Echoflex Installation Guide

Dual Tech Vacancy Sensor

Control Wire Specification

The sensor connects to the EchoConnect

®

communication bus. EchoConnect is

a bidirectional protocol that uses one pair of wires (data + and data -) for both
data and power. Echoflex recommends using Belden 8471 (or approved equal)
Class 2 wire. The total combined length of an EchoConnect wire run (using
Belden 8471, or equal) may not exceed 1,640 feet (500 m).

Note:

All control wiring should be installed and terminated by a

qualified installer and should follow standard wiring installation practices.

Leave approximately 8" (20 cm) of wiring in the back box for connection
and to allow slack for future service needs.

Note:

Echoflex requires that all Elaho stations and devices be grounded

for ESD protection. Pull an additional 14 AWG (2.5 mm

2

) wire for

grounding when control wires are not installed in grounded metal conduit.

Note:

When using Category 5 (or equivalent) cable on the EchoConnect

communication bus, please note the following:

Cat5 wiring must be terminated using EchoConnect Cat5
Termination Kit and must be installed using a bus topology.
Refer to the installation guide that is provided with the Cat5
Termination Kit (8186A1207) for information to terminate
Cat5 wiring.

Not all topologies are supported using Cat5; careful planning
is required to ensure the proper termination kits are available
and the wire is pulled appropriately.

Parts and Supplies

The following parts and supplies are included with the sensor:

mounting bracket with pre-routed EchoConnect and ground wires

mounting screws

WAGO connectors (wire termination connectors)

decorator style wall plate

Dual Tech Wall-mount Vacancy Sensor

Page 3 of 12

Echoflex Solutions, Inc.

Summary of Contents for Elaho Dual Tech Wall-mount Vacancy Sensor

Page 1: ...y upon detection of vacancy The wall mount unit offers up to 140 degree field of detection with optimized lens options to accommodate wide or narrow angle spaces and is available in white black or cre...

Page 2: ...ls use only The sensor operates in ambient temperatures of 10 C to 40 C with a maximum of 90 non condensing humidity Installation Echoflex recommends paying special attention to the installation envir...

Page 3: ...or ESD protection Pull an additional 14 AWG 2 5 mm2 wire for grounding when control wires are not installed in grounded metal conduit Note When using Category 5 or equivalent cable on the EchoConnect...

Page 4: ...0 mm 2 Connect the EchoConnect pigtail wires from the mounting bracket to the installed wall wires a Connect the data typically black EchoConnect wire from mounting bracket to the incoming EchoConnect...

Page 5: ...ets engage d If the wall plate does not fully attach wiggle the bottom of the plate until all of the magnets are seated properly a b c d 5 Attach the sensor head a Slide the removable cover off the se...

Page 6: ...used and have no functionality on the Dual Tech Wall mount Vacancy Sensor Set Space and Address Two rotary switches on the controller provide for assignment of the sensor Space and Address By default...

Page 7: ...red Instead the settings made by the EchoAccess Mobile App are used 3 and 4 Vacancy Timeout 5 min Switches 3 and 4 are Off 15 min Switch 3 is Off and Switch 4 is On default 30 min Switch 3 is On and S...

Page 8: ...hen the vacancy timeout in the space has only been reset by acoustic detection for 60 minutes acoustic detection is disabled until the next PIR detection event PIR only Detection When acoustic detecti...

Page 9: ...he sensor does not detect occupancy again during the vacancy timeout period the lights turn off and a 30 second grace period begins Grace Period The sensor features a 30 second grace period after a va...

Page 10: ...f the sensor to enable the Walk Test feature A green LED will flash indicating Walk Test is enabled and the vacancy timer will be shortened to ten seconds 3 Move throughout the space including corners...

Page 11: ...or Sensor Coverage Narrow Lens 100ft 30 5m 18 3m 60ft 2 2m 7ft 1m 3ft 2 1m 6 8ft 3m 10ft 10 7m 35ft 6 56 2 5m 8ft 0 C L 77 29 21 5 14 5m 16ft 5m 16ft 2 5m 8ft Top View Side View Dual Tech Wall mount V...

Page 12: ...e Dual Tech Vacancy Sensor Wide Lens 19 4 0 5m 10m 16ft 33ft 5m 10m 16ft 33ft 15 3m 7 7 m 4 6m 1 7m 50ft 25ft 15ft 6ft 2 1m 6 8ft 140 Top View Side View Dual Tech Wall mount Vacancy Sensor Page 12 of...

Reviews: