3.2 Nominal data

Motor

M3G055-DF

Phase

1~

Nominal voltage / VAC

230

Nominal voltage
range / VAC

200 .. 240

Frequency / Hz

50/60

Method of obtaining
data

ml

Speed / min

-1

2860

Power consumption / W

170

Current draw / A

1.4

Min. ambient
temperature / °C

-25

Max. ambient
temperature / °C

60

ml = Max. load · me = Max. efficiency · fa = Free air

cs = Customer specification · ce = Customer equipment

Subject to change

3.3 Data according to ErP Directive

Actual

Req. 2015

01 Overall efficiency η

es

/ %

61.7

43.1

02 Measurement category

A

03 Efficiency category

Static

04 Efficiency grade N

80.6

62

05 Variable speed drive

Yes

06 Year of manufacture

The year of manufacture is specified on the
product's rating label.

07 Manufacturer

ebm-papst Mulfingen GmbH & Co. KG
Amtsgericht (court of registration) Stuttgart ·
HRA 590344
D-74673 Mulfingen

08 Type

R3G225-RE07-01

09 Power consumption P

ed

/ kW

0.16

09 Air flow q

v

/ m³/h

705

09 Pressure increase total p

sf

/

Pa

458

10 Speed n / min

-1

2865

11 Specific ratio

*

1.00

12 Recycling/disposal

Information on recycling and disposal is
provided in the operating instructions.

13 Maintenance

Information on installation, operation and
maintenance is provided in the operating
instructions.

14 Additional components

Components used to calculate the energy
efficiency that are not apparent from the
measurement category are detailed in the
CE declaration.

*

Specific ratio = 1 + p

fs

/ 100 000 Pa

Data obtained at optimum efficiency level. The ErP data is determined using a motor-impeller

combination in a standardized measurement setup.

3.4 Technical description

Weight

1.7 kg

Fan size

225 mm

Rotor surface

Thick-film passivated

Electronics housing
material

Die-cast aluminum

Impeller material

PA plastic

Number of blades

7

Direction of rotation

Clockwise, viewed toward rotor

Degree of protection

IP54

Insulation class

"B"

Installation position

Shaft horizontal or rotor on bottom; rotor
on top on request

Condensation
drainage holes

None, open rotor

Mode

S1

Motor bearing

Ball bearing

Technical features

- Speed setting input (230 V)
- Motor current limitation
- Soft start
- Thermal overload protection for
electronics/motor
- Line undervoltage detection

Speed levels

2

Touch current
according to IEC
60990 (measuring
circuit Fig. 4, TN
system)

<= 3.5 mA

Motor protection

Locked-rotor protection

with cable

Variable

Protection class

I (with customer connection of protective
earth)

Conformity with
standards

EN 60335-1; CE

Approval

CCC; CSA C22.2 No. 77; UL 2111

With regard to cyclic speed loads, note that the rotating parts of
the device are designed for a maximum of one million load
cycles. If you have special questions, consult ebm-papst for
support.

3.5 Mounting data

For screw clearance, see Chapter 3.1 Product drawing

;

Secure the screws against unintentional loosening (e.g. use self-
locking screws).

Strength class of
screws

8.8

Any further mounting data required can be taken from the product drawing.

3.6 Transport and storage conditions

;

Use the device in accordance with its degree of protection.

Max. permitted
ambient temp. for
motor (transport/
storage)

+ 80 °C

Min. permitted
ambient temp. for
motor (transport/
storage)

- 40 °C

Item no. 51187-5-9970 · ENU · Change 89188 · Approved 2016-04-18 · Page 5 / 10

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for R3G225-RE07-01

Page 1: ...ted maintained and otherwise used by suitably qualified trained and authorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform wo...

Page 2: ...he user NOTE Electrical or electromagnetic interference after installing the device in customer equipment Verify that the entire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device R...

Page 3: ...ve devices Following the operating instructions Improper use In particular operating the device in the following ways is prohibited and could be hazardous Operating the device in an unbalanced state e...

Page 4: ...t ring 96358 2 4013 not included in scope of delivery 2 Cable PVC 4G 0 5 mm 4x crimped splices 3 Max clearance for screw 5 mm 4 Max clearance for screw 10 mm Item no 51187 5 9970 ENU Change 89188 Appr...

Page 5: ...t setup 3 4 Technical description Weight 1 7 kg Fan size 225 mm Rotor surface Thick film passivated Electronics housing material Die cast aluminum Impeller material PA plastic Number of blades 7 Direc...

Page 6: ...ower supply matches the device voltage Only use cables designed for the current level indicated on the nameplate For determining the cross section note the sizing criteria according to EN 61800 5 1 Th...

Page 7: ...230 VAC 50 60 Hz see nameplate for voltage range CON 11 N blue Neutral conductor CON 12 PE green yellow Protective earth CON 70 SL brown Speed selection switch open speed 1 switch closed speed 2 Item...

Page 8: ...the blockage is removed the motor restarts automatically 6 MAINTENANCE MALFUNCTIONS POSSIBLE CAUSES AND REMEDIES Do not perform any repairs on your device Send the device to ebm papst for repair or r...

Page 9: ...he basis of German standards Right from the development stage ecological design technical safety and health protection are fixed criteria The following section contains recommendations for ecological...

Page 10: ...mploying the proper procedures for electronic scrap Please contact ebm papst for any other questions on disposal Item no 51187 5 9970 ENU Change 89188 Approved 2016 04 18 Page 10 10 ebm papst Mulfinge...

Reviews: