel B To open the regulator squeeze the cover from the ends as shown and li...

Page 17: ...ve probe QBE620 P QAE22 FT TP 1000 P4 P10 P16 P25 P40 Analog input 1 2 and 3 setpoint changeover shift C111 9030 5030 G000 G000 G000 G000 G000 Limit comparator controller type setpoint 1 locking C112...

Page 18: ...0 T P T P QBE620 P GL M U1 22 24 23 9 19 20 21 3 1 2 6 5 4 M1 LANDIS RWF 40 L N Q Q14 Y2 Y1 Q13 G G B9 U1 G1 M9 RELASE 9 0 CONSENSI PREOVENIENTI DAL POTENZIOMENTRO DEL MOTORIDUTTORE SAMA 1 2 3 0 KMRLI...

Page 19: ...DATA FIRMA COMUNICARE A TERZI IL CONTENUTO DEL PRESENTE A TERMINE DI LEGGE E VIETATO RIPRODURRE O CONTROLLO DI TENUTA APPARECCHIATURA UFF TECNICO SETTORE ELETTRICO DENOMINAZIONE SIST RIVELAZ CODICE IN...

Page 20: ...THERMIQUE MOTEUR VENTILATEUR RELE TERMICO MOTOR VENTILADOR FUSE FUSIBLE FUSIBLE ANTJAMMING FILTER FILTRE ANTIPARASITES FILTRO DE PROTECION ANTIDISTURBIO MOTOR FAN MUTEUR VENTILATEUR MOTOR VENTILADOR M...

Page 21: ...60 75 90 0 I 0 AUTO OIL RESET 20 21 19 22 FIN D FIN D FIN DER FIN DER 12 10 11 16 15 17 13 K6 RWF 40 PGM PGM EXIT EXIT 23 24 18 14 26 27 70 60 61 62 31 64 65 63 59 1 3 58 2 36 34 35 33 71 72 73 54 55...

Page 22: ...RESET SWITCH 23 FUSE HOLDER 24 LAMP 319017030SGREEN E1507 2 319010010S RED E1507 25 PLUG WIELAND E222 26 IGNITION TRANSFORMER BRAHMA T8 T101 27 PHOTORESISTOR LANDIS A207 1 28 FAN RU 560 M d 42 BFV104...

Page 23: ...N BFV10203 4 62 COUPLING BFV10203 3 63 COUPLING BFV10201 1 64 UNION PUMP BFV10201 6 65 COUPLING PUMP BFV10201 2 66 GAS VALVE BRAHMA EG12S V142 67 COIL BRAHMA EG12S 68 GAS VALVE BRAHMA EG12SR V142 1 69...

Page 24: ...cessarie o utili senza pregiudicarne le caratteristiche principali Ecoflam S p A via Roma 64 31023 RESANA TV Italy tel 0423 715345 r a telefax 0423 715444 Italy 480009 Export 480873 715538 http www ec...

Reviews: