background image

Operating instructions

D3G146-LT13-30

Translation of the original operating instructions

WARNING
Terminals and connections have voltage even with a
unit that is shut off

Electric shock
→ Wait five minutes after disconnecting the voltage at all poles

before opening the device.

CAUTION
In the event of failure, there is electric voltage at the
rotor and impeller

The rotor and impeller are base insulated.
→ Do not touch the rotor and impeller once they are installed.

CAUTION
If control voltage is applied or a speed setpoint is stored,
the motor will restart automatically, e.g. after a mains
failure.

Risk of injury
→ Keep out of the device hazard zone.
→ When working on the device, switch off the mains power

and ensure that it cannot be switched back on.

→ Wait until the device stops.
→ After working on the device, remove any tools used or

other objects from the device.

1.5 Safety and protective functions

DANGER
Guard missing and guard not functioning

Without a guard there is a risk of serious injury, for instance
when reaching into the device during operation. Loose parts or
items of clothing could be drawn in.
→ The device is a built-in component. As the operator, you are

responsible for ensuring that the device is secured
adequately.# Operate the device only with a fixed protective
device and guard grille.

→ Stop the device immediately if a protective device is

found to be missing or ineffective.

1.6 Electromagnetic radiation

Interference from electromagnetic radiation is possible, e.g. in conjunction
with open and closed-loop control devices.
If unacceptable emission intensities occur when the fan is installed,
appropriate shielding measures have to be taken by the user.

NOTE
Electrical or electromagnetic interferences after
integrating the device in installations on the customer's
side.

→ Verify that the entire setup is EMC compliant.

1.7 Mechanical movement

DANGER
Rotating device

Body parts that come into contact with the rotor and impeller
can be injured.
→ Secure the device against accidental contact.
→ Before working on the system/machine, wait until all

parts have come to a standstill.

WARNING
Rotating device

Long hair, dangling items of clothing, jewellery and similar items
can become entangled and be pulled into the device. Risk of
injury.
→ Do not wear any loose-fitting or dangling clothing or jewellery

while working on rotating parts.

→ Protect long hair with a cap.

1.8 Emission

WARNING
Depending on the installation and operating conditions,
a sound pressure level greater than 70 dB(A) may arise.

Danger of noise-induced hearing loss
→ Take appropriate technical safety measures.
→ Protect operating personnel with appropriate safety

equipment, e.g. hearing protection.

→ Also observe the requirements of local agencies.

1.9 Hot surface

CAUTION
High temperature at the electronics housing

Risk of burns
→ Ensure sufficient contact protection.

1.10 Transport

NOTE
Transporting the device

→ Transport the device in its original packaging only.

1.11 Storage

;

Store the device, partially or fully assembled, in the original
packaging in a clean, dry and weatherproof place free of vibrations.

;

Protect the device against environmental effects and dirt until final
installation.

;

We recommend storing the device for no longer than one year in
order to guarantee trouble-free operation and longest possible service
life.

;

Even devices explicitly intended for outdoor use are to be stored as
described prior to commissioning.

;

Maintain the storage temperature, see
chapter 3.5 Transport and storage conditions.

Item no. 53670-5-9970 · ENG · Revision 230387 · Release 2021-03-29 · Page 2 / 11

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for D3G146-LT13-30

Page 1: ...orised specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it is installed in the end device The local industrial safety regulations must always be observed when working on the device Keep the workplace clean an...

Page 2: ...n installations on the customer s side Verify that the entire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device Body parts that come into contact with the rotor and impeller can be injured Secure the device against accidental contact Before working on the system machine wait until all parts have come to a standstill WARNING Rotating device Long hair dangling items of clothing j...

Page 3: ... and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Resonance mode operation with heavy vibrations These also include vibrations that are transmitted from the customer system to the fan Operation in medical equipment with a life sustaining or lifesaving function Moving solids content in flow medium Painting the device Connections e g screws coming loo...

Page 4: ... 2 Tach 1 3 0 10 V lin PWM 1 4 GND 2 Connector Lumberg 3642 03 K01 pluggable with 3626 03 K01 2 1 PE 2 2 L 2 3 N 3 4x sheet metal nut for thread EN ISO 1478 ST4 8 min screw length 14 5 mm plus thickness of mounting material Item no 53670 5 9970 ENG Revision 230387 Release 2021 03 29 Page 4 11 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 inf...

Page 5: ... CE Approval CSA C22 2 no 77 CAN CSA E60730 1 UL 1004 7 60730 1 For cyclic speed loads note that the rotating parts of the device are designed for maximum one million load cycles If you have specific questions contact ebm papst for support Use the device in accordance with its protection type Notes on surface quality The surfaces of the products conform to the generally applicable industrial stand...

Page 6: ...to leads or wires Water enters at the cable end on the customers side and can damage the device Make sure that the cable end is connected in a dry environment Connect the device only to circuits that can be switched off using an all pole disconnecting switch 4 2 1 Prerequisites Check that the data on the type plate match the connection data Before connecting the device ensure that the supply volta...

Page 7: ...rent FLA 4 3 Connection via plug 4 3 1 Establish supply connections Check the PIN assignment of your connector Connect the panel connector and mating connector Ensure that the connector is locked in correctly Item no 53670 5 9970 ENG Revision 230387 Release 2021 03 29 Page 7 11 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst ...

Page 8: ...1 1 mA red Voltage output 10 V 1 1 mA electrically isolated not short circuit proof CON11 11 2 Tach white Tach output Open collector 1 pulse per revolution electrically isolated Isink max 10 mA CON11 11 3 0 10 V PWM yellow Control input 0 10 V or PWM electrically isolated CON11 11 4 GND blue GND connection for control interface Item no 53670 5 9970 ENG Revision 230387 Release 2021 03 29 Page 8 11 ...

Page 9: ...l input Do not switch the motor e g in cyclic operation on and off via power supply Disconnect the device from the supply voltage When disconnecting be sure to disconnect the earth wire connection last 5 INTEGRATED PROTECTIVE FUNCTIONS The integrated protective functions cause the motor to switch off automatically in case of faults described in the table Malfunctions Description Function of safety...

Page 10: ...ovided with maintenance free ball bearings The lifetime lubrication of the ball bearings is designed for a service life of 40 000 hours Please contact ebm papst if bearing replacement is required after this period Adapt the maintenance intervals to the dust pollution occurring 6 2 Safety test NOTE High voltage test The integrated EMC filter contains Y capacitors Therefore the trigger current is ex...

Page 11: ...etallic materials are generally considered to be fully recyclable Separate the components for recycling into the following categories Steel and iron Aluminium Non ferrous metal e g motor windings Plastics particularly with brominated flame retardants in accordance with marking Insulating materials Cables and wires Electronic scrap e g circuit boards Only ferrite magnets and not rare earth magnets ...