Operating instructions

R3G355-AY43-21

Translation of the original operating instructions

3.2 Nominal data

Motor

M3G112-GA

Phase

1~

Nominal voltage / VAC

230

Nominal voltage
range / VAC

200 .. 277

Frequency / Hz

50/60

Type of data definition

ml

Speed (rpm) / min

-1

2450

Power input / W

1400

Current draw / A

6.0

Min. ambient
temperature / °C

-25

Max. ambient
temperature / °C

50

ml = Max. load · me = Max. efficiency · fa = Running at free air

cs = Customer specs · cu = Customer unit

Subject to alterations

3.3 Data in accordance with ecodesign regulation EU 327/
2011

Actual

Request 2015

01 Overall efficiency η

es

/ %

63.8

53

02 Measurement category

A

03 Efficiency category

Static

04 Efficiency grade N

72.8

62

05 Variable speed drive

Yes

06 Year of manufacture

The year of manufacture is specified on the
rating plate on the product.

07 Manufacturer

ebm-papst Mulfingen GmbH & Co. KG
County court Stuttgart · HRA 590344
D-74673 Mulfingen

08 Type

R3G355-AY43-21

09 Power input P

ed

/ kW

1.4

09 Air flow q

v

/ m³/h

3755

09 Pressure increase total p

sf

/

Pa

794

10 Speed (rpm) n / min

-1

2380

11 Specific ratio

*

1.01

12 Recycling/disposal

Information on recycling and disposal is
provided in the operating instructions.

13 Maintenance

Information on installation, operation and
maintenance is provided in the operating
instructions.

14 Additional components

Components used to calculate the energy
efficiency that are not apparent from the
measurement category are detailed in the
CE declaration.

*

Specific ratio = 1 + p

fs

/ 100 000 Pa

Data definition with optimum efficiency. The ErP data is determined using a motor-impeller

combination in a standardised measurement configuration.

3.4 Technical features

Mass

14 kg

Size

355 mm

Motor size

112

Surface of rotor

Coated in black

Material of electronics
housing

Die-cast aluminium

Material of impeller

Aluminium sheet

Number of blades

7

Direction of rotation

Clockwise, seen on rotor

Type of protection

IP54

Insulation class

"B"

Humidity (F) /
environmental
protection class (H)

H1

Mounting position

Shaft horizontal or rotor on bottom; rotor
on top on request

Condensation
drainage holes

Rotor-side

Operation mode

S1

Motor bearing

Ball bearing

Technical features

- Output 10 VDC, max. 10 mA
- Output 20 VDC, max. 50 mA
- Output for slave 0-10 V
- Tach output
- Input for sensor 0-10 V or 4-20 mA
- External 24 V input (programming)
- External release input
- Alarm relay
- Integrated PID controller
- Output limit
- Motor current limit
- PFC, active
- RS485 MODBUS RTU
- Soft start
- Control input 0-10 VDC / PWM
- Control interface with SELV potential
safely disconnected from the mains
- Over-temperature protected
electronics / motor
- Line undervoltage / phase failure
detection

Touch current acc.
IEC 60990 (measuring
network Fig. 4, TN
system)

<= 3.5 mA

Electrical connection

Terminal box

Motor protection

Thermal overload protector (TOP) wired
internally

Cable exit

Variable

Protection class

I (if protective earth is connected by
customer)

Product conforming
to standard

EN 61800-5-1; CE

Approval

EAC; UL 1004-7 + 60730-1

Item no. 51028-5-9970 · ENG · Revision 212555 · Release 2020-04-29 · Page 5 / 14

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for R3G355-AY43-21

Page 1: ...ce to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it i...

Page 2: ...mpliant 1 7 Mechanical movement DANGER Rotating device Body parts that come into contact with the rotor and impeller can be injured Secure the device against accidental contact Before working on the s...

Page 3: ...Operating the device with an imbalance e g caused by dirt deposits or icing Resonance mode operation with heavy vibrations These also include vibrations that are transmitted from the customer system...

Page 4: ...6 Nm 2 Accessory part inlet nozzle 35675 2 4013 with a pressure tap not included in the standard scope of delivery other inlet nozzles on request 3 Depth of screw 12 16 mm 4 Tightening torque 3 5 0 5...

Page 5: ...on with optimum efficiency The ErP data is determined using a motor impeller combination in a standardised measurement configuration 3 4 Technical features Mass 14 kg Size 355 mm Motor size 112 Surfac...

Page 6: ...Make sure to avoid any shock Wear safety shoes and cut resistant safety gloves CAUTION Heavy load when taking out the device Bodily harm e g back injuries are possible Two people should remove the dev...

Page 7: ...alues are typically in the range 250 mA At the same time the effective power in this operating state operational readiness is typically 4 W 4 2 3 Residual current operated device If the use of a resid...

Page 8: ...n front of the cable gland for example When routing the cable ensure that the screwed cable glands are arranged at the bottom The cables must always be routed downwards Fig 3 Cable routing for fans in...

Page 9: ...ive to input Ain1 SELV KL3 5 10 V Fixed voltage output 10 VDC 10 V 3 max 10 mA short circuit proof power supply for ext devices e g potentiometer SELV KL3 6 Ain1 I Analogue input 1 set value 4 20 mA R...

Page 10: ...k parametrisable curve only usable as alternative to input Ain2 SELV KL3 12 20 V Fixed voltage output 20 VDC 20 V 25 10 max 50 mA short circuit proof power supply for ext devices e g sensors SELV Alte...

Page 11: ...determine the speed ranges with excessive vibration levels and also any resonance frequencies that may be present When regulating the speed pass through resonance ranges as quickly as possible or fin...

Page 12: ...during cleaning make sure to remove them afterwards Motor does not turn Mechanical blockage Switch off de energise and remove mechanical blockage Mains supply voltage faulty Check mains supply voltage...

Page 13: ...r replacement of the device Check the device for damage to blades and housing Visual inspection At least every 6 months Replacement of the device Mounting the connection lines Visual inspection At lea...

Page 14: ...external rotor motors from ebm papst Mulfingen GmbH Co KG Ferrite magnets can be disposed of in the same way as normal iron and steel Electrical insulating materials on the product in cables and wires...