Drawing   : - TPC303 
Issue 

: - 7 

Date 

: - 03/10/12 

TROUBLESHOOTING 

S

YMPTOM

 

C

AUSE

 

R

EMEDY

 

Unit inoperative 

1. No power to unit

1. Check the power from
power supply panel

Little or no airflow 

1. Loose fan on shaft
2. Fan motor burnt out
3. Dirty refrigeration coils
4. Loose electrical wiring

5. Fuse blown or circuit

breaker tripped

1. Tighten fan
2. Replace the fan motor
3. See 

Routine Maintenance

Section
4. Check the wiring diagram
to find fault and repair
5. Replace the fuse or reset
the circuit breaker

Little or no water 
extraction 

1. Insufficient air flow
2. Compressor fault
3. Loss of refrigerant gas

1. Check all of the above
2. Contact the Factory
Service Center
3. Contact the Factory
Service Center

Little or no defrost 
when required 

1. Faulty timer
2. Faulty by-pass valve

1. Contact the Factory
Service Center
2. Contact the Factory
Service Center

Unit vibrates 
excessively 

1. Loose compressor
2. Damaged fan

1. Tighten the nuts on the
compressor mounts
2. Replace fan

Water flooding inside 
the machine 

1. Drain pipe blocked/frozen
2. Drain pipe too high
3. Crimped or blocked tubing

1. Clear the obstruction
2. Ensure that no section of
the drain hose is above the
level of the water outlet
3. Straighten, clear, or replace
tubing

E B A C    K O M P A C T    R E S T O R A T I O N    D E H U M I D I F I E R 

Pure n Natural Systems  |  purennatural.com  |  1-800-237-9199

Summary of Contents for KOMPACT

Page 1: ...9 Drawing TPC303 Issue 7 Date 03 10 12 KOMPACT INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL E B A C K O M P A C T R E S T O R A T I O N D E H U M I D I F I E R Pure n Natural Systems purennatural com 1 800...

Page 2: ...ONTENTS Item Description Quantity 10240KP US Dehumidifier 1 3086144 Quick release hose coupling 1 3944110 PVC Tube 3 8 I D 7 8M TPC303 Manual 1 E B A C K O M P A C T R E S T O R A T I O N D E H U M I...

Page 3: ...asses through the hot condenser coil where it is reheated using the same energy removed during the cooling phase plus the additional heat generated by the compressor The air is therefore discharged fr...

Page 4: ...ial Products Ltd is as follows R134a 1300 R407c 1610 For type and weight of refrigerant contained in this unit please refer to the product data label MODEL 10240KP US HEIGHT 24 610mm WIDTH 20 508mm DE...

Page 5: ...ve 78 F frost and or droplets of condensed water should cover the entire evaporator coil F After continuous running time of approximately 55 minutes unit will enter Hot Gas defrost mode for several mi...

Page 6: ...rost Partial frosting accompanied by frosting of the thin capillary tubes indicates loss of refrigerant gas or low charge During this inspection check visually to ensure that the pump rollers are turn...

Page 7: ...and rebrazed after servicing NEVER allow permanent service valves to be fitted to any part of the circuit Service valves may leak causing further loss of refrigerant gas 3 The refrigerant compressor f...

Page 8: ...3 Loss of refrigerant gas 1 Check all of the above 2 Contact the Factory Service Center 3 Contact the Factory Service Center Little or no defrost when required 1 Faulty timer 2 Faulty by pass valve 1...

Page 9: ...1107 1 6 Capillary Tube 3014251 48 7 Solenoid Valve 3020814 1 8 Filter Dryer 3020901 1 9 Compressor 3022169 1 10 Solenoid Coil 3030421 1 11 Capacitor 3030908 1 12 Terminal Block 3031460 1 13 Fan Motor...

Reviews: