background image

Operating instructions

S4D500-AM01-03

Translation of the original operating instructions

3.5 Mounting data

;

Secure the mounting screws against accidentally coming loose (e.g.
by using self-locking screws).

Strength class for
mounting screws

8.8

You can obtain additional mounting data from the product drawing if
necessary.

3.6 Transport and storage conditions

;

Use the device in accordance with its protection type.

Max. permissible
ambient motor temp.
(transp./ storage)

+ 80 °C

Min. permissible
ambient motor temp.
(transp./storage)

- 40 °C

4. CONNECTION AND START-UP

4.1 Connecting the mechanical system

CAUTION
Cutting and crushing hazard when removing the fan
from the packaging

→ Carefully remove the device from its packaging, only

touching the guard grille. Make sure to avoid any shock.

→ Wear safety shoes and cut-resistant safety gloves.

CAUTION
Heavy load when taking out the device

Bodily harm, e.g. back injuries, are possible.
→ Two people should remove the device out of its packaging

together.

;

Check the device for transport damage. Damaged devices must no
longer be installed.

;

Do not make any modifications, additions or renovations to the
device. Replacing the terminal box is not permitted.

;

Install the undamaged device according to your application.

4.2 Connecting the electrical system

DANGER
Electric voltage on the device

Electric shock
→ Always install a protective earth first.
→ Check the protective earth.

DANGER
Incorrect insulation

Risk of fatal injury from electric shock
→ Use only cables that meet the specified installation

requirements for voltage, current, insulation material, load etc.

→ Route cables such that they cannot be touched by any

rotating parts.

DANGER
Electrical load (>50 µC) between mains wire and
protective earth connection after switching of the supply
when switching multiple devices in parallel.

Electric shock, risk of injury
→ Make sure that sufficient protection against accidental contact

is provided.
Before working on the electrical connection, the
connections to the mains supply and PE must be shorted.

CAUTION
Electrical voltage

The fan is a built-in component and features no electrically
isolating switch.
→ Only connect the fan to circuits that can be switched off with

an all-pole separating switch.

→ When working on the fan, you must switch off the

installation/machine in which the fan is installed and secure it
from being switched on again.

NOTE
Water penetration into leads or wires

Water enters at the cable end on the customers side and can
damage the device.

Item no. 11295-5-9970 · Revision 82543 · Release 2014-05-08 · Page 6 / 11

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for S4D500-AM01-03

Page 1: ...nly authorised specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety haz...

Page 2: ...ng hair loose items of clothing and jewellery could become entangled and pulled into the device You could be injured Do not wear any loose clothing or jewellery while working on rotating parts Protect...

Page 3: ...se hazards Operating the device with an imbalance e g caused by dirt deposits or icing Operation in medical equipment with a life sustaining or lifesaving function Operation with external vibrations M...

Page 4: ...ve the unit mm 1 Direction of air flow V 2 Tightening torque 1 5 0 2 Nm 3 Cable diameter min 6 mm max 12 mm tightening torque 2 0 3 Nm Item no 11295 5 9970 Revision 82543 Release 2014 05 08 Page 4 11...

Page 5: ...Power input Pe kW 0 66 Air flow qv m h 5985 Pressure increase total psf Pa 134 Speed n min 1 1355 Data definition with optimum efficiency The ErP data is determined using a motor impeller combination...

Page 6: ...necting the electrical system DANGER Electric voltage on the device Electric shock Always install a protective earth first Check the protective earth DANGER Incorrect insulation Risk of fatal injury f...

Page 7: ...equency inverter Please use a frequency converter only after consultation with ebm papst When a frequency converter is used for speed adjustment the maximum safe operating speed see 3 2 Nominal data m...

Page 8: ...o prevent it from being switched back on NOTE Lack of motor protection Without motor protection the motor can overheat and suffer damage Connect up the thermal overload protector installed in the coil...

Page 9: ...ction Y Star connection L1 V1 blue L2 U1 black L3 W1 brown W2 yellow U2 green V2 white TOP 2 x grey PE green yellow Item no 11295 5 9970 Revision 82543 Release 2014 05 08 Page 9 11 ebm papst Mulfingen...

Page 10: ...that all screws and screwed cable glands are properly tightened 4 7 Switch on device The device may only be switched on if it has been installed properly and in accordance with its intended use includ...

Page 11: ...on diagram Thermal overload protector responded Allow motor to cool off locate and rectify cause of error if necessary cancel restart lock out Unacceptable operating point Check operating point Overte...