techniques for energy saving
LB1374
MULTIFLAM 700.1÷1200.1 PR
WORKING FIELDS
Burner output
Backpressure in combustion chamber
E
D - D1
G
C
B
A
F
I
L
M
H
N
O
SUNTEC
SUNTEC
SUNTEC
OVERALL DIMENSIONS
Models
Multiflam
700.1 PR
800.1 PR
1000.1 PR
1200.1 PR
Thermal power max.
kW
7.250
8.500
10.500
13.100
kcal/h
6.250.000
7.327.500
9.052.000
11.293.100
Thermal power min.
kW
1.500
2.000
2.500
2.700
kcal/h
1.290.000
1.724.000
2.155.000
2.327.600
Max. capacity (Natural Gas) Nm
3
/ h
729
855
1.056
1.318
Min. capacity (Natural Gas) Nm
3
/ h
150
201
251
272
Max. heavy oil flow rate
kg/h
638
748
924
1.152
Min. heavy oil flow rate
kg/h
132
176
220
237
Gas pressure
mbar
300
300
300
300
Voltage 50 Hz
V
230/400
230/400
230/400
230/400
Motor
kW
15
18,5
22
37
Rpm
N°
2800
2800
2800
2800
Fuels: Nat. Gas L.C.V. 8.570 kcal/Nm
3
; Heavy Oil L.C.V. 9.800 kcal/kg max. visc.50°E at 50 °C
D
= Short head
D1
= Long head
MODELS
A
B
C
D
D1
E
F
G
H
I
L
M
N
O
Multiflam 700.1 1215 585
630
570
-
1420 420
800 480
460
460 M20 195
232
Multiflam 800.1
1285 655
630
570
-
1420 420
800 480
460
460 M20 195
232
Multiflam 1000.1 1315 685
630
570
-
1420 420
800 480
460
460 M20 195
232
Multiflam 1200.1 1425 795
630
570
-
1420 450
800 480
460
460 M20
195
232