Operating instructions

R3G175-RC05-03

Translation of the original operating instructions

4. CONNECTION AND START-UP

4.1 Connecting the mechanical system

CAUTION
Cutting and crushing hazard when removing the fan
from the packaging

→ Carefully hold the impeller to remove the device from its

packaging. Make sure to avoid any shock.

→ Wear safety shoes and cut-resistant safety gloves.

;

Check the device for transport damage. Damaged devices must no
longer be installed.

;

Install the undamaged device according to your application.

4.2 Connecting the electrical system

DANGER
Electric voltage on the device

Electric shock
→ Always install a protective earth first.
→ Check the protective earth.

DANGER
Incorrect insulation

Risk of fatal injury from electric shock
→ Use only cables that meet the specified installation

requirements for voltage, current, insulation material, load etc.

→ Route cables such that they cannot be touched by any

rotating parts.

DANGER
Electrical load (>50 µC) between mains wire and
protective earth connection after switching of the supply
when switching multiple devices in parallel.

Electric shock, risk of injury
→ Make sure that sufficient protection against accidental contact

is provided.
Before working on the electrical connection, the
connections to the mains supply and PE must be shorted.

CAUTION
Electrical voltage

The fan is a built-in component and features no electrically
isolating switch.
→ Only connect the fan to circuits that can be switched off with

an all-pole separating switch.

→ When working on the fan, you must switch off the

installation/machine in which the fan is installed and secure it
from being switched on again.

NOTE
Water penetration into leads or wires

Water enters at the cable end on the customers side and can
damage the device.
→ Make sure that the cable end is connected in a dry

environment.

Connect the device only to circuits that can be switched off
using an all-pole disconnecting switch.

4.2.1 Prerequisites

;

Check whether the data on the type plate agree with the connection
data.

;

Before connecting the device, ensure that the supply voltage matches
the operating voltage of the device.

;

Only use cables designed for current according to the type plate.
For determining the cross-section, follow the basic principles in
accordance with EN 61800-5-1. The protective earth must have a
cross-section equal to or greater than the outer conductor cross-
section.
We recommend the use of 105°C cables. Ensure that the minimum
cable cross-section is at least
AWG26/0.13 mm².

4.2.2 Idle current

Because of the EMC filter integrated for compliance with EMC
limits (interference emission and interference immunity), idle
currents in the mains cable can be measured even when the
motor is at a standstill and the mains voltage is switched on.

The values lie in a range of typical < 50 mA.

The effective power in this operating state (readiness for operation) is
simultaneously at typical < 2 W.

4.2.3 Residual current operated device

Only pulse-current sensitive and/or universal RCD protective
devices (Type A or B) are permitted. Like frequency inverters,
RCD protective devices cannot provide personal safety while
operating the device. When switching on the power supply of
the device, pulsed charge currents from the capacitors in the
integrated EMC filter can lead to the RCD protective devices
triggering without delay. We recommend residual current
devices with a trigger threshold of 300 mA and delayed
triggering (super-resistant, characteristic K).

4.2.4 Locked-rotor protection

Due to the locked-rotor protection, the start-up current (LRA) is
equal to or less than the nominal current (FLA).

4.3 Connection of the cables

External leads are brought out of device.

;

First connect the "PE" (protective earth) connection.

Connect the lines according to your application. When doing so,
observe chapter 4.4 Connection screen.

Item no. 53282-5-9970 · Revision 82891 · Release 2014-03-20 · Page 6 / 10

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for R3G175-RC05-03

Page 1: ...authorised specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards...

Page 2: ...t the entire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device Body parts that come into contact with the rotor and impeller can be injured Secure the device against accidental con...

Page 3: ...the following ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Moving air that contains abrasive particles Moving highl...

Page 4: ...zle 09576 2 4013 not included in scope of delivery 2 Depth of screw max 5 mm 3 Connection line PVC AWG20 3x lead tips crimped 4 Connection line PVC AWG22 4x lead tips crimped Item no 53282 5 9970 Revi...

Page 5: ...r protection Locked rotor protection Cable exit Variable Protection class I if protective earth is connected by customer Product conforming to standard CE Approval CSA C22 2 Nr 77 UL 2111 For cyclic s...

Page 6: ...ing switch 4 2 1 Prerequisites Check whether the data on the type plate agree with the connection data Before connecting the device ensure that the supply voltage matches the operating voltage of the...

Page 7: ...ND blue GND Connection for control interface 2 0 10V PWM yellow Control input 0 10 V or PWM electrically isolated 3 10V max 1 1mA red Voltage output 10 V 1 1 mA electrically isolated not short circuit...

Page 8: ...the nominal voltage to the voltage supply Start the device by changing the input signal 4 7 Switching off the device Switching off the device during operation Switch off the device via the control inp...

Page 9: ...ise correct connection see connection diagram Overtemperature of electronics motor Insufficient cooling Improve cooling Let the device cool down To reset the error message switch off the mains supply...

Page 10: ...the wires for damage Visual inspection At least every 6 months Replace wires Impeller for wear deposits corrosion and damage Visual inspection At least every 6 months Clean or replace impeller Item n...