4. CONNECTION AND STARTUP

4.1 Mechanical connection

DANGER
Gas leaking from poorly sealed housing

Risk of fatal injury
→ Prior to startup, verify whether the gas blower's housing is

pressure-tight.
When doing so, seal off the intake and outlet openings as
well as the shaft opening.

→ In addition, verify that no rotating parts scrape against

stationary parts.

DANGER
Leaks may occur.

Due to its design, the gas blower is not tightly sealed, e.g. at
the shaft opening. This may result in leaks during operation.
Deflagrations may also cause long-term damage or deformation
of the housing, which can result in leaks. An air/gas mixture
may accumulate outside of the gas blower. The blower can
explode. Severe injuries can result.
→ Check which hazards arise from installing, operating,

servicing or disposing of the gas blower in conjunction with
your device.
Avoid any such hazards.
Carry out all necessary measures.

CAUTION
Cutting and crushing hazard when removing blower
from packaging

→ Carefully remove the blower from its packaging, touching

only the housing. Strictly avoid shocks.

→ Wear safety shoes and cut-resistant safety gloves.

NOTE
Damage to the device from vibration

Bearing damage, shorter service life
→ The fan must not be subjected to force or excessive vibration

from sections of the installation.

→ If the fan is connected to air ducts, the connection should

be isolated from vibration, e.g. using compensators or similar
elements.

→ Ensure stress-free attachment of the fan to the

substructure.

;

Check the device for transport damage. Damaged devices are not to
be installed.

;

Install the undamaged device in accordance with your application.

CAUTION
Possible damage to the device

If the device slips during installation, serious damage can result.
→ Ensure that the device is securely positioned at its place of

installation until all fastening screws have been tightened.

The fan must not be strained on fastening.

4.2 Electrical connection

CAUTION
Voltage

The device is a built-in component and has no disconnecting
switch.
→ Only connect the device to circuits that can be switched off

with an all-pole disconnection switch.

→ When working on the device, secure the system/

machine in which the device is installed so as to prevent it
from being switched back on.

NOTE
Water ingress into wires or cables

Water ingress at the customer end of the cable can damage the
device.
→ Make sure the end of the cable is connected in a dry

environment.

The control voltage circuit is not electrically isolated. Only
connect the device to circuits that can be switched off with an
all-pole disconnection switch.

Operate the device with a safely isolated power supply.

4.2.1 Requirements

;

Check whether the information on the nameplate matches the
connection data.

;

Before connecting the device, make sure the power supply matches
the device voltage.

;

Only use cables designed for the current level indicated on the
nameplate.
For determining the cross-section, note the sizing criteria according
to EN 61800-5-1. The protective earth must have a cross-section
equal to or greater than that of the phase conductor.
We recommend the use of 105 °C cables. Ensure that the minimum
cable cross-section is at least
AWG 26 / 0.13 mm².

4.3 Plug connection

4.3.1 Making supply connections

;

Check your connector's pin assignment.

;

Connect the built-in connector with the mating connector.

;

Ensure that the connector is properly engaged.

Item no. 50402-5-9970 · ENU · Change 202174 · Approved 2018-12-27 · Page 6 / 9

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for G1G126-AB13-13

Page 1: ...lified trained and authorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the device must be assessed again following installation in the final product The locally applicable industrial safety regulations a...

Page 2: ...s Escaping gas can also cause explosions Never open the blower WARNING Rotating device Long hair and dangling items of clothing jewelry and the like can become entangled and be pulled into the device Injuries can result Do not wear any loose fitting or dangling clothing or jewelry while working on rotating parts Protect long hair with a cap WARNING Ejected parts Missing protective devices may allo...

Page 3: ...ant operation operation with severe vibration This also includes vibration transmitted to the fan from the customer installation Conveying a medium that contains abrasive particles Conveying a highly corrosive medium Conveying a medium with high dust content e g suctioning off sawdust Operating the gas blower in an environment that contains flammable gases or dust or combustible solids or fluids C...

Page 4: ...ing side parts sealed with NBR edge cord pentane resistant 2 Edge connection 2 1 2 2 PWM input 2 3 free 2 4 Speed monitoring 2 5 3 Pressure tap sealed drilled open if required Item no 50402 5 9970 ENU Change 202174 Approved 2018 12 27 Page 4 9 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Page 5: ...regard to cyclic speed loads note that the rotating parts of the device are designed for a maximum of one million load cycles If you have special questions consult ebm papst for support Use the device in accordance with its degree of protection Information on surface quality The surfaces of the products conform to the generally applicable industrial standard The surface quality may change during t...

Page 6: ...age to the device If the device slips during installation serious damage can result Ensure that the device is securely positioned at its place of installation until all fastening screws have been tightened The fan must not be strained on fastening 4 2 Electrical connection CAUTION Voltage The device is a built in component and has no disconnecting switch Only connect the device to circuits that ca...

Page 7: ...ating instructions 4 4 Connection diagram Drawing preliminary Item no 50402 5 9970 ENU Change 202174 Approved 2018 12 27 Page 7 9 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Page 8: ...not switch the motor e g in cyclic operation on and off via power supply Switching off the device for maintenance Switch off the device via the control input Do not switch the motor e g in cyclic operation on and off via power supply Disconnect the device from the power supply 5 MAINTENANCE MALFUNCTIONS POSSIBLE CAUSES AND REMEDIES Do not perform any repairs on your device Send the device to ebm p...

Page 9: ...ve the applicable country specific legal regulations with regard to the disposal of products or waste occurring in the various phases of the life cycle The corresponding disposal standards are also to be heeded 5 3 2 Disassembly Disassembly of the product must be performed or supervised by qualified personnel with the appropriate technical knowledge The product is to be disassembled into suitable ...

Reviews: