background image

Operating instructions

D3G180-AB62-01

Translation of the original operating instructions

WARNING
Terminals and connections have voltage even with a
unit that is shut off

Electric shock
→ Wait five minutes after disconnecting the voltage at all poles

before opening the device.

CAUTION
In the event of failure, there is electric voltage at the
rotor and impeller

The rotor and impeller are base insulated.
→ Do not touch the rotor and impeller once they are installed.

CAUTION
If control voltage is applied or a speed setpoint is stored,
the motor will restart automatically, e.g. after a mains
failure.

Risk of injury
→ Keep out of the device hazard zone.
→ When working on the device, switch off the mains power

and ensure that it cannot be switched back on.

→ Wait until the device stops.
→ After working on the device, remove any tools used or

other objects from the device.

1.5 Safety and protective functions

DANGER
Protective device missing and protective device not
functioning

Without a protective device there is a risk of serious injury, for
instance when reaching into the device during operation.
→ Operate the device only with a fixed protective device and

guard grille.

→ The fixed protective device must be able to withstand the

kinetic energy of a fan blade that becomes detached at
maximum speed. There must not be any gaps which it is
possible to reach into with the fingers, for example.

→ The device is a built-in component. As the operator, you

are responsible for ensuring that the device is secured
adequately.

→ Stop the device immediately if a protective device is

found to be missing or ineffective.

1.6 Electromagnetic radiation

Interference from electromagnetic radiation is possible, e.g. in conjunction
with open and closed-loop control devices.
If unacceptable emission intensities occur when the fan is installed,
appropriate shielding measures have to be taken by the user.

NOTE
Electrical or electromagnetic interferences after
integrating the device in installations on the customer's
side.

→ Verify that the entire setup is EMC compliant.

1.7 Mechanical movement

DANGER
Rotating device

Body parts that come into contact with the rotor and impeller
can be injured.
→ Secure the device against accidental contact.
→ Before working on the system/machine, wait until all

parts have come to a standstill.

WARNING
Rotating device

Long hair, dangling items of clothing, jewellery and similar items
can become entangled and be pulled into the device. Risk of
injury.
→ Do not wear any loose-fitting or dangling clothing or jewellery

while working on rotating parts.

→ Protect long hair with a cap.

1.8 Emission

WARNING
Depending on the installation and operating conditions,
a sound pressure level greater than 70 dB(A) may arise.

Danger of noise-induced hearing loss
→ Take appropriate technical safety measures.
→ Protect operating personnel with appropriate safety

equipment, e.g. hearing protection.

→ Also observe the requirements of local agencies.

1.9 Hot surface

CAUTION
High temperature at the electronics housing

Risk of burns
→ Ensure sufficient contact protection.

1.10 Transport

NOTE
Transporting the device

→ Transport the device in its original packaging only.

1.11 Storage

;

Store the device, partially or fully assembled, in the original
packaging in a clean, dry and weatherproof place free of vibrations.

;

Protect the device against environmental effects and dirt until final
installation.

;

We recommend storing the device for no longer than one year in
order to guarantee trouble-free operation and longest possible service
life.

;

Even devices explicitly intended for outdoor use are to be stored as
described prior to commissioning.

;

Maintain the storage temperature, see
chapter 3.5 Transport and storage conditions.

Item no. 50035-5-9970 · ENG · Revision 200166 · Release 2019-06-17 · Page 2 / 10

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for D3G180-AB62-01

Page 1: ...rised specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it is installed in the end device The local industrial safety regulations must always be observed when working on the device Keep the workplace clean and...

Page 2: ...o be taken by the user NOTE Electrical or electromagnetic interferences after integrating the device in installations on the customer s side Verify that the entire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device Body parts that come into contact with the rotor and impeller can be injured Secure the device against accidental contact Before working on the system machine wait un...

Page 3: ... and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Resonance mode operation with heavy vibrations These also include vibrations that are transmitted from the customer system to the fan Operation in medical equipment with a life sustaining or lifesaving function Moving solids content in flow medium Painting the device Connections e g screws coming loo...

Page 4: ...measures have the unit mm 1 Connection line PVC AWG22 4x core end sleeve 2 Connection line PVC AWG18 3x core end sleeve Item no 50035 5 9970 ENG Revision 200166 Release 2019 06 17 Page 4 10 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Page 5: ...335 1 EN 61800 5 1 CE For cyclic speed loads note that the rotating parts of the device are designed for maximum one million load cycles If you have specific questions contact ebm papst for support Use the device in accordance with its protection type Notes on surface quality The surfaces of the products conform to the generally applicable industrial standard The surface quality may vary during th...

Page 6: ...ly to circuits that can be switched off using an all pole disconnecting switch When working on the device you must switch off the system machine in which the device is installed and secure it from being switched on again NOTE Interferences and failures are possible Maintain a distance to the power supply line when routing the control lines of the device Ensure a sufficiently large clearance Recomm...

Page 7: ...h 8 0 10 V PWM yellow Control input 0 10 V or PWM electrically isolated 9 Tach white Tach output open collector 1 pulse per revolution electrically isolated 11 10V max 1 1 mA red Voltage output 10 V max 1 1 mA electrically isolated 12 GND blue GND Connection for control interface Item no 50035 5 9970 ENG Revision 200166 Release 2019 06 17 Page 7 10 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 7467...

Page 8: ...e supply voltage When disconnecting be sure to disconnect the earth wire connection last 5 INTEGRATED PROTECTIVE FUNCTIONS The integrated protective functions cause the motor to switch off automatically in case of faults described in the table Malfunctions Description Function of safety feature Rotor position detection error An automatic restart occurs Locked rotor After the blockage is removed th...

Page 9: ...ts used Immediately switch off and replace the device if severe corrosion is apparent at load bearing or rotating parts Repairs to load bearing or rotating parts are not permissible Operate the fan for 2 hours at maximum speed to permit the evaporation of any moisture which may have ingressed If cleaning does not eliminate vibration the fan may have to be re balanced In such cases please contact e...

Page 10: ...nts could drop off during disassembly This can result in fatal or serious injury and material damage Secure components before unfastening to stop them falling 6 3 3 Component disposal The products are mostly made of steel copper aluminium and plastic Metallic materials are generally considered to be fully recyclable Separate the components for recycling into the following categories Steel and iron...