3.2 Nominal data
Motor
M4D110-GF
Phase
3~
3~
3~
3~
Nominal voltage / VAC
230
230
277
400
Connection
Δ
Δ
Δ
Y
Frequency / Hz
50
60
60
50
Type of data definition
ml
ml
ml
ml
Valid for approval /
standard
CE
CE
CE
CE
Speed / min
-1
1350
1510
1590
1350
Power input / W
690
950
1050
690
Current draw / A
2.34
2.77
2.72
1.35
Max. back pressure / Pa
155
145
160
155
Min. ambient temperature
/ °C
-40
-40
-40
-40
Max. ambient
temperature
/ °C
65
60
60
65
Starting current / A
10
Maximum safe operating
speed / min
-1
1920
@ 55 °C
1920
@ 55 °C
1920
@ 55 °C
1920
@ 55 °C
Phase
3~
3~
Nominal voltage / VAC
400
480
Connection
Y
Y
Frequency / Hz
60
60
Type of data definition
ml
ml
Valid for approval /
standard
CE
CE
Speed / min
-1
1510
1590
Power input / W
950
1050
Current draw / A
1.6
1.57
Max. back pressure / Pa
145
160
Min. ambient temperature
/ °C
-40
-40
Max. ambient
temperature
/ °C
60
60
Starting current / A
9.6
Maximum safe operating
speed / min
-1
1920
@ 55 °C
1920
@ 55 °C
ml = Max. load · me = Max. efficiency · fa = Running at free air
cs = Customer specs · cu = Customer unit
Subject to alterations
3.3 Data according to ErP directive
Installation category
A
Efficiency category
Static
Variable speed drive
No
Specific ratio
*
1.00
*
Specific ratio = 1 + p
fs
/ 100 000 Pa
Actual
Request
2013
Request
2015
Overall efficiency η
es
/ %
33.3
28.5
32.5
Efficiency grade N
40.8
36
40
Power input P
e
/ kW
0.66
Air flow q
v
/ m³/h
5985
Pressure increase total p
sf
/ Pa
134
Speed n / min
-1
1355
Data definition with optimum efficiency.
The ErP data is determined using a motor-impeller combination in a standardised
measurement configuration.
3.4 Technical features
Mass
13 kg
Size
500 mm
Surface of rotor
Coated in black
Material of terminal box
PC / ABS plastic
Material of blades
Press-fitted sheet steel blank, sprayed
with PP plastic
Material of guard grille
Steel, coated in black plastic (RAL9005)
Number of blades
5
Direction of air flow
"V"
Direction of rotation
Counter-clockwise, seen on rotor
Type of protection
IP 54
Insulation class
"F"
Humidity class
F4-1
Mounting position
Shaft horizontal or rotor on bottom; rotor
on top on request
Condensate discharge
holes
Rotor-side
Operation mode
S1
Motor bearing
Ball bearing
Touch current acc.
IEC 60990 (measuring
network Fig. 4, TN
system)
<= 3.5 mA
Electrical leads
Via terminal box
Motor protection
Thermal overload protector (TOP)
brought out
Cable exit
Axial
Protection class
I (if protective earth is connected by
customer)
Product conforming
to standard
EN 61800-5-1; CE
Approval
EAC; UL 1004-1; VDE; CCC; CSA
C22.2 Nr.100
For cyclic speed loads, note that the rotating parts of the device
are designed for maximum one million load cycles. If you have
specific questions, contact ebm-papst for support.
Item no. 11295-5-9970 · Revision 82543 · Release 2014-05-08 · Page 5 / 11