Operating instructions

R3G355-AY43-21

Translation of the original operating instructions

No.

Conn.

Designation

Function / assignment

KL3

9

Din3

Digital input 3: Controller function of integrated controller, depending on EEPROM setting, the controller function
of the integrated controller can be selected via the bus or the digital input Din 3
normal: pin open or applied voltage 5-50 VDC
inverse: bridge to GND or applied voltage <1 VDC; SELV

KL3

10

GND

Signal ground for control interface, SELV

KL3

11

Ain2 U

Analogue input 2, actual value: 0-10 V, Ri = 100 kΩ, parametrisable curve, only usable as alternative to input
Ain2; SELV

KL3

12

+20 V

Fixed voltage output 20 VDC, +20 V +25/-10%, max. 50 mA, short-circuit-proof, power supply for ext.
devices (e.g. sensors); SELV
Alternatively: +24 VDC input for parametrisation without mains power

KL3

13

Ain2 I

Analogue input 2, actual value: 4-20 mA, Ri = 100 Ω, parametrisable curve, only for use as alternative to input
Ain2 U; SELV

KL3

14

Aout

Analogue output 0-10 VDC, max. 5 mA, output of the current motor level control coefficient / motor speed
parametrisable curve; SELV

Item no. 51028-5-9970 · ENG · Revision 212555 · Release 2020-04-29 · Page 10 / 14

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for R3G355-AY43-21

Page 1: ...ce to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it i...

Page 2: ...mpliant 1 7 Mechanical movement DANGER Rotating device Body parts that come into contact with the rotor and impeller can be injured Secure the device against accidental contact Before working on the s...

Page 3: ...Operating the device with an imbalance e g caused by dirt deposits or icing Resonance mode operation with heavy vibrations These also include vibrations that are transmitted from the customer system...

Page 4: ...6 Nm 2 Accessory part inlet nozzle 35675 2 4013 with a pressure tap not included in the standard scope of delivery other inlet nozzles on request 3 Depth of screw 12 16 mm 4 Tightening torque 3 5 0 5...

Page 5: ...on with optimum efficiency The ErP data is determined using a motor impeller combination in a standardised measurement configuration 3 4 Technical features Mass 14 kg Size 355 mm Motor size 112 Surfac...

Page 6: ...Make sure to avoid any shock Wear safety shoes and cut resistant safety gloves CAUTION Heavy load when taking out the device Bodily harm e g back injuries are possible Two people should remove the dev...

Page 7: ...alues are typically in the range 250 mA At the same time the effective power in this operating state operational readiness is typically 4 W 4 2 3 Residual current operated device If the use of a resid...

Page 8: ...n front of the cable gland for example When routing the cable ensure that the screwed cable glands are arranged at the bottom The cables must always be routed downwards Fig 3 Cable routing for fans in...

Page 9: ...ive to input Ain1 SELV KL3 5 10 V Fixed voltage output 10 VDC 10 V 3 max 10 mA short circuit proof power supply for ext devices e g potentiometer SELV KL3 6 Ain1 I Analogue input 1 set value 4 20 mA R...

Page 10: ...k parametrisable curve only usable as alternative to input Ain2 SELV KL3 12 20 V Fixed voltage output 20 VDC 20 V 25 10 max 50 mA short circuit proof power supply for ext devices e g sensors SELV Alte...

Page 11: ...determine the speed ranges with excessive vibration levels and also any resonance frequencies that may be present When regulating the speed pass through resonance ranges as quickly as possible or fin...

Page 12: ...during cleaning make sure to remove them afterwards Motor does not turn Mechanical blockage Switch off de energise and remove mechanical blockage Mains supply voltage faulty Check mains supply voltage...

Page 13: ...r replacement of the device Check the device for damage to blades and housing Visual inspection At least every 6 months Replacement of the device Mounting the connection lines Visual inspection At lea...

Page 14: ...external rotor motors from ebm papst Mulfingen GmbH Co KG Ferrite magnets can be disposed of in the same way as normal iron and steel Electrical insulating materials on the product in cables and wires...