Operating and Maintenance Instructions
210-OMI13277_Iss1.doc
ORIGINAL INSTRUCTIONS
Page 6 of 15
© ebm-papst UK Ltd, 2012
Chelmsford Business Park Chelmsford Essex CM2 5EZ
Telephone: +44(0)1245468555 Fax: +44(0)1245466336
e-mail
CN1090
Fan Speed Select
Inputs
J1, J2
Proportional Band Control, Fan Speed
FAN STOP
Minimum
Speed,
S2 setting
Proportional
Band Control,
Sensor Demand
Maximum
Speed,
S3 setting
SL2, Switched
Live Input 2
Stop/Run
(J1 pin 2)
Open
-
Linked to
230VAC
Linked to
230VAC
Linked to
230VAC
Volt Free Stop/Run
(J2 pin 11)
-
Open
Linked to 0V
Linked to 0V
Linked to 0V
SL1, Switched
Live Input 1
(J1 pin 1)
-
-
Open
-
Linked to
230VAC,
and
DIP SW 6
OFF
-
Linked to
230VAC,
and
DIP SW 6
ON
Volt Free Select
Input 1 (J2 pin 9)
-
-
Open
Linked
to 0V
-
-
-
Volt Free Select
Input 2 (J2 pin 13)
-
-
Open
Open
Open
Linked
to 0V
-
In the above table “-” indicates “Input state ignored”
DIP Switch 1
Position
Proportional Band Control, Options
OFF
ON
5
Normal Operation
Commissioning, see table below
6
SL1 selects Sensor Demand Fan Speed
SL1 selects Maximum Fan Speed, S3 setting.
DIP Switch 1
Position
Proportional Band Control, Commissioning
5
6
PWM Outputs
Indicator LED
ON
Off
Fan 1 Speed Control PWM Output = R1 Setting
Fan 2 Speed Control PWM Output = R2 Setting
NTC1 Red LED Pulse
ON
ON
Fan 1 Speed Control PWM Output = R3 Setting
Fan 2 Speed Control PWM Output = R4 Setting
NTC2 Red LED Pulse
Off
-
Normal Operation,
Fan 1 Speed Control PWM Output = Fan 1 speed control
Fan 2 Speed Control PWM Output = Fan 2 speed control
NTC1 & NTC2 Red LED Off
Variable
Resistors
Proportional Band Control, Set-points
R1
Sensor 1, input voltage at bottom of proportional band 1
R2
Sensor 1, input voltage at top of proportional band 1
R3
Sensor 2, input voltage at bottom of proportional band 2
R4
Sensor 2, input voltage at top of proportional band 2
Rotary DIP
Switch
Proportional Band Control, normal
profile, Fan Speed Range
Invert Speed Control Output
(Heating Profile)
, Fan Speed Range
S2
Fan Minimum Speed
Fan Maximum Speed
S3
Fan Maximum Speed
Fan Minimum Speed
To invert Speed Control Output (Heating Profile), make S2 setting higher than S3 setting.