Eclipse RatioAir v1 Design Guide No. 115, 11/12/2008

10

Control Motor

Select a control motor. Standard control motor options include 

various models which Eclipse will mount to the burner. RatioAirs 

can be ordered with control motor bracket and mounting hardware 

only. Customer supplied control motors must conform to the these 

specifications:

rotation not to exceed 2 rpm

• 

minimum torque of 25 in-lb (2,8 Nm)

• 

90° stroke

• 

continuous modulating or high/low modulating control

• 

reversible direction of rotation

• 

certain applications may require control motors with a limit 

• 

switch or switches if:

 

the burner capacity is to be limited to fit an application

 

-  the chamber is to be fired with positive or negative  

 

  pressure

 

-  the chamber pressure is outside the range -1" w.c.  

 

  to +1" w.c. (-2,5 to 2,5 mbar)

 

-  there is a need to indicate a high and/or low fire air    

  butterfly valve (BV) position

Burner Configuration

Select configuration.

Gas Pipe Connection

Select the gas pipe connection including the pipe thread type and 

the turndown required.
The piping, burner gas inlet, and ratio regulator are threaded using 

the customer selected pipe thread option.
The high turndown option includes a ratio regulator with an 

adjustment for lower inputs.

Flame Supervision

Determine if a flame rod or an ultraviolet (UV) scanner will be 

required. Flame rods are available on model RA0025, RA0040, 

RA0075 and RA0100 burners with alloy or SiC tubes. A flamerod 

can also be used on RA0200 burners but with upright left hand 

piping or inverted right hand piping configurations only. All other 

options and models require UV scanners. If a UV scanner is 

required, it must be ordered separately. 

Warning:

A UV scanner could possibly detect another burner’s 

flame if it is in the line of sight, and falsely indicate 

flame presence.

Air Flow Switch

The air flow switch provides a signal to the monitoring system 

when there is not enough air pressure from the blower. If a switch 

is selected, it will be factory mounted.

Warning:

Eclipse supports the NFPA regulation requiring, as 

a minimum standard for main gas shut-off systems, 

the use of an air pressure switch in conjunction with 

other system components.

Configuration Selections:

Step 1:

 

Burner Option 

Selection 

(Continued)

Upright Left Hand Piping

Upright Right Hand Piping

Inverted Left Hand Piping

Inverted Right Hand Piping

Summary of Contents for RA Series

Page 1: ...Eclipse RatioAir Burners RA Series Version 1 Design Guide 115 11 12 2008...

Page 2: ...sed or implied We have made every effort to make this manual as accurate and complete as possible Should you find errors or omissions please bring them to our attention so that we may correct them In...

Page 3: ...ign Guide No 115 This document Datasheet Series 115 Available for individual RA models Required to complete design and selection Installation Guide No 115 Used with Datasheet to complete installation...

Page 4: ...Act with great care and follow the instructions Warning Indicates hazards or unsafe practices which could result in severe personal injury or damage Act with great care and follow the instructions Ca...

Page 5: ...lities 7 Operator Training 7 Replacement Parts 7 System Design 8 Design 8 Step 1 Burner Option Selection 9 Step 2 Blower Option Selection 11 Step 3 Control Methodology 11 Step 4 Ignition System 12 Ste...

Page 6: ...ower and an air gas ratio regulator to fire over a wide gas turndown range with controlled ratio Available with three different outlet tube velocity characteristics standard medium and high velocity R...

Page 7: ...sign purpose Do not deviate from any instructions or application limits described herein without written advice from Eclipse Read the entire manual before attempting to start this system If you do not...

Page 8: ...on Gas Pipe Connection Flame Supervision Air Flow Switch Blower Option Selection Including 2 Power Supply Frequency Pressure and Flow Blower Motor Type Blower Inlet Motor Orientation Control Methodolo...

Page 9: ...and clean without corrosives Combustion Air Temperature Changes in air supply temperature can affect the burner capacity The combustion air supply temperature should not exceed 250 F Fuel Type Variati...

Page 10: ...lator are threaded using the customer selected pipe thread option The high turndown option includes a ratio regulator with an adjustment for lower inputs Flame Supervision Determine if a flame rod or...

Page 11: ...e limitations cleanliness requirements of the process Motor Orientation All RatioAirs are assembled with a right hand blower motor orientation All standard RatioAirs are designed for air gas ratio con...

Page 12: ...under certain circumstances RatioAirs are capable of direct spark ignition at higher gas inputs Most local safety codes and insurance requirements limit the maximum trial for ignition time the time i...

Page 13: ...itoring Control Flame Sensor Two types can be used on a RatioAir Burner Flame Rod UV scanner Flame rods are available on model RA0025 RA0040 RA0075 and RA0100 burners with alloy or SiC tubes A flame r...

Page 14: ...cted during trial for ignition Component Selection Eclipse can help in the design of a main gas shut off valve train that satisfies the customer and complies with all local safety standards and codes...

Page 15: ...ter mm inch in 3 94 x 10 2 MJ m normal BTU ft standard 2 491 x 10 2 Metric to English From To Multiply By kiloPascals kPa millibar mbar 10 meter m millimeter mm 1000 millibar mbar kiloPascals kPa 0 1...

Page 16: ...y burners 760 Fuel Orifice Meter Fuel orifice meters are used to measure gas flow 910 Adjustable Limiting Orifice Adjustable limiting orifices are used for fine adjustment of gas flow Pressure Regulat...

Page 17: ...Offered By Burnerparts com 2011 Williamsburg Road Richmond Virginia 23231 Phone 804 236 3881 Fax 804 236 3882 www burnerparts com...

Reviews: