background image

Operating instructions

R4D450-AK03-05

Translation of the original operating instructions

3.2 Nominal data

Motor

M4D110-GF

Phase

3~

3~

3~

3~

Nominal voltage / VAC

230

277

400

400

Nominal voltage
range / VAC

220 .. 240

380 .. 415 380 .. 415

Wiring

Δ

Δ

Δ

Y

Frequency / Hz

50

60

50

50

Method of obtaining
data

ml

ml

ml

ml

Status

prelim.

Valid for approval/
standard

CE

CE

CE

CE

Speed (rpm) / min

-1

1090

1205

1350

1090

Power consumption / W

510

770

730

510

Current draw / A

1.52

2.02

1.48

0.88

Min. back pressure / Pa

0

0

0

0

Min. ambient
temperature / °C

-40

-40

-40

-40

Max. ambient
temperature / °C

80

55

80

80

Starting current / A

6.5

Phase

3~

3~

Nominal voltage / VAC

480

480

Nominal voltage
range / VAC
Wiring

Δ

Y

Frequency / Hz

60

60

Method of obtaining
data

ml

ml

Status

prelim.

Valid for approval/
standard

CE

CE

Speed (rpm) / min

-1

1580

1205

Power consumption / W

1180

770

Current draw / A

1.8

1.17

Min. back pressure / Pa

0

0

Min. ambient
temperature / °C

-40

-40

Max. ambient
temperature / °C

55

55

Starting current / A

7.5

ml = Max. load · me = Max. efficiency · fa = Free air

cs = Customer specification · ce = Customer equipment

Subject to change

3.3 Data according to Commission Regulation (EU) 327/
2011

Actual

Req. 2015

01 Overall efficiency η

es

/ %

51.1

50

02 Measurement category

A

03 Efficiency category

Static

04 Efficiency grade N

63.1

62

05 Variable speed drive

No

06 Year of manufacture

The year of manufacture is specified on the
product's rating label.

07 Manufacturer

ebm-papst Mulfingen GmbH & Co. KG
Amtsgericht (court of registration) Stuttgart ·
HRA 590344
D-74673 Mulfingen

08 Type

R4D450-AK03-05

09 Power consumption P

e

/ kW

0.72

09 Air flow q

v

/ m³/h

3810

09 Pressure increase total p

fs

/

Pa

350

10 Speed (rpm) n / min

-1

1350

11 Specific ratio

*

1.00

12 Recycling/disposal

Information on recycling and disposal is
provided in the operating instructions.

13 Maintenance

Information on installation, operation and
maintenance is provided in the operating
instructions.

14 Additional components

Components used to calculate the energy
efficiency that are not apparent from the
measurement category are detailed in the
CE declaration.

*

Specific ratio = 1 + p

fs

/ 100 000 Pa

Data obtained at optimum efficiency level. The efficiency values displayed for achieving

conformity with the Ecodesign Regulation EU 327/2011 has been reached with defined air

duct components (e.g. inlet rings). The dimensions must be requested from ebm-papst. If

other air conduction geometries are used on the installation side, the ebm-papst evaluation

loses its validity/the conformity must be confirmed again. The product does not fall within

the scope of Regulation (EU) 2019/1781 due to the exception specified in Article 2 (2a)

(motors completely integrated into a product).

3.4 Technical description

Weight

11.7 kg

Size

450 mm

Motor size

110

Rotor surface

Cast in aluminum

Terminal box material

ABS plastic, black

Impeller material

Sheet aluminum

Number of blades

6

Direction of rotation

Clockwise, viewed toward rotor

Degree of protection

IP54

Insulation class

"F"

Moisture (F) /
Environmental (H)
protection class

H2

Ambient temperature
note

Occasional start-up at temperatures
between -40°C and -25°C is permitted.
For continuous operation at ambient
temperatures below -25°C (such as
refrigeration applications), use must be
made of a fan design with special low-
temperature bearings.

Installation position

Shaft horizontal or rotor on bottom; rotor
on top on request

Condensation
drainage holes

On rotor side

Mode

S1

Motor bearing

Ball bearing

Touch current
according to IEC
60990 (measuring
circuit Fig. 4, TN
system)

<= 3.5 mA

Electrical hookup

Terminal box with cable

Item no. 11001-5-9970 · ENU · Change 235653 · Approved 2021-11-15 · Page 5 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for R4D450-AK03-05

Page 1: ...echnical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the device must be assessed again following installation in the final product The locally applicable industrial safety regulations are always to be observed when w...

Page 2: ... Injuries can result Do not wear any loose fitting or dangling clothing or jewelry while working on rotating parts Protect long hair with a cap 1 7 Emissions WARNING Depending on the installation and operating conditions the sound pressure level may exceed 70 dB A Risk of noise induced hearing loss Take appropriate technical safety measures Protect operating personnel with appropriate safety equip...

Page 3: ...following ways is prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operation operation with severe vibration This also includes vibration transmitted to the fan from the customer installation Operation in medical equipment with a life sustaining or life support function Conveying solids in the flow medium Painting the ...

Page 4: ...ncluded in scope of delivery other inlet rings on request 2 Max clearance for screw 12 mm 3 Cable diameter min 6 mm max 12 mm tightening torque 2 0 3 Nm 4 Tightening torque 1 0 0 15 Nm Item no 11001 5 9970 ENU Change 235653 Approved 2021 11 15 Page 4 12 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Page 5: ...3 Maintenance Information on installation operation and maintenance is provided in the operating instructions 14 Additional components Components used to calculate the energy efficiency that are not apparent from the measurement category are detailed in the CE declaration Specific ratio 1 pfs 100 000 Pa Data obtained at optimum efficiency level The efficiency values displayed for achieving conform...

Page 6: ...rage 80 C Min permitted ambient temp for motor transport storage 40 C 4 CONNECTION AND STARTUP 4 1 Mechanical connection CAUTION Cutting and crushing hazard when removing fan from packaging Carefully remove the device from its packaging by the fan impeller Strictly avoid shocks Wear safety shoes and cut resistant safety gloves CAUTION Heavy load when unpacking device Risk of physical injury such a...

Page 7: ...ety while operating the device 4 2 3 Voltage control NOTE Current overshoots may occur if speed control is implemented by transformers or electronic voltage regulators e g phase control Depending on the type of installation of the device noise and vibration may also occur in the case of phase control Vibration can lead to bearing damage and thus premature failure Heating up of the motor when using...

Page 8: ... built in component and has no disconnecting switch Connect the device to a suitable tripping unit Only connect the device to circuits that can be switched off with an all pole disconnection switch When working on the device secure the system machine in which the device is installed so as to prevent it from being switched back on NOTE Lack of motor protection Without motor protection the motor can...

Page 9: ...ection Y Star connection L1 U1 black L2 V1 blue L3 W1 brown W2 yellow U2 green V2 white TOP 2x gray PE green yellow Item no 11001 5 9970 ENU Change 235653 Approved 2021 11 15 Page 9 12 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Page 10: ... visible external damage and make sure the protective devices are functional Check the fan s air flow paths for foreign matter and remove any foreign matter found Apply the nominal supply voltage NOTE Damage to the device from vibration Bearing damage shorter service life Low vibration operation of the fan must be ensured over the entire speed control range Severe vibration can arise for instance ...

Page 11: ...al overload protector activated Allow motor to cool off locate and rectify cause of error release restart lockout if necessary Impermissible point of operation Check point of operation Motor overtemperature Ambient temperature too high Reduce ambient temperature if possible Deficient cooling Improve cooling In the event of further malfunctions contact ebm papst 5 1 Vibration testing Checking of fa...

Page 12: ...esign technical safety and health protection are fixed criteria The following section contains recommendations for ecological disposal of the product and its components 5 4 1 Country specific legal requirements NOTE Country specific legal requirements Always observe the applicable country specific legal regulations with regard to the disposal of products or waste occurring in the various phases of...

Reviews: