Temperature Sensor Description

The temperature sensor (also referred to as the sensor in this guide) is a wireless, energy 

harvesting sensor that monitors room temperature in the range of 0-40°C (32° - 104°F) 

and relative humidity in the range of 0-100% . The sensor is intended for indoor use only.

Some models have a temperature set point knob and/or a fan speed slide switch. These 

options provide the user an interface to manually adjust how the temperature control 

operates.

A button on the lower right edge of the sensor body can be used to invoke an occupancy 

event (for RTS-2HS models) or to go into test mode (when the button is held down, see 

“Test Operating Modes”).

The temperature sensor transmits to a receiver which is typically a device that is 

programmed to provide temperature control in the space that the sensor is monitoring 

for closed loop temperature control. The sensor and receiver must be within range, 

preferably  in  the  same  room  and  installed  within  50’  (15.2  m)  of  each  other.  For 

applications exceeding 50’ (15.2 m) range, greater care must be taken to insure proper 

reception of the sensors transmissions at the receiver, refer to sections “Test Operating 

Modes” and ‘Installing Wireless Devices”.

Even with a brief exposure to light the sensor will operate; however for best results the 

sensor should be mounted in a location with exposure of 4 hours of natural or artificial 

light on a daily basis.

The temperature sensor transmits status telegrams that contain the information defined 

within a equipment profile.
The temperature sensor supports the following profiles:

•  A5-02-05: Temperature Sensor

• 

A5-04-01: Temperature  Humidity Sensor

• 

A5-10-03: Temperature  Temperature Set Point Control

• 

A5-10-19: Tempe Hu Set Point + Fan Speed + Occupancy Button.

The valid ranges for each data element:

• 

Temperature: 0 - 40°C, (32° - 104°F)

• 

Temperature Set Point: offset scale 0-250

• 

Humidity Sensor: 0 -100% RH

• 

Fan Speed Switch: Auto, OFF, Low (1) Med (2), High (3)

• 

Occupancy Button: Occupied

Temperature Sensing Operation

Temperature and Humidity Monitoring 

- The temperature sensor will record 

the temperature, temperature set point and humidity values* every 10 seconds 

(sample period) when there is approximately 100 lux (10 foot-candles) available. 

If there is less than 100 lux (10 fc), the sample period will increase to 100 seconds. 

After 24 hours at < 15 lux (1.5 fc) the sample period will increase to 200 seconds. 

*Assuming sufficient storage charge to operate.

Temperature Set Point

 - Users can adjust the temperature set point by rotating 

the knob counterclockwise to lower the set point value; clockwise to increase 

the set point value.
The receiving temperature control equipment must scale the set point range to 

values that are applicable for the application.

Fan Speed Switch 

- Users can adjust the fan speed switch by sliding the switch to 

a setting: Auto, OFF, Low (1) Med (2), High (3).

Summary of Contents for RTS-1T-nW

Page 1: ...h temperature set point RTS 2HS nW Temperature and humidity sensor with temperature set point fan speed and occupancy button The character n is replaced with U for 902MHz C for 315MHz Y for 868MHz and...

Page 2: ...Page Intentionally Left Blank...

Page 3: ...with exposure of 4 hours of natural or artificial light on a daily basis The temperature sensor transmits status telegrams that contain the information defined within a equipment profile The temperat...

Page 4: ...this will directly affect the receivers reception of the telegrams Before installing refer to the sections in the guide detailing the installation of wireless devices layout tips and the test operati...

Page 5: ...om the back plate 2 To remove old battery Using a small flat head screwdriver or pen as a lever insert pointed end under the clear plastic battery retaining clip s edge and pop the clip off 3 Install...

Page 6: ...capability only F series controllers have range confirmation ability One and only one receiver can be linked to the sensor for proper operation of the test disable repeaters in range for proper test...

Page 7: ...ors Line of sight 150 46m open halls Plasterboard 80 24m through 3 walls Brick 33 10m through 1 wall Ferro concrete 33 10m through 1 wall Ceiling Not Recommended Wireless System Layout Hints Avoid loc...

Page 8: ...ly 928 MHz and 315 MHz models that bear a MIC mark Japanese Radio Law and Japanese Telecommunications Business Law Compliance This device is granted pursuant to the Japanese Radio Law and the Japanese...

Reviews: