4.5  Connection diagram 

42 

 

 

 

 

 

No. 

Conn. 

Designation 

Color 

Function/assignment 

1, 2 

PE 

Green/ye

llow 

Protective earth

 

Blue 

Power supply, neutral conductor, 50/60 Hz

 

Black 

Power supply, phase, 50/60 Hz

 

NC 

White 1 

Status relay, floating status contact; break for failure, contact rating 250 VAC / 2A (AC1) / 

min. 10 mA, basic insulation on supply side and reinforced insulation on control interface 

side

 

COM 

White 2 

Status relay, floating status contact; common connection, contact rating 250 VAC / 2A 

(AC1) / min. 10 mA, basic insulation on supply side and reinforced insulation on control 

interface side

 

0-10V 

Yellow 

Analog input (set value); 0-10 V; Ri = 100 k

Ω

; adjustable curve

 

10 

RSB 

Brown 

RS485 interface for MODBUS, RSB

 

11 

RSA 

White 

RS485 interface for MODBUS, RSA

 

12 

GND 

Blue 

Reference ground for control interface, SELV

 

13 

+10V 

Red 

Fixed voltage output 10 VDC, +10 V ±3%; max. 10 mA; short-circuit-proof; power supply 

for external devices (e.g. pot)

 

 

 

 

 

 

 

 

Summary of Contents for BoxFan BF700S-355RT01I2

Page 1: ...akes it resistant to various climate impacts Inside the box the fan is mounted on a warm galvanized sheet metal plate and this is accessed by removing the inspection hatch The fan itself is an EC fan...

Page 2: ...surface 5 1 10 Storage 5 1 11 Disposal 5 1 12 Transport 5 2 INTENDED USE 5 3 TECHNICAL DATA 6 3 1 Product drawing 6 3 2 Nominal Data 7 3 3 Technical description 8 3 4 Mounting data 8 3 5 Electromagnet...

Page 3: ...TION Indicates a potentially hazardous situation which can result in minor or moderate injury or damage to property if the specified actions are not taken 4 NOTE A potentially harmful situation can oc...

Page 4: ...free blowing or free suctioning and is not connected to ducts The protective net must be able to withstand the kinetic energy of an impeller part The unit is a built in component You the owner is res...

Page 5: ...he longest possible service life The unit must be stored in the temperature range 40o C to 80o C Avoid shocks and bumps When storing or installing the product must be positioned so that it cannot func...

Page 6: ...under this application 24 Moving air contaminated by dust e g extraction of sawdust Operation of the unit close to combustible materials or components Operation of the device in an explosive atmosphe...

Page 7: ...x static pressure 880 Pa 1 Nominal data in working point with max load at 230 VAC 26 Additional data PFC Passive LwA Sound effect 87 dB A 2 LpA Sound pressure at 1 m 76 dB A 2 LpA Sound pressure at 3...

Page 8: ...cordance with the rules of ISO 14118 31 Any emergency stop functions must meet the requirements of ISO 13850 3 5 Electromagnetic compatibility 32 EMC emission EN 61000 6 3 EMC Immunity EN 6100 6 2 Har...

Page 9: ...e a gap between the supply cable and the control cable when installing these in the application Provide adequate distance Recommendation distance 10 cm separate wiring 39 NOTE Water ingress into wires...

Page 10: ...asic insulation on supply side and reinforced insulation on control interface side 1 7 COM White 2 Status relay floating status contact common connection contact rating 250 VAC 2A AC1 min 10 mA basic...

Page 11: ...ominal supply voltage Start the device by changing the input signal 4 8 Switching off the device 46 Switching off the device during operation Switch off the device via the control input to protect it...

Page 12: ...Lower temp if possible Reset by reducing control signal to 0 VDC Impeller runs unevenly Imbalance in rotating parts Clean the unit and balance it properly If imbalance Is still present the unit is re...

Reviews: