Mounting and operating instructions
9.1
Malfunction with error-
no.
The error is indicated on the display of
the control unit.
Definition of the column "Reaction".
A The drive mechanism deactivates itself during a
certain period: Manual operating mode or stopping
position.
F
Fatal error
H Manual operating mode with re-starting attempt
W Warning
9.1.1
Drive mechanism
No.
Description
Cause
Elimination
Checking time
Reaction
E1
03
Encoder
Channels A + B lost
Check the encoder connection.
Check the motor cable.
The sense of rotation of the motor is not in
compliance with the rod assembly.
The door is blocked.
Check if a jumper has been inserted on
X106.
During run.
H
04
Short-circuit A + B
05
Dysfunctions
06
Motor cable uncorrect plugged
in
Prior to start-up.
H
07
No channel A
08
No channel B
09
No channel A + B
10
Short-circuit A + B
E2
01
Motor current
Current too high
Check the motor cable.
Check if a jumper has been inserted on
X106.
Prior to start-up.
H
02
Current too low
Jumper missing
E3
01
Cushioning
Test failed once
Switch the drive mechanism to the MANU
-
AL operating mode and carefully check if
the door closes in a cushioned manner. If
not: replace the hardware. If yes: check/
correct the friction of the door leaf and
the pre-stressing of the closing spring.
Prior to the closing motion,
after start-up, and subse
-
quently every 24 h.
W
02
Test failed twice.
Damping defective or opening
beyond the peak of the cardioids
curve.
F
Drive unit is
functionning.
Buzzer actif.
E4
01
Reference switch Detected in the open position.
Check the connection and the switching
point of the reference switch (see chapter
4.9.2).
The reference switch must be activated
in the closed position (switching contact
open).
Open position.
F
02
Not detected in the closed
position.
Prior to the first setting-
up run.
A
03
Not detected in open position.
E5
00
Power limitation Overload of the control. the
maximum power is restricted.
Check/correct the friction of the door leaf
and the pre-stressing of the closing spring.
Permanent.
A
9
TROUBLESHOOTING
Warning:
Electrocution hazard! Before working on any live elements, pull out the mains plug
respectively switch off the main installation switch!
If a malfunction occurs which might be detrimental to the safety of the users, and
which cannot be eliminated without delay, the operator must be informed and if requi
-
red the installation shall be taken out of operation. The installation must be repaired as
soon as possible.
Note:
Every troubleshooting procedure which is carried out must be entered into the control
booklet!