Important information
The burners of type E 10... L-EUF have
been designed for the combustion of
heavy fuel oil. The burners should be
installed and taken into operation care-
fully by qualified personnel. The work
should be done in accordance with the
applicable regulations and guidelines.
Only a duly authorized specialist should
be entrusted with the installation of the
gas system.
Any repair work on monitors, limiters
and automatic furnace controllers and
on the other safety facilities are allowed
to be done on the single items only by
the manufacturers themselves or spe-
cialists authorized by them.
Original parts should only be exchan-
ged by a duly qualified specialist.
Standards and regulations
The following standards should be
observed in the interest of a safe, easy-
on-the-environment and energy-saving
operation of the burner:
EN267/
DIN4787
Oil Atomizing Bur-
ners
VDE 0116
Electrical Equipment
of Furnaces
According to DIN 4755 the user must be
instructed in the operation of the fur-
nace system.
For the installation of an oil furnace sys-
tem, care should be taken to observe
DIN 4755, TRbF (Technical Regulation
on Combustible Liquids) and the local
furnace construction regulations appli-
cable in the country.
Place of installation
The burner must not be operated in
rooms containing corrosive vapours
(e.g. spray, perchloroethylene, hydro-
carbon tetrachloride, solvent, etc.) and
tending to heavy dust formation and
only up to 60% relativ air humidity.
Adequate ventilation must be provided
at the place of installation of the furnace
system to ensure a reliable supply with
combustion air.
Maintenance
The furnace system should be serviced
at least once a year by an authorized
specialist. It is recommended to con-
clude a maintenance agreement to this
effect.
Warranty
Manufacturer will not accept any war-
ranty if the operating instructions have
not been duly observed in the start-up
and maintenance of the burner and
damages have been caused by impro-
per installation, incorrect adjustment,
unauthorized interference or operating
errors.
Product description
The burners of type E10...L-EUF have
been designed as oil-burner for the
combustion of heavy fuel oil according
to DIN 51603-1.
They are fitted with a free-flame burner
head as a system to ensure low-NOx
combustion.
The burners are equipped with combu-
stion air fan and air pressure switch with
test key, air box with actuator for the air
dampers, oil pressure-atomizer with
high-pressure oil pump, nozzle rod,
return nozzle, and oil hydraulic system
(with pressure switches, valves and
control shaft), pressure hoses, electrical
ignition system for the oil operating
mode.
The burners are designed for operation
with electronic compound control.