background image

Operating instructions

S4D500-AM01-03

Translation of the original operating instructions

3.2 Nominal data

Motor

M4D110-GF

Phase

3~

3~

3~

3~

Nominal voltage / VAC

230

230

277

400

Connection

Δ

Δ

Δ

Y

Frequency / Hz

50

60

60

50

Type of data definition

ml

ml

ml

ml

Valid for approval /
standard

CE

CE

CE

CE

Speed / min

-1

1350

1510

1590

1350

Power input / W

690

950

1050

690

Current draw / A

2.34

2.77

2.72

1.35

Max. back pressure / Pa

155

145

160

155

Min. ambient temperature
/ °C

-40

-40

-40

-40

Max. ambient
temperature
/ °C

65

60

60

65

Starting current / A

10

Maximum safe operating
speed / min

-1

1920
@ 55 °C

1920
@ 55 °C

1920
@ 55 °C

1920
@ 55 °C

Phase

3~

3~

Nominal voltage / VAC

400

480

Connection

Y

Y

Frequency / Hz

60

60

Type of data definition

ml

ml

Valid for approval /
standard

CE

CE

Speed / min

-1

1510

1590

Power input / W

950

1050

Current draw / A

1.6

1.57

Max. back pressure / Pa

145

160

Min. ambient temperature
/ °C

-40

-40

Max. ambient
temperature
/ °C

60

60

Starting current / A

9.6

Maximum safe operating
speed / min

-1

1920
@ 55 °C

1920
@ 55 °C

ml = Max. load · me = Max. efficiency · fa = Running at free air

cs = Customer specs · cu = Customer unit

Subject to alterations

3.3 Data according to ErP directive

Installation category

A

Efficiency category

Static

Variable speed drive

No

Specific ratio

*

1.00

*

Specific ratio = 1 + p

fs

/ 100 000 Pa

Actual

Request
2013

Request
2015

Overall efficiency η

es

/ %

33.3

28.5

32.5

Efficiency grade N

40.8

36

40

Power input P

e

/ kW

0.66

Air flow q

v

/ m³/h

5985

Pressure increase total p

sf

/ Pa

134

Speed n / min

-1

1355

Data definition with optimum efficiency.

The ErP data is determined using a motor-impeller combination in a standardised

measurement configuration.

3.4 Technical features

Mass

13 kg

Size

500 mm

Surface of rotor

Coated in black

Material of terminal box

PC / ABS plastic

Material of blades

Press-fitted sheet steel blank, sprayed
with PP plastic

Material of guard grille

Steel, coated in black plastic (RAL9005)

Number of blades

5

Direction of air flow

"V"

Direction of rotation

Counter-clockwise, seen on rotor

Type of protection

IP 54

Insulation class

"F"

Humidity class

F4-1

Mounting position

Shaft horizontal or rotor on bottom; rotor
on top on request

Condensate discharge
holes

Rotor-side

Operation mode

S1

Motor bearing

Ball bearing

Touch current acc.
IEC 60990 (measuring
network Fig. 4, TN
system)

<= 3.5 mA

Electrical leads

Via terminal box

Motor protection

Thermal overload protector (TOP)
brought out

Cable exit

Axial

Protection class

I (if protective earth is connected by
customer)

Product conforming
to standard

EN 61800-5-1; CE

Approval

EAC; UL 1004-1; VDE; CCC; CSA
C22.2 Nr.100

For cyclic speed loads, note that the rotating parts of the device
are designed for maximum one million load cycles. If you have
specific questions, contact ebm-papst for support.

Item no. 11295-5-9970 · Revision 82543 · Release 2014-05-08 · Page 5 / 11

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for S4D500-AM01-03

Page 1: ...nly authorised specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety haz...

Page 2: ...ng hair loose items of clothing and jewellery could become entangled and pulled into the device You could be injured Do not wear any loose clothing or jewellery while working on rotating parts Protect...

Page 3: ...se hazards Operating the device with an imbalance e g caused by dirt deposits or icing Operation in medical equipment with a life sustaining or lifesaving function Operation with external vibrations M...

Page 4: ...ve the unit mm 1 Direction of air flow V 2 Tightening torque 1 5 0 2 Nm 3 Cable diameter min 6 mm max 12 mm tightening torque 2 0 3 Nm Item no 11295 5 9970 Revision 82543 Release 2014 05 08 Page 4 11...

Page 5: ...Power input Pe kW 0 66 Air flow qv m h 5985 Pressure increase total psf Pa 134 Speed n min 1 1355 Data definition with optimum efficiency The ErP data is determined using a motor impeller combination...

Page 6: ...necting the electrical system DANGER Electric voltage on the device Electric shock Always install a protective earth first Check the protective earth DANGER Incorrect insulation Risk of fatal injury f...

Page 7: ...equency inverter Please use a frequency converter only after consultation with ebm papst When a frequency converter is used for speed adjustment the maximum safe operating speed see 3 2 Nominal data m...

Page 8: ...o prevent it from being switched back on NOTE Lack of motor protection Without motor protection the motor can overheat and suffer damage Connect up the thermal overload protector installed in the coil...

Page 9: ...ction Y Star connection L1 V1 blue L2 U1 black L3 W1 brown W2 yellow U2 green V2 white TOP 2 x grey PE green yellow Item no 11295 5 9970 Revision 82543 Release 2014 05 08 Page 9 11 ebm papst Mulfingen...

Page 10: ...that all screws and screwed cable glands are properly tightened 4 7 Switch on device The device may only be switched on if it has been installed properly and in accordance with its intended use includ...

Page 11: ...on diagram Thermal overload protector responded Allow motor to cool off locate and rectify cause of error if necessary cancel restart lock out Unacceptable operating point Check operating point Overte...

Reviews: