background image

Page 7

RVS-RCS Installation Guide

1. 

To enter sensor setting mode, press and hold the teach button until the green LED 

begins to blink (about 6 seconds).

2.  A quick press of the button at this level will allow you to scroll between the test/

setting modes. When the red and amber LEDs are blinking, go to step 3. 

3.  Press and hold the button again until the LEDs stop blinking to select this mode, 

about 6 seconds.

4. A quick press of the button at this level scrolls between:

Double Green - PIR Sensitivity

Double Amber - Audio Gain (DT model only)

Double Red - Occupancy Sensor Timer (DT model only)

5. Press and hold the teach button again for 5 seconds to select the desired sensor 

setting. The corresponding LED will blink according to the current setting. Press the 

button to scroll through the available settings.

PIR Sensitivity

 - green LED  blinks indicate setting

1 blink = high (default);  

2 blinks = medium;  

 

3 blinks = low

Audio Sensitivity

 - amber LED  blinks indicate setting (DT model only)

1 blink = automatic (default) 

2 blinks = low sensitivity 

3 blinks = disabled

Sensor

 

Occupancy Timer

 - red LED  blinks indicate setting (DT model only)

1 blink = disabled  

 

2 blinks = 5 minutes 

3 blinks = 10 minutes 

 

4 blinks = 15 minutes

5 blinks = 20 minutes (default) 

6 blinks = 25 minutes

i

Note:

If  the  Disabled  setting  is  selected  for  the  Sensor  Occupancy  

Timer,  the  audio  will  remain  active  the  entire  60  minute 

duration of the Audio Enabled Timer. Disabling both the Sensor 

Occupancy  Timer  and  Audio  Sensitivity  setting  will  have  the 

sensor behave exactly like the IR model. 

To  save  the  Sensor  setting,  press  and  hold  the  teach  button 

until all the LEDs double blink. The unit will now be in normal 

operating mode with the new setting in effect..

To select a setting press and hold the test button for 10 seconds when the desired LED is 

blinking. To exit without saving, allow the test to time-out in 60 seconds.

LED Indication  Enable/Disabl

e

1. 

Enter Test mode as usual, press and hold the teach button until the green LED begins to 

blink (about 6 seconds).

i

Note:

New settings do not take affect until you save and exit

2.  A quick press and release of the button at this point will allow you to select between test 

modes. When the green and red LEDs are both blinking simultaneously, go to step 3.

3.   Press and hold the teach button again for about 6 seconds until they stop blinking.

4.   The red LED blinking indicates the motion detection LED is active. The green LED 

blinking indicates the LEDs are inactive. Tapping the teach button will toggle between 

these two states.

5.   Save and exit by press and holding the teach button for 5 seconds.

Installing Wireless Devices

Careful planning is needed when locating the receivers and transmitters based on the construction 

materials in the space and possibility of tenant’s furniture disrupting the transmissions. 

Summary of Contents for RVS-A-XW

Page 1: ...on i Note The RVS is a solar powered device that absorbs solar energy from artificial or natural light sources Before assigning the RVS sensor to a receiver or controller the sensor should be exposed to a good light source for a minimum of 2 minutes RVS Vacancy RCS Occupancy Sensor Description The RVS RCS also referred to as the sensor in this guide is a wireless energy harvesting sensor The model...

Page 2: ...e time in which an occupancy trigger PIR or audio must be detected to keep the audio input active The default value for this timer is 20 minutes and it is configurable to values of 5 10 15 20 25 minutes or disabled If the sensor occupancy timer expires the sensor will send out a vacancy signal and 40 seconds later the audio will be disabled The 40 seconds grace time allows an occupant to use sound...

Page 3: ...uide An LED under the lens will blink once every 100 seconds when the sensor is detecting motion Additionally the LED color indicates the status of the battery when applicable see the following table LED Color Battery Status Red No battery or weak Amber 50 discharged Green Full charge Mounting the Sensor The mounting location of the sensor is important as this will directly affect the receivers re...

Page 4: ...a steel T bar ceiling frame or other metallic surface by placing the sensor on to the metal rail With screws and anchors not provided to a wall board ceiling i Use a pencil to mark the mounting base keyhole locations and remove the sensor ii Using a drill bore the two holes and insert the anchors iii Install the screws leaving them loose while you place the sensor iv Tighten the screws With the pr...

Page 5: ... Gently twist the screw driver and pull the cover away from the base 2 To remove an old battery use a small screwdriver as a lever and insert under the battery Gently twist the screwdriver so the battery pops out 3 Install or replace the battery with a new CR1632 coin cell battery insuring the positive side will be facing up 4 Place the battery in the holder and press in place with your thumb Test...

Page 6: ... sensor displaying the linked signal strength status for 2 5 seconds RANGE CONFIRMATION TEST TABLE LED Signal Strength Green Blinking 2 5 sec 41 to 70 dBm Amber Blinking 2 5 sec 70 to 80 dBm Red Blinking 2 5 sec 80 to 95 dBm No LED No linked receivers detected The test will repeat every 4 seconds and run for a duration of 50 seconds You may quit the test at any time by pressing the test button for...

Page 7: ...ancy Timer the audio will remain active the entire 60 minute duration of the Audio Enabled Timer Disabling both the Sensor Occupancy Timer and Audio Sensitivity setting will have the sensor behave exactly like the IR model To save the Sensor setting press and hold the teach button until all the LEDs double blink The unit will now be in normal operating mode with the new setting in effect To select...

Page 8: ... Built in an ISO9001 certified facility FCC Part 15 231 902 MHz models only Contains FCC ID TCM300U The enclosed device complies with Part 15 of the FCC Rules Operation is subject to the following two conditions I This device may not cause harmful interference and ii This device must accept any interference received including interference that may cause undesired operation IC RSS 210 902 MHz model...

Reviews: