Operating instructions

K3G630-PW04-01

Translation of the original operating instructions

3.2 Nominal data

Motor

M3G200-LA

Phase

3~

Nominal voltage / VAC

400

Nominal voltage
range / VAC

380 .. 480

Frequency / Hz

50/60

Method of obtaining
data

ml

Speed (rpm) / min

-1

1950

Power consumption / W

9780

Current draw / A

15.2

Min. ambient
temperature / °C

-40

Max. ambient
temperature / °C

40

ml = Max. load · me = Max. efficiency · fa = Free air

cs = Customer specification · ce = Customer equipment

Subject to change

3.3 Data according to Commission Regulation (EU) 327/
2011

Actual

Req. 2015

01 Overall efficiency η

es

/ %

67.2

61.8

02 Measurement category

A

03 Efficiency category

Static

04 Efficiency grade N

67.4

62

05 Variable speed drive

Yes

06 Year of manufacture

The year of manufacture is specified on the
product's rating label.

07 Manufacturer

ebm-papst Mulfingen GmbH & Co. KG
Amtsgericht (court of registration) Stuttgart ·
HRA 590344
D-74673 Mulfingen

08 Type

K3G630-PW04-01

09 Power consumption P

ed

/ kW

9.56

09 Air flow q

v

/ m³/h

17165

09 Pressure increase total p

fs

/

Pa

1304

10 Speed (rpm) n / min

-1

1945

11 Specific ratio

*

1.01

12 Recycling/disposal

Information on recycling and disposal is
provided in the operating instructions.

13 Maintenance

Information on installation, operation and
maintenance is provided in the operating
instructions.

14 Additional components

Components used to calculate the energy
efficiency that are not apparent from the
measurement category are detailed in the
CE declaration.

*

Specific ratio = 1 + p

fs

/ 100 000 Pa

Data obtained at optimum efficiency level. The efficiency values displayed for achieving

conformity with the Ecodesign Regulation EU 327/2011 has been reached with defined air

duct components (e.g. inlet rings). The dimensions must be requested from ebm-papst. If

other air conduction geometries are used on the installation side, the ebm-papst evaluation

loses its validity/the conformity must be confirmed again. The product does not fall within

the scope of Regulation (EU) 2019/1781 due to the exception specified in Article 2 (2a)

(motors completely integrated into a product).

3.4 Technical description

Weight

114.7 kg

Size

630 mm

Motor size

200

Rotor surface

Painted black

Electronics housing
material

Die-cast aluminum, painted black

Impeller material

Sheet aluminum

Support plate material

Sheet steel, galvanized

Spacer material

Aluminum

Inlet nozzle material

Sheet steel, galvanized

Number of blades

5

Direction of rotation

Clockwise, viewed toward rotor

Degree of protection

IP55

Insulation class

"F"

Moisture (F) /
Environmental (H)
protection class

H1

Ambient temperature
note

Occasional start-up at temperatures
between -40°C and -25°C is permitted.
For continuous operation at ambient
temperatures below -25°C (such as
refrigeration applications), use must be
made of a fan design with special low-
temperature bearings.

Installation position

See legend on product drawing

Condensation
drainage holes

On rotor side

Mode

S1

Motor bearing

Ball bearing

Technical features

- Output 10 VDC, max. 10 mA
- Output 20 VDC, max. 50 mA
- Output for slave 0-10 V
- Operation and alarm display
- Input for sensor 0-10 V or 4-20 mA
- External 24 V input (parameter setting)
- External release input
- Alarm relay
- Integrated PID controller
- Power limiter
- Motor current limitation
- PFC, passive
- RS-485 MODBUS-RTU
- Soft start
- EEPROM write cycles: 100,000
maximum
- Control input 0-10 VDC / PWM
- Control interface with SELV potential
safely disconnected from the mains
- Temperature derating
- Thermal overload protection for
electronics/motor
- Line undervoltage / phase failure
detection

Touch current
according to IEC
60990 (measuring
circuit Fig. 4, TN
system)

<= 3.5 mA

Electrical hookup

Terminal box

Motor protection

Reverse polarity and locked-rotor
protection

Item no. 55797-5-9970 · ENU · Change 277818 · Approved 2023-04-27 · Page 5 / 13

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for K3G630-PW04-01

Page 1: ...ed technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety...

Page 2: ...have to be taken by the user NOTE Electrical or electromagnetic interference after installing the device in customer equipment Verify that the entire setup is EMC compliant 1 7 Mechanical movement DAN...

Page 3: ...nding or in IT power systems The device is to be used in networks with network quality characteristics as per EN 50160 Using the device only in stationary systems Performing all maintenance work Conve...

Page 4: ...torque 6 0 9 Nm 5 Tightening torque 3 5 0 5 Nm 6 Attachment holes for FlowGrid 00630 2 2957 not included in scope of delivery 7 Motor support plate Installation position Only base mounting shaft hori...

Page 5: ...validity the conformity must be confirmed again The product does not fall within the scope of Regulation EU 2019 1781 due to the exception specified in Article 2 2a motors completely integrated into a...

Page 6: ...ial environment If several devices are connected in parallel on the supply side so that the line current of the arrangement is in the range 16 75 A this arrangement conforms to IEC 61000 3 12 provided...

Page 7: ...g parts DANGER Electrical charge 50 C between phase conductor and protective earth connection after switching off supply with multiple devices connected in parallel Electric shock risk of injury Ensur...

Page 8: ...For asymmetrical power systems or if a phase fails the leakage current can increase to a multiple of the nominal value 4 2 6 Locked rotor protection Due to the locked rotor protection the starting cu...

Page 9: ...cs enable pin open or applied voltage 5 50 VDC disable bridge to GND or applied voltage 1 VDC reset function triggers software reset after a level change to 1 V KL 3 8 Din2 Digital input 2 Switching p...

Page 10: ...ng Either run through the resonant range as quickly as possible with speed control or find another remedy Operation with excessively high vibration levels can lead to premature failure The maximum per...

Page 11: ...e from supply and remove mechanical blockage Line voltage faulty Check line voltage restore power supply Attention The error message resets automatically Device restarts automatically without warning...

Page 12: ...aintenance intervals to the actual level of dust exposure 6 3 Safety inspection NOTE High voltage test The integrated EMC filter has Y capacitors The tripping current is exceeded when AC testing volta...

Page 13: ...tallic materials are generally considered to be fully recyclable Separate the components for recycling into the following categories Steel and iron Aluminum Non ferrous metal e g motor windings Plasti...

Reviews: