ELIO
EN
33
www.eberg.eu
technician is aware of potentially flammable atmospheres. Ensure that the leak tection equipment being
used is suitable for use with flammable refrigerants, i.e. nonsparking, adequately sealed or intrinsically
safe.
1.5 Presence of fire extinguisher
If any hot work is to be conducted on the refrigeration equipment or any associated parts, propriate fire
extinguishing equipment shall be available to hand. Have a dry powder or CO 2 fire extinguisher adjacent
to the charging area.
1.6 No ignition sources
No person carrying out work in relation to a refrigeration system which involves exposing any pipe work
that contains or has contained flammable refrigerant shall use any sources of ignition in such a manner
that it may lead to the risk of fire or explosion. All possible ignition sources, including igarette smoking,
should be kept sufficiently far away from the site of installation, repairing, removing and disposal, during
which flammable refrigerant can possibly be released to the surrounding space. Prior to work taking place,
the area around the equipment is to be surveyed to make sure that there are no flammable hazards or
ignition risks. “No Smoking” signs shall be
displayed.
1.7 Ventilated area
Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or
conducting any hot work. A degree of ventilation shall continue during the period that the work is carried
out. The ventilation should safely disperse any released refrigerant and preferably expel it externally into
the atmosphere.
1.8 Checks to the refrigeration equipment
Where electrical components are being changed, they shall be fit for the purpose and to the correct
specification. At all times the manufacturer’s maintenance and service guidelines shall be followed. If
in doubt consult the manufacturer’s technical department for assistance.The following checks shall be
applied to installations using flammable refrigerants: the charge size is in accordance with the room
size within which the refrigerant containing parts are installed; the ventilation machinery and outlets
are operating adequately and are not obstructed; if an indirect refrigerating circuit is being used, the
secondary circuit shall be checked for the presence of refrigerant; marking to the equipment continues to
be visible and legible. Markings and signs that
are illegible shall be corrected; refrigeration pipe or components are installed in a position where they are
unlikely to be exposed to any substance which may corrode refrigerant containing components, unless
the components are constructed of materials which are inherently resistant to being corroded or are
suitably protected against being so corroded.
1.9 Checks to electrical devices
Repair and maintenance to electrical components shall include initial safety checks and component
inspection procedures. If a fault exists that could compromise safety, then no electrical supply shall be
connected to the circuit until it is satisfactorily dealt with. If the fault cannot be corrected immediately but
it is necessary to continue operation, an adequate temporary solution shall be used. This shall be reported
to the owner of the equipment so all parties are advised.
Initial safety checks shall include: that capacitors are discharged: this shall be done in a safe manner
to avoid possibility of sparking; that there no live electrical components and wiring are exposed while
charging, recovering or purging the system; that there is continuity of earth bonding.
2. REPAIRS TO SEALED COMPONENTS
2.1
During repairs to sealed components, all electrical supplies shall be disconnected from the equipment
being worked upon prior to any removal of sealed covers, etc. If it is absolutely necessary to have an
electrical supply to equipment during servicing, then a permanently operating form of leak detection
shall be located at the most critical point to warn of a potentially hazardous situation.