Operating instructions

G2E160-AY50-91

Translation of the original operating instructions

3.6 Transport and storage conditions

Max. permissible
ambient motor temp.
(transp./ storage)

+ 80 °C

Min. permissible
ambient motor temp.
(transp./storage)

- 40 °C

4. CONNECTION AND START-UP

4.1 Connecting the mechanical system

CAUTION
Cutting and crushing hazard when removing blower
from packaging

→ Carefully remove the blower from its packaging by grasping

hold of the housing. Never subject to impact.

→ Wear safety shoes and cut-resistant safety gloves.

NOTE
Damage to device from vibration

Bearing damage, reduced service life
→ Forces or impermissibly high vibration levels must not be

transmitted to the fan from system components.

→ If the fan is connected to air ducts, it should isolated from

vibrations, for example using compensators or similar
elements.

→ Fasten the fan to the substructure without distorting it.

;

Check the device for transport damage. Damaged devices must no
longer be installed.

;

Install the undamaged device according to your application.

CAUTION
Possibility of damage to the device

Serious damage may result if the device slips during assembly.
→ Keep the device fixed in position at the installation location

until all attachment screws have been tightened.

The fan must not be strained on fastening.

4.2 Connecting the electrical system

DANGER
Electric voltage on the device

Electric shock
→ Always install a protective earth first.
→ Check the protective earth.

DANGER
Incorrect insulation

Risk of fatal injury from electric shock
→ Use only cables that meet the specified installation

requirements for voltage, current, insulation material, load etc.

→ Route cables such that they cannot be touched by any

rotating parts.

CAUTION
Electrical voltage

The device is a built-in component and features no electrically
isolating switch.

→ Connect the device only to circuits that can be switched off

using an all-pole disconnecting switch.

→ When working on the device, you must switch off the

system/machine in which the device is installed and secure
it from being switched on again.

NOTE
Water penetration into leads or wires

Water enters at the cable end on the customers side and can
damage the device.
→ Make sure that the cable end is connected in a dry

environment.

Connect the device only to circuits that can be switched off
using an all-pole disconnecting switch.

4.2.1 Prerequisites

;

Check that the data on the type plate match the connection data.

;

If the operating capacitor is not installed by ebm-papst, check whether
the data of the operating capacitor match the data on the type plate.

;

Before connecting the device, ensure that the supply voltage matches
the operating voltage of the device.

;

Only use cables designed for current according to the type plate.
For determining the cross-section, follow the basic principles in
accordance with EN 61800-5-1. The protective earth must have a
cross-section equal to or greater than the outer conductor cross-
section.
We recommend the use of 105°C cables. Ensure that the minimum
cable cross-section is at least
AWG26/0.13 mm².

Protective earth contact resistance as per EN 60335

Compliance with the resistance specifications as per EN 60335 for the
protective earth connection circuit must be verified in the application.
Depending on the installation situation, it may be necessary to connect
an additional protective earth conductor by way of the extra protective
earth terminal provided on the device.

4.2.2 Voltage control

NOTE

Excessive current may occur with speed control using
transformers or electronic voltage regulators (e.g. phase angle
control). In addition, depending on how the unit is installed,
noise and vibration can occur with phase angle control.
Vibrations can lead to bearing damage, which can lead to
premature failure.

4.2.3 Frequency inverter

Please use a frequency converter only after consultation with ebm-papst.

For operation with frequency converters, fit sinusoidal filters that
work on all poles (phase-phase and phase-earth) between the
frequency converter and the motor.
During operation with frequency converters, an all-pole sine
filter protects the motor against high-voltage transients that can
destroy the winding insulation system, and against harmful
bearing currents.

Heating-up of the motor when using a frequency converter must be
checked by the customer following installation in the end device.

Item no. 14128-5-9970 · ENG · Revision 202174 · Release 2018-12-28 · Page 6 / 11

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for G2E160-AY50-91

Page 1: ...al staff Only authorised specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any...

Page 2: ...s that come into contact with the rotor and impeller can be injured Secure the device against accidental contact Before working on the system machine wait until all parts have come to a standstill WAR...

Page 3: ...evice with an imbalance e g caused by dirt deposits or icing Resonance mode operation with heavy vibrations These also include vibrations that are transmitted from the customer system to the fan Opera...

Page 4: ...duct drawing All measures have the unit mm 1 Connection line silicone 4G 0 5 mm 4x lead tips crimped Item no 14128 5 9970 ENG Revision 202174 Release 2018 12 28 Page 4 11 ebm papst Mulfingen GmbH Co K...

Page 5: ...ller Sheet steel galvanised Housing material Die cast aluminium Direction of rotation Clockwise seen on rotor Type of protection IP44 Depending on installation and position Insulation class F Humidity...

Page 6: ...sure that the cable end is connected in a dry environment Connect the device only to circuits that can be switched off using an all pole disconnecting switch 4 2 1 Prerequisites Check that the data o...

Page 7: ...irst connect the PE protective earth connection Connect the lines according to your application When doing so observe chapter 4 4 Connection screen Item no 14128 5 9970 ENG Revision 202174 Release 201...

Page 8: ...ctions 4 4 Connection screen U1 blue Z brown U2 black PE green yellow Item no 14128 5 9970 ENG Revision 202174 Release 2018 12 28 Page 8 11 ebm papst Mulfingen GmbH Co KG Bachm hle 2 D 74673 Mulfingen...

Page 9: ...ALFUNCTIONS POSSIBLE CAUSES AND REMEDIES Do not perform any repairs on your device Return the device to ebm papst for repair or replacement WARNING Terminals and connections have voltage even with a u...

Page 10: ...recommendations for ecological disposal of the product and its components 5 3 1 Country specific legal requirements NOTE Country specific legal requirements Always observe the applicable country spec...