26
Command
Value Description
Reply
SensorOn
0x07
Turn on sensor power
None
SensorOff
0x08
Turn off sensor power
None
OWDisable
0x0A
Ignore 1wire memory (OWDisabled) and use
EE memory values, unit subsequently
performs defForceOW/EERead
None
OWEnable
0x0B
Use 1wire memory values (OWEnabled),
unit subsequently performs
defForceOW/EERead
None
ForceOW/EERead
0x0C
Force the module to read the 1wire
memory (OWEnabled)
OR
read the EEprom
(OWDisabled)
defOWReadSuccessfully
0x00
defEEReadSuccessfully
0x01
defOWInvalidSenType
0xFD
defOWZeroSpanDataCRCFail
0xFE
defOWReadError
0xFF
ZeroNH3
0x0F
Set zero for NH3, requires write to OD
0x5000 (old value) and 0x5001 (desired
value)
defZeroSpanSuccessful
0x00
defSenModNotReady
0xFD
defZeroSpanDataInvalid
0xFE
defOWZeroSpanWrFail
0xFF
SpanNH3
0x10
Set span for NH3, requires write to OD
0x5000 (old value) and 0x5001 (desired
value)
defZeroSpanSuccessful
0x00
defSpanInvalidNegativeSlope
0xFB
defSpanTooCloseToOffset
0xFC
defSenModNotReady
0xFD
defZeroSpanDataInvalid
0xFE
defOWZeroSpanWrFail
0xFF
ResetNH3
0x12
Resets the zero and span for NH3 back to
factory values (M=1, b=0, x=0)
defZeroSpanSuccessful
0x00
defSenModNotReady
0xFD
defZeroSpanDataInvalid
0xFE
defOWZeroSpanWrFail
0xFF
ResetAllFilters
0x15
Resets alpha for recursive average of
NH3 to factory value (alpha=375)
defAlphaOK
0x00
ExpertModeDisable
0x16
This command removes the unit from
expert mode.
None
ResetDeltaNH3Table
0x1D
Set all delta %O2 values to 0.
None