EN | Assembly instructions for MI-60

Important

 The system is a mains voltage installation and must 

therefore be installed in accordance with the current regulations 

and under the supervision of a qualified electrician. 

Before you start installing

• Check that the material supplied corresponds with the information 

on the delivery note.

Measurements and test record

• Measure the insulation and resistance of the cable, see values in the 

table. Enter the values in the test report (at the end of the manual). 

• The insulation and resistance of the cable must be measured before 

and after embedding/surface coating, to check that the cable was 

not damaged when it was laid. Enter the values in the test report.

Technical specifications for MI-60

Thank you for choosing Ebeco. For the guarantee to be valid, the 

product must be installed and operated as indicated in this manual. 

This means it is extremely important that you read the entire manual.

 

If you have any questions, you are always more than welcome 

to contact Ebeco. Call +46 (0) 31 707 75 50 or send an e-mail 

to [email protected]. Feel free to visit ebeco.com for more 

information.

Roughly plan how to lay the cable

• Take into account that the heating cable has a 3 m long cold cable 

at each end and that both ends must be connected to the same 

junction box.

• Check the c/c distance using the formula:

Design of the cable

MI heating 

cable

MI heating cable to MI 

cold cable junction

MI cold cable

Flex joint

Flexible cold cable

PROTECTIVE PIPE

Important to know

• The cold cable consists of a flexible cold cable section with earth 

braid. The flexible cold cable can be shortened. The heating cable 

must not be cut. 

• Protect the cold cables from moisture and damage.

• Do not lay the flex joint and the flexible cold cable in direct contact 

with the hot asphalt. Use a protective pipe (metal), see diagram 

above. The sensor cable must also be laid in a protective pipe.

• The joint between the MI cold cable and the MI heating cable must 

be covered with the same material used for the MI heating cable. 

Check that the MI heating cable is completely covered.

• The cable must not touch or cross itself. Minimum distance 60 mm.

• The cable must not cross any expansion joints.

• Minimum bend radius is 6 x the heating cable’s diameter.

Areas of application

The cable can be laid in asphalt, concrete or sand which is 

covered with paving stones, flagstones or asphalt.  

• The working temperature of the asphalt must not exceed 250 °C

• Do not expose the sensor and the cable roll to extreme 

temperatures (≥ 80 °C) for a long period of time.

• Lowest laying temperature is -5 °C.

C/c distance  = 

Area

Cable length

Art. no.

Power 

Length

Resistance

Area (300 W/m²)

89 607 80

2,380 W

42 m

67 

8 m²

89 607 82

3,450 W

58 m

46 

11.5 m²

89 607 84

3,800 W

67 m

42 

12.5 m²

89 607 86

4,500 W

79 m

35 

15 m²

89 607 88

5,350 W

95 m

30 Ω

18 m²

Tolerance ± 10 %

c/c distance approx. 19 cm

Voltage:  400 V 

Insulation:  >10 m Ω

Summary of Contents for MI-60

Page 1: ...onteringsanvisning EN Assembly instructions NO Monteringsanvisning FI Asennusohje MI 60 Kopparmantlad v rmekabel Copper clad heating cable Kobbermantlet varmekabel Metallivaippainen l mp kaapeli ebeco...

Page 2: ...p av formeln Kabelns konstruktion MI v rmekabel verg ng MI v rmekabel till MI kallkabel MI kallkabel Flexskarv Flexibel kallkabel SKYDDSR R Viktigt att veta Kallkabeln best r av en flexibel kallkabel...

Page 3: ...f rs nkt f r att kunna l gga v rmekabeln p en plan yta 3 Montera galvade f stband Art nr 8960968 med cc avst nd ca 50 cm Fixera mot underlaget 4 Rulla f rsiktigt ut v rmekabeln se till att den inte vr...

Page 4: ...Design of the cable MI heating cable MI heating cable to MI cold cable junction MI cold cable Flex joint Flexible cold cable PROTECTIVE PIPE Important to know The cold cable consists of a flexible col...

Page 5: ...le is recessed in order to lay the heating cable on a flat surface 3 Fix the galvanised fixing strip Art no 8960968 at a c c distance of about 50 cm Fix on the substrate 4 Roll out the heating cable w...

Page 6: ...n Kabelens konstruksjon MI varmekabell Overgang MI varmekabel til MI kaldkabel MI kaldkabel Fleksskj t Fleksibel kaldkabel BESKYTTELSESR R Viktig vite Kaldkabelen best r av en fl eksibel kaldkabel med...

Page 7: ...ligger forsenket slik at varmekabelen kan legges p plant underlag 3 Monter galvaniserte festeb nd Art nr 8960968 med cc avstand p ca 50 cm Fest mot underlaget 4 Rull varmekabelen forsiktig ut og pass...

Page 8: ...aapeli ja MI kylm kaapeli jatko MI kylm kaapeli Joustava liitos Joustava kylm kaapeli SUOJAPUTKI Tuotenro Teho Pituus Vastus Pinta ala 300 W m 89 607 80 2380 W 42 m 67 8 m 89 607 82 3450 W 58 m 46 11...

Page 9: ...asennettua l mmityskaapelin tasaiselle pinnalle 3 Asenna galvanoitu kiinnitysnauha tuotenro 8960968 siten ett c c v li on noin 50 cm Kiinnit alustaan 4 Pura l mmityskaapeli varovasti kelalta Varmista...

Page 10: ...beh rig elinstallat r har vidtagit ndringar eller reparationer Garantin g ller ej heller om felet har uppst tt som ett resultat av anv ndning av felaktigt material och konstruktion eller som ett resul...

Page 11: ...ivt om en ikke autorisert installat r har gjort endringer eller reparasjoner Garantien gjelder heller ikke dersom feilen har oppst tt som resultat av bruk av feilaktig materiell og konstruksjon eller...

Page 12: ...out by an unqualified electrician or alternatively if an unqualified electrician has carried out modifications or repairs Nor does the guarantee apply if the defect has arisen as a result of using in...

Page 13: ...u muu kuin p tev s hk asentaja eik tilanteita joissa joku muu kuin p tev s h k asentajaontehnytmuutoksiataikorjauksia Takuueimy sk n kata vikoja jotka ovat aiheutuneet viallisen materiaalin ja ra kent...

Reviews: