Do not use means to accelerate the defrosting process or to clean, other than those
recommended by the manufacturer.
•
The appliance shall be stored in a room without continuously operating open flames (for example
an operating gas appliance) or other potential ignition sources (for example an operating electric
heater, hot surfaces).
•
All the work men who are engaging in the refrigeration system should bear the valid certification
awarded by the authoritative organization and the qualification for dealing
with
the
refrigeration system recognized by this industry. If it needs other technician to maintain and repair
the appliance, they should be supervised by the person who bears the qualification for using the
flammable refrigerant.
•
It can only be repaired by the method suggested by the equipment’s manufacturer.
•
Do not pierce or burn.
•
Be aware that the refrigerants may not contain an odour.
•
Compliance with national gas regulations shall be observed.
•
Keep ventilation openings clear of obstruction.
•
The appliance shall be stored so as to prevent mechanical damage from occurring.
•
Any person who is involved with working on or breaking into a refrigerant circuit should hold a
current valid certificate from an industry-accredited assessment authority, which authorizes their
competence to handle refrigerants safely in accordance with an industry recognized assessment
specification.
•
Servicing shall only be performed as recommended by the equipment manufacturer.
•
Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under
the supervision of the person competent in the use of flammable refrigerants.
•
Appliance should be installed, operated and stored in a room with a floor area larger than the one
indicated in the chart.
Quantity of R290 gas in charge
(see rating label on the appliance) (g)
Minimum size of the site for use and
storage (m²)
m < 152
4
152 ≤ m ≤ 185
9
186 ≤ m ≤ 225
11
226 ≤ m ≤ 270
13
271 ≤ m ≤ 290
14
Caution Risk of fire