pag.11
LB1374
MULTIFLAM 700.1÷1200.1 PR
techniques for energy saving
ADJUSTMENT OF FUEL TEMPERATURE
Increase key
Decrease key
“Function” key
Display
The display shows oil temperature.
The 4 leds are related to the following functions:
Out 1: pump start
Out 2: stage 1st resistance (1/4 of the power)
Out 3: stage 2nd resistance (1/2 of the power)
Out 4: stage 3rd resistance (1/4 of the power)
- The temperatures are already properly Factory setted :
Out 1(
90°
)- Out 2(
115°
)- Out 3(
118°
)- Out 4(
120°
).
- To modify factory temperature setting act as follows:
- press key “
F
”
- the led Out 1 starts to flash, if You need to modify minimum oil temperature press increase or decrease
button, after confirm the new value pressing again “
F
”
- if You need to modify an other temperature press again “
F
” untill You the relevant led flashes.
Please take care: if key “
F
” is pressed for a too long time, You enter in “configuration level” phase1, (see
“CF1” on the display); these parameters are Factory setted and they have not to be modified: if You enter
this function – You see “CF1” flashing on the display – wait 10 seconds untill the regulator automatically
goes out from “configuration level”.