Eclipse PulsePak Installation Manual Download Page 9

9

Eclipse PulsePak Valve Train Segments, V1,  Installation Guide 791-2, 8/10/2010

Adjustment, Start &
Stop

Before Applying Gas

Before applying the site gas supply, be sure the actual
pressure does not exceed the inlet rating of the system.
Close the zone inlet valve and outlet manual valve on the
PulsePak valve train segment and then slowly open the
site gas supply valve.

Ŷ

 Check for any abnormal conditions and

immediately shut off the site gas supply to the
system if you sense any danger such as gas leaks
or mechanical stress.

Tests

Leak Testing

The valve train segment is tested and leak tight at the
factory, however, shipping and installation may cause
joints to loosen. Check and test all piping for leaks.

Ŷ

  Test pressure must not exceed 7 PSIG or 500 mbar

and any components with ratings less than the test
pressure should first be isolated. Check the
individual product datasheets for specific ratings.

Shutoff Valve Functional Test

1.

Slowly open the zone manual valve to allow gas to
flow to the PulsePak valve train segment safety
shutoff valve.

2.

Verify the pressure to the inlet of the ratio regulator
does not exceed the maximum allowable pressure to
the PulsePak valve train segment.

3.

Initiate air source and set air control valve to high fire
setting.

4.

Verify there is enough loading line pressure to the
ratio regulator for gas flow.

5.

Verify there is no pressure rise at the test port on
either safety shutoff valve. If there is a pressure rise,

stop, and investigate if the valve seats may be
leaking.

6.

Apply power to the upstream shutoff valve. Verify
there is a pressure rise on the upstream shutoff valve
test port and there is not a pressure rise at the down
stream shutoff valve test port. If there is a pressure
rise at the down stream shutoff valve, stop, and
investigate if the valve seat may be leaking.

7.

Finally apply power to both shut off valves and verify
there is a pressure rise at the down stream shutoff
valve as well.

Safety Shutoff Valve Seat Leak Test

The safety shutoff valve seats should be tested whenever
there is an event that raises the possibility of
contamination entering into the valve. Because valve
seats can deteriorate over time, the test should be
performed at least annually.

Ŷ

  Take care when performing the test since small

amounts of flammable gas will be released into the
local area. Ensure adequate ventilation.

Prepare a glass with water and insert one end of flexible
tubing to a depth of 1/8 to 1/4 inch or 3 to 6mm. With the
burner shut off and gas supplied to the ratio regulator
perform the following test:

1.

Close the downstream manual valve.

2.

Bleed trapped gas by opening the leak test ports on
both shutoff valves.

3.

Connect the free end of the tubing to the port on the
upstream shutoff valve.

4.

If bubbles appear immediately and continue, the
upstream valve seat is leaking and must be serviced;
otherwise wait 30 seconds to charge the volume
between the valve seats.

5.

Count the bubbles for the next minute; if the number
is greater than that allowed by local standards then
the valve must be serviced; see the following chart for
guidelines.

WARNING

WARNING

WARNING

4

Summary of Contents for PulsePak

Page 1: ...Eclipse PulsePak Valve Train Segments Gas Valve Train 2 1 2 3 Air Valve Train NFPA and CE Models 791 2 Installation Guide 8 10 2010 Version 1 ...

Page 2: ...our customers Please send your corrections and comments to our Marketing Communications Manager It must be understood that Eclipse s liability for its product whether due to breach of warranty negligence strict liability or otherwise is limited to the furnishing of replacement parts and Eclipse will not be liable for any other injury loss damage or expenses whether direct or consequential includin...

Page 3: ... Training 5 Replacement Parts 5 3 Installation 6 Introduction 6 Handling Storage 6 Approval of Components 6 Checklist Before Installation 7 Installation 7 Checklist After Installation 8 4 Adjustment Start and Stop 9 Before Applying Gas 9 Tests 9 Leakage Rate Limits 10 5 Maintenance Troubleshooting 11 Introduction 11 Maintenance 11 Monthly Checklist 11 Yearly Checklist 11 Troubleshooting Guide 11 A...

Page 4: ... found in the zone panel or through the T400 Flame Safety Unit Low fire bypass with flow adjustment Quick electrical disconnect To fully meet the requirements of local codes these sub assemblies will require additional components such as a drip leg strainer filter dryer regulator high and low gas pressure switches air flow switch and overpressure protection depending on the end use application Whe...

Page 5: ... to light a burner if it shows signs of damage or malfunction Ŷ This manual provides information for the use of these valve trains for their specific design purpose Do not deviate from any instructions or application limits in this manual without written advice from Eclipse Capabilities Only qualified personnel with good mechanical aptitude and experience with combustion equipment should adjust ma...

Page 6: ...or standards and must be listed for combustion safety by an independent testing agency Typical application examples include American NFPA 86 with listing marks from UL FM CSA European EN 746 2 with CE mark from TuV Gastec Advantica Electrical Wiring All the electrical wiring must comply with all applicable local codes and or standards such as NFPA Standard 70 IEC60364 CSA C22 BS7671 Gas Piping All...

Page 7: ...re to sunlight water ice wind and vibration Preparation for Installation Protect and prevent contamination of the piping during installation Remove any packing and shipping materials and inspect for foreign objects in the piping Ŷ Make sure all devices are properly oriented with respect to flow direction and vertical gravity orientations Ŷ Avoid severe size reductions in pipe connections unnecessa...

Page 8: ...g the pressure evenly distributed Take care to avoid undue strain on valves fittings and other accessories Do not install undersized bolts to make up for misalignment of bolt holes Electrical Wiring All electrical wiring must be done in accordance with the national electrical code the local utility company and municipal agency requirements Before making any electrical connections compare the elect...

Page 9: ...p and investigate if the valve seats may be leaking 6 Apply power to the upstream shutoff valve Verify there is a pressure rise on the upstream shutoff valve test port and there is not a pressure rise at the down stream shutoff valve test port If there is a pressure rise at the down stream shutoff valve stop and investigate if the valve seat may be leaking 7 Finally apply power to both shut off va...

Page 10: ... 30 seconds to charge the volume between the valve seat and manual outlet valve 10 Count the bubbles for the next minute if the number is greater than that allowed by local standards then the valve must be serviced see the following chart for guidelines 11 Remove power remove the tubing and close the test ports Leakage Rate Limits NPT in DN mm UL 429 ANSI Z21 21 CSA6 5 Bubbles min FM7400 Bubbles m...

Page 11: ...nthly Checklist Inspect and tighten loose mechanical components Look for signs of damage and repair as needed Clean the external surfaces Yearly Checklist Perform all monthly checklists plus Check tightness of wiring connections Check for gas pipe leaks Perform safety shut off valve seat leak test Troubleshooting Guide CAUTION Problem Possible Cause Solution Gas valves not opening Loss of power Ch...

Page 12: ...12 Eclipse PulsePak Valve Train Segments V1 Installation Guide 791 2 8 10 2010 NOTES ...

Page 13: ...r mm inch in 3 94 x 10 2 MJ Nm BTU ft standard 26 86 From To Multiply By kiloPascals kPa millibar mbar 10 meter m millimeter mm 1000 millibar mbar kiloPascals kPa 0 1 millimeter mm meter m 0 001 From To Multiply By cubic foot ft cubic meter m 2 832 x 10 2 cubic foot hour cfh cubic meter hour m h 2 832 x 10 2 degrees Fahrenheit F degrees Celsius C F 32 x 5 9 pound lb kilogram kg 0 454 BTU hr kilowa...

Page 14: ...Offered By Power Equipment Company 2011 Williamsburg Road Richmond Virginia 23231 Phone 804 236 3800 Fax 804 236 3882 www peconet com ...

Reviews: