E E P R O M S E T T I N G S
EQK
N/A. Do not adjust.
FS - Fire Service type
Australia:
Set to 00: 00000000
USA Only.
Fire Service Code 17.1. FS EEprom setting must be set to 01: 00000001
HFAF - Hall Fire Alternate (Front doors) floor setup
USA Only.
Fire Service Code 17.1. FS EEprom setting must be set to 01
When the designated floor smoke alarm is activated, the lift shall return to the HFAF floor if there is a setting floor.
See also Inputs-Outputs HFAF
HFAF…EEPROM Hall Fire Alternate (Front doors) floor. (MASK)
00: 00000000 (No setting floor)
80: 10000000 (Level 1)
40: 01000000 (Level 2)
20: 00100000 (Level 3)
10: 00010000 (Level 4)
08: 00001000 (Level 5)
04: 00000100 (Level 6)
Note: Set either HFAF OR HFAR. DO NOT set both of them.
HFAR - Hall Fire Alternate (Rear doors) floor setup
USA Only.
Fire Service Code 17.1. FS EEprom setting must be set to 01
When the designated floor smoke alarm is activated, the lift shall return to the HFAR floor if there is a setting
floor.
See also Inputs-Outputs HFAR
HFAR…EEPROM Hall Fire Alternate (Rear doors) floor. (MASK)
00: 00000000 (No setting floor)
80: 10000000 (Level 1)
40: 01000000 (Level 2)
20: 00100000 (Level 3)
10: 00010000 (Level 4)
08: 00001000 (Level 5)
04: 00000100 (Level 6)
Note: Set either HFAF OR HFAR. DO NOT set both of them.
HFSF - Hall Fire Service (Front doors) return floor setup
This sets the hall fire service return front doors floor activated when HFS input is active whilst in normal mode and
HFSF has a setting floor.
HFSF…EEPROM Hall Fire Service (Front doors) floor. (MASK)
00: 00000000 (No setting floor)
80: 10000000 (Level 1)
40: 01000000 (Level 2)
20: 00100000 (Level 3)
10: 00010000 (Level 4)
08: 00001000 (Level 5)
04: 00000100 (Level 6)
Note: Set either HFSF OR HFSR. DO NOT set both of them.