background image

22

Adjusting Instructions

Start-up of Burner Control System Type BCS 300

Flame Detecting System Type FLW 05

Description

The electronic burner control system 
type BCS 300 is a programmable auto-
matic firing controller of modular con-
struction with integrated electronic 
compound controller. It is designed for 
the control and automatic control of oil, 
gas and dual-fuel burners of medium to 
larger outputs.
The automatic firing controller may be 
used for intermittent or continuous 
mode of operation and for furnace 
systems built according to TRD.
The controller consists of the following 
units that communicate via a safety-ori-
ented bus system:
-

burner controller module type 
BCS 300 (attached to burner)

-

flame detector module type BCS-
FLW 05 (attached to burner)

-

fuel and air servomotors

-

operating and display unit type 
BAM (not required for operation of 
furnace system)

The system also incorporates a PID 
firing rate controller with standard or 
servo-control parameterization capabi-
lity and a valve leak tester.

Technical data:

Operating voltage:

230  V a.c.

Frequency:

50-60 Hz

Power input:

BCS incl. BAM:<15 VA
FLW 05:

<1.5 VA

Back-up fuse:

max. 10 AF

Equipment fuse:

6.3 A slow-blow
0.1 A slow-blow

Permissible ambient temperature:

in operation:

0 - 60 °C

during storage:       -20 - 70 °C

Starting the burner control system

NOTE:

 The burner control system is 

allowed to be started by duly qualified 
specialists only. The personnel opera-
ting the system should strictly observe 
the applicable instructions for start-up.

Before proceeding with the pro-
gramming of the system make a check 
of its wiring (especially for compliance 
with the relevant DIN-VDE standards 
and the regulations of the local power 
supply company).

The parameterization of the automatic 
firing controller programs, the valve leak 
test and the firing rate adjustment will 
be handled from the operating and dis-
play module. 

NOTE:

 For selecting the automatic con-

troller programs and adjusting the pre-
ventilation times care should be taken to 
observe the applicable standards.
The fixed safety time settings are not 
allowed to be extended by external swit-
ching operations.

The fuel-air compound curves may be 
programmed by means of the operating 
and control module or a laptop compu-
ter.
If the compound controller is adjusted 
by means of the operating and display 
module it will only be possible to correct 
the curve point settings.
A completely new curve and the defini-
tion of new curve points can be achie-
ved with the aid of a laptop computer 
only.

After the automatic controller programs 
have been set it will be possible to 
check the inputs and outputs of the bur-
ner control system for proper 
functioning via the operating and dis-
play module.

NOTE:

 For the tests, all manual fuel 

shut-off valves must be kept in closed 
position in any case.

The compound modules are provided 
with a basic curve when delivered ex 
works. This may be changed by means 
of the operating and control module to 
adjust it to the local conditions. For this 
purpose, it is possible to correct the 
damper positions for the 10 index points 
in the range from 10, 20, 30, etc. to 100.

Flame detecting system

The flame detector module type FLW 05 
is used in conjunction with the burner 
control system.
The following flame sensors may be 
connected to the flame detector 
module:
-

QRA  2

-

QRA 53/55

-

RAR  7/8

-

ionization electrode

-

any flame detector with contact 
output

The sensor to be used will be selected 
by appropriate programming in the bur-
ner control system. The type of sensor 
used will depend on the burner opera-
ting mode (continuous or intermittent).
The flame boosters integrated in the 
flame detector will be checked for pro-
per operation at an interval of 90 
seconds in continuous mode. 
Flame detectors with contact output 
must if run in continuous mode be intrin-
sically safe because only the parts of 
the BCS flame detector are checked for 
safe operation.

The intensity of the flame signals (UV 
sensor, light sensor, ionization elec-
trode) is evaluated in the burner control 
system and indicated on the operating 
and display module.
This allows an exact orientation of the 
flame sensors.
It is not possible to measure the flame 
intensity by means of instruments.

The flame sensors must be checked for 
accumulation of dirt at regular intervals. 
Take care that the sensor window is 
kept free of dust all the time.
The flame intensity display may be used 
as an indicator for the dirt accumulation 
load. 
If the situation cannot be remedied by 
cleaning it will be necessary to replace 
the flame sensor.

Summary of Contents for E10.14000.45 L-EUF

Page 1: ...Operation Manual for the authorized specialist Dual fuel Burner E 10 L EUF 06 2006 102 885 8162...

Page 2: ...rt up Return Nozzle Rod RDG 1250 17 Nozzle selection Sonic 18 Checking Procedure 19 Adjusting Instructions Air Flow Rate Adjusting Procedure 20 Elektronic Burner Control with Electronic Compound Contr...

Page 3: ...ry Place of installation The burner must not be operated in rooms containing corrosive vapours e g spray perchloroethylene hydro carbon tetrachloride solvent etc and tending to heavy dust formation an...

Page 4: ...acc EN267 Detailed values on request Oil connection High pressure pump 30 bar mounted on burner approx 2700 l h 4 0 kW approx 4000 l h 5 5 kW Fan motor 400 690 V 50 60 Hz 2950 3550 U min IP55 37 kW 4...

Page 5: ...sion Drilling Template Motor with disassembled protection grid The air intake box can be rotated in steps of 22 5 C the swivelling function however is then not functional Note In pecial cases the air...

Page 6: ...rough the burner chamber heat exchanger and chimney The interior cooling los ses will be greatly minimized General safety functions In case a flame does not develop when starting the burner fuel relea...

Page 7: ...epending on the heat demand Electronic compound control The air box includes an actuator for operating the air damper The oil control valve incorporates an actuator for adju sting the return oil flow...

Page 8: ...Return oil pressure switch 312 Feed oil pressure switch 349 Actuator In case of TRD 604 72 hr control items pos 311 312 need to be tested according to special construc tion design or must be installed...

Page 9: ...eturn flow rate Control shafts with different control contour parameters are available for adjustment to various oil nozzle sizes This concept ensures that an excellent control characteristic and a wi...

Page 10: ...10 E 10 1200 L EUF Start up Burner Head Settings E 10 L EUF...

Page 11: ...allo wed to be entrusted to authorized spe cialists only Burner installation For mounting the burner to the boiler make sure the connection plate is pre pared in accordance with the dimensi ons given...

Page 12: ...lers for example should done at a diameter not below 70 of the combu stion chamber diameter The space between the flame pipe of the burner and the boiler lining should be lined with heat resistant mat...

Page 13: ...gauge are mounted to the oil pump for measu ring the oil pressure NOTE After the burner has been taken into operation the gauges must be removed again and the connections sealed with suitable means I...

Page 14: ...m 20 to 40bar and oil temperatures up to 140 C The ambient temperature in the vicinity of the coil should not exceed a temperature of 60 C SW 41 SW 41 SW 41 swirl chamber platee adapter mounting rod N...

Page 15: ...k pres sure If this pipe is connected to a ring main having a low overpres sure it is essential to observe that the pressure at connection S must in any case be at least 20 bar higher than that pressu...

Page 16: ...withdrawn and the nozzle needle is opened During the short time where the piston moves from closed to open needle position the pressure at connection C is always at least 2bar lower than the pressure...

Page 17: ...re would keep the slider open Under normal circum stances both locking mechanisms would open at the same time The oil in the forward flow section would exit through the nozzle head to be mixed with th...

Page 18: ...1000 60 with controlled return Light fuel Oil Feed pressure 28bar Return nozzles of the type Sonic Spray are available in different ratings with an angle of spray of 45 60 or 80 The 45 nozzles are pr...

Page 19: ...ly system Set fuel selector switch to its Oil posi tion Fill pump with oil Mount pressure gauge in the feed line and return line Mount the pressure gauge for checking the pump suction pressure Bleedin...

Page 20: ...n and open in maximum position The combustion air flow rate required for proper fuel combustion is controlled by an electronic fuel air compound con trol system over the full load range A check is mad...

Page 21: ...OEM Refer to the documentation supplied with the electronic compound control system for the pre operational work on the burner the checking requirements e g actuators limit switches potentio meters et...

Page 22: ...grammed by means of the operating and control module or a laptop compu ter If the compound controller is adjusted by means of the operating and display module it will only be possible to correct the c...

Page 23: ...ND 5 AA MA 6 AB MB NOTE Check the zero position of the servomotors prior to start up Technical documentation BCS 300 Dungs Technical data Maximum torque 15 Nm Gear reduction 745 1 Positioning times at...

Page 24: ...ime 40 sec for 90 Torque 15 Nm Static holding moment 8 Nm Dimensiones B x H x T 93 mm x 144 mm x 149 mm Potentiometer integrated 5 k Electrical Actuator STM 40 The actuator STM 40 is used in connec ti...

Page 25: ...ker attached to the housing side wall Functional test without burner start After the electronic compound controller has been connected electrically pro ceed with adjusting the potentiometers of the ac...

Page 26: ...cc to DIN EN in pumps without quick action stop valve DSF 146 F 0 10 bar 0 5 2 5 bar Return line acc to TRD 604 72h DSB 158 F 3 25 bar 1 0 4 3 bar Feed line acc to TRD 604 72h Air pressure switch The...

Page 27: ...gases such as refinery and high furnace gases FFS 06 IR 1200 2800nm oil gas furnaces with heavy flue gas recirculation waste gases with yellowish colouring without UV radiation Sensitivity Adjustment...

Page 28: ...ation detectors cover the spectral range from 190 to 520nm All blue burning flames such as gas or oil flames can be monitored with these flame monitors In particular flames the UV radiation of which a...

Page 29: ...he detector current Circuit for detector current measure ment A Incidence of light M Micro ammeter direct current internal resistance 5000 Refer to the data sheet of the respective automatic furnace c...

Page 30: ...only qualified personnel to per form commissioning and maintenance work A trouble free burner operation can be ensured only if the intensity of the UV radiation on the location of the detec tor is st...

Page 31: ...t temperatures will signifi cantly decrease the lifetime System of protection QRA2 IP40 QRA53 QRA55 IP 54 Dimensioned drawings All dimensions in mm Mounting position any Transport IEC 721 3 2 Climatic...

Page 32: ...ays a clean and fat free surface of all parts to be fitted into one another For reassembly Place the disk and the bush into their initial position wit hout rotating into one another make sure that the...

Page 33: ...0 Check the electrical connections 11 Check the burner head setting 12 Check the control equipment for proper operation setting and safety period 13 Check the pressure switch for pro per setting and o...

Page 34: ...move the casing cover When closing the casing cover do the following steps Screw in the screws 1 to 6 by doing only a few turns Tighten the screws beginning with the screws 1 and 2 followed by the scr...

Page 35: ...12 97 0 40 15 11 3 40 12 89 0 50 15 03 3 50 12 82 0 60 14 96 3 60 12 75 0 70 14 88 3 70 12 67 0 80 14 81 3 80 12 60 0 90 14 74 3 90 12 53 1 00 14 66 4 00 12 45 1 10 14 59 4 10 12 38 1 20 14 52 4 20 12...

Page 36: ...electrodes Cracked insulator Replace insulator Defective igni tion transformer Replace transformer Defective auto matic furnace controller Replace controller Burnt ignition cable Replace cable search...

Page 37: ...ause Remedy Dirty flame sen sor Clean flame sensor Burner fails to start Check connection of automatic fur nace controller Trouble lamp lights flame trouble Unlock and search for cause Weak flame sen...

Page 38: ...e due to any of the above mentioned points it will be necessary to test the burner functions very carefully Prevailing conditions The burner will be found to be out of operation and in faulty and inte...

Page 39: ...illing line 10 Limit transmitter 11 Vent line 12 Pump unit 13 Pressure holding valvel Stepless control with supply pump and ring line system Stepless control direct intake 1 Burner blower 2 Oil filter...

Page 40: ...h the required air quantity After the required pre ventilation time the air damper is moved into the ignition position Ignition is initiated and the oil supply is released The solenoid valves open and...

Page 41: ...41...

Page 42: ...44 Customer Service ECB GmbH Struppener Strasse 01796 Pirna...

Reviews: