- pag.13 -

LB1312  

Oilflam 700.1-800.1 PR/MD

SETTING PARAMETERS

When the burner is ignited all displays of the regulator light up.  The set point display will blink for about 10 seconds.  The value
in the upper field of the display (red) indicates the actual value.  The value in the lower field of the display (green) indicates the set
point currently programmed. 

CHANGING THE SET POINT

To change the set point, proceed as follows: 

--

--

Press the 

PGM

PGM

button to access the user level. SP1* will appear in the lower display

--

--

  

  

Change the value of set point SP1 using the t and s keys.

.

--

--

  

  

After a 2 second delay the value set is stored automatically – To

return to normal display press 

EXIT

EXIT

**

The value of SP1 depends on the value set previously in configuration level 

C111

.

SETTING PID PARAMETERS

PID parameters are factory set to standard mean values.  The operation of the regulator can be self-adapted to suit the system by
activating the “tunE” function. The regulator will set the PID parameters automatically.  To activate the “tunE” function proceed
as follows:  

--

--

  

  

With the burner in operation, press  

PGM 

PGM 

--

--

  

  

the caption “tunE*” will blink in the display. – When “tunE” stops

blinking, the self-adaptation routine has been completed. 

--

--

  

  

Confirm the computed parameters by pressing the 

key for 2 seconds. 

**  

The “tunE” function cannot be activated in Manual mode, or when the burner is off. 

The PID parameters can be corrected manually from the parameters level, working on the proportional band Pb1, the
derivative action time dt and the integral action time rt. 

To change parameters Pb1, dt and rt, proceeds as follows: 

--

--

  

  

Press the 

PGM

PGM

button to access the parameters level. 

--

--

  

  

To move from

one parameter to the next, press 

PGM

PGM

--

--

  

  

When 

Pb1

is displayed, the value can be increased or decreased using the s and t keys.  

--

--

Confirm the changed parameters by pressing 

PGM

PGM

--

--

  

  

If confirmation is not given within 2 seconds the value will be stored

automatically. 

--

--

  

  

Press 

PGM

PGM

to access the next parameter. 

--

--

  

  

When dt is displayed, repeat the procedure described above. 

--

--

  

  

Press

PGM to access the next parameter. 

--

--

  

  

When rt is displayed, repeat the procedure above. 

--

--

  

  

To return to normal display press  

EXIT

EXIT

DIFFERENTIAL SETTING FOR IGNITION AND SHUTOFF
The regulator allows the selection of an adjustable switching differential that establishes burner ignition and shutoff values.
HYS1 indicates the lower ignition limit, below which the regulator switches the burner to maximum power.  HYS3 indicates
the upper shutoff limit, above which the regulator switches the burner off.  To set HYS1 and HYS3 proceed as follows: --

--

  

  

Press

the 

PGM

PGM

key to access the parameters level. 

--

--

  

  

To move from one parameter to the next, press 

PGM

PGM

--

--

  

  

When 

HYS1

is displayed

(burner ignition differential-stage II), increase or decrease the value using the 

and 

keys. 

--

--

  

  

Confirm the changed parameters by

pressing 

PGM

PGM

--

--

  

  

If confirmation is not given within 2 seconds the value will be stored automatically. 

--

--

  

  

Press 

PGM

PGM

to access the

next parameter. 

--

--

  

  

When 

HYS2

is displayed (burner shutoff differential-stage II), repeat the procedure described above. 

--

--

  

  

Press

PGM

PGM

to access the next parameter. 

--

--

  

  

When 

HYS3

is displayed (upper shutoff differential) repeat the procedure described above. 

--

--

  

  

To return to normal display press 

EXIT

EXIT

MANUAL/AUTOMATIC MODE

To access “MANUAL” mode, press and hold 

EXIT

EXIT

for at least 5 seconds.  Manual mode can only be selected when the burner is

in operation.  It is deactivated automatically when the burner shuts off.  When the LED above the hand symbol is alight, the
regulator is in manual mode and the position of the servocontrol can be changed using the 

and 

keys. The LEDS on the front

of the regulator indicate whether the servocontrol OPEN or CLOSE command is currently active.  Pressing the 

key the

servocontrol OPENS. Pressing the 

key the servocontrol CLOSES.  To select automatic mode press and hold 

EXIT

EXIT

for at least 5

seconds.  The LED above the hand symbol goes out and the regulator reverts to automatic. 

CLIMATIC COMPENSATION

The RWF 40 regulator can be set with the set point interlocked to the external probe.  To select this operating mode, proceed as
follows:  

--

--

  

  

Connect the required probe as in the wiring diagram.  

--

--

  

  

Change the regulator settings.  When using an external probe

the regulator must be set as follows:  

--

--

  

  

Press the 

PGM

PGM

key to access the configuration level.  When the caption 

C111

(XXXX) is

displayed, use the 

key to access the second figure (XXXX).  Use the 

key to select the type of probe (XX3X).  

--

--

  

  

Confirm the

change of  parameters by pressing 

PGM

PGM

.  If this is not done within 2 seconds, the value is stored automatically  

--

--

  

  

Press 

PGM

PGM

to

access the configuration level.  When the display reads 

C112

(XXXX), use the 

key to access the second figure (XXXX).  Press the

key to set the type of probe (XX3X).  

--

--

  

  

Confirm the changed parameters by pressing 

PGM

PGM

.  

--

--

  

  

If confirmation is not given

within 2 seconds the value will be stored automatically.  

--

--

  

  

To return to normal display press 

EXIT

EXIT

. To establish the heating curve, proceed as follows: 

--

--

  

  

Press 

PGM

PGM

to access the parameters level.  

--

--

  

  

Press 

PGM

PGM

to move from one parameter to the next.  

--

--

  

  

When the letter H is

displayed (heating curve gradient), increase or decrease the value using the 

and 

keys.  

--

--

  

  

Confirm the changed parameters by

pressing 

PGM

PGM

.  

--

--

  

  

If confirmation is not given within 2 seconds the value will be stored automatically.  

--

--

  

  

To return to normal display press 

EXIT

EXIT

.

Summary of Contents for OILFLAM 700.1 PR/MD

Page 1: ...techniques for energy saving MODEL HEAVY OIL BURNERS OILFLAM 700 1 PR MD OILFLAM 800 1 PR MD AIR DAMPER MOTOR 230 400 V 50 Hz LB 1312 03 02 2005...

Page 2: ...1 PR MD Thermal power max kcal h 6 250 000 7 327 500 kW 7 250 8 500 Thermal power min kcal h 2 096 270 2 385 100 kW 2 417 2 750 Oil capacity max kg h 638 748 Oil capacity min kg h 214 243 Max viscosit...

Page 3: ...660 820 455 1240 425 800 480 460 460 M20 D Short head D1 Long head LB1312 Oilflam 700 1 800 1 PR MD pag 3 OIL PUMP 1 Suction 2 Return 3 Bleed and pressure gauge port 4 Vacuum gauge port 5 Pressure adj...

Page 4: ...ent burner start up it is advisable to carry out the following checks Power line must be adequate to system s adsorbed load Fuses must be adequate to the system s load Boiler s thermostats must have b...

Page 5: ...r heavy fuel oil up to 50 E at 50 C Hot water Return hot water pipe hot water pipe oil pipe oil pipe heating cable insulation section 1 Burner 2 Tank 3 Heater 4 Safety operation thermostat 5 Level swi...

Page 6: ...the cyclic control programmer cutting in Once ignition has taken place and after the flame stabilisation period the system starts operating in modulating mode Before start up make sure that the pump a...

Page 7: ...pag 7 LB1312 Oilflam 700 1 800 1 PR MD...

Page 8: ...pag 8 LB1312 Oilflam 700 1 800 1 PR MD FLUIDICS NOZZLE...

Page 9: ...I H E G N A D F Q P PRE PURGING PHASE LEGEND A Solenoid valve N C D Regulator E Tank F Anti gas valve G Resistance of the preheather H Pipe filter I Oil pump N Manometr O Resistance of combustion hea...

Page 10: ...ower The temperatures are already properly Factory setted LANDIS SQM 50 481A2 Remove cover to gain access to the adjusting cams The cams are to be adjusted through the suitable key provided Descriptio...

Page 11: ...temperature press increase or decrease button after confirm the new value pressing again F if You need to modify an other temperature press again F untill You the relevant led flashes Please take care...

Page 12: ...OSE 1st Stage Increase power OPEN 2nd Stage Two stage operation Description of display and keys on the RWF 40 microprocessor regulator The figure shows the normal display indicating the actual value a...

Page 13: ...to access the parameters level To move from one parameter to the next press PGM PGM When HYS1 is displayed burner ignition differential stage II increase or decrease the value using the and keys Confi...

Page 14: ...1 Connection for probe QAE2 passive probe Water probe Configuration code C111 9XXX Connection for probe FT TP passive probe Degusa probe Configuration code C111 5XXX Connection for probe QBE620 P acti...

Page 15: ...faulty the regulator will not indicate the real value Situation The number 1999 blinks in the display as the actual value with SP E showing in the set point field Cause The external set point value is...

Page 16: ...relative opening in the electrical panel A Insert the fixing anchors and screws into the slots and secure the unit to the panel B To open the regulator squeeze the cover from the ends as shown and li...

Page 17: ...ve probe QBE620 P QAE22 FT TP 1000 P4 P10 P16 P25 P40 Analog input 1 2 and 3 setpoint changeover shift C111 9030 5030 G000 G000 G000 G000 G000 Limit comparator controller type setpoint 1 locking C112...

Page 18: ...0 T P T P QBE620 P GL M U1 22 24 23 9 19 20 21 3 1 2 6 5 4 M1 LANDIS RWF 40 L N Q Q14 Y2 Y1 Q13 G G B9 U1 G1 M9 RELASE 9 0 CONSENSI PREOVENIENTI DAL POTENZIOMENTRO DEL MOTORIDUTTORE SAMA 1 2 3 0 KMRLI...

Page 19: ...DATA FIRMA COMUNICARE A TERZI IL CONTENUTO DEL PRESENTE A TERMINE DI LEGGE E VIETATO RIPRODURRE O CONTROLLO DI TENUTA APPARECCHIATURA UFF TECNICO SETTORE ELETTRICO DENOMINAZIONE SIST RIVELAZ CODICE IN...

Page 20: ...THERMIQUE MOTEUR VENTILATEUR RELE TERMICO MOTOR VENTILADOR FUSE FUSIBLE FUSIBLE ANTJAMMING FILTER FILTRE ANTIPARASITES FILTRO DE PROTECION ANTIDISTURBIO MOTOR FAN MUTEUR VENTILATEUR MOTOR VENTILADOR M...

Page 21: ...60 75 90 0 I 0 AUTO OIL RESET 20 21 19 22 FIN D FIN D FIN DER FIN DER 12 10 11 16 15 17 13 K6 RWF 40 PGM PGM EXIT EXIT 23 24 18 14 26 27 70 60 61 62 31 64 65 63 59 1 3 58 2 36 34 35 33 71 72 73 54 55...

Page 22: ...RESET SWITCH 23 FUSE HOLDER 24 LAMP 319017030SGREEN E1507 2 319010010S RED E1507 25 PLUG WIELAND E222 26 IGNITION TRANSFORMER BRAHMA T8 T101 27 PHOTORESISTOR LANDIS A207 1 28 FAN RU 560 M d 42 BFV104...

Page 23: ...N BFV10203 4 62 COUPLING BFV10203 3 63 COUPLING BFV10201 1 64 UNION PUMP BFV10201 6 65 COUPLING PUMP BFV10201 2 66 GAS VALVE BRAHMA EG12S V142 67 COIL BRAHMA EG12S 68 GAS VALVE BRAHMA EG12SR V142 1 69...

Page 24: ...cessarie o utili senza pregiudicarne le caratteristiche principali Ecoflam S p A via Roma 64 31023 RESANA TV Italy tel 0423 715345 r a telefax 0423 715444 Italy 480009 Export 480873 715538 http www ec...

Reviews: