REPAIRS 

 
 

 

1. 

Should an electrical component fail, consult the Factory Service Center to obtain the  

  proper 

replacement 

part. 

 
 

 

 

2. 

If refrigerant gas is lost from the machine, it will be necessary to use a refrigeration  

 

 

technician to correct the fault.  Contact the Factory Service Center prior to initiating  

 

 

this action.  

 

 

 

Any competent refrigeration technician will be able to service the equipment.  The 
following procedure must be used: 

 
 

 

a.  The source of the leak must be determined and corrected. 

 
 

 

b.  The machine should be thoroughly evacuated before recharging. 

 

 

 

 

c.  The unit must be recharged with refrigerant measured accurately by weight. 

 
 

 

d.  For evacuation and recharging of the machine, use the crimped and brazed 

charging stub attached to the side of the refrigerant compressor. 

 

 

 

 

The charging stub should be crimped and rebrazed after servicing.  

N

EVER

 

allow 

permanent service valves to be fitted to any part of the circuit.  Service valves 
may leak causing further loss of refrigerant gas. 

 

 

 

 

3.  The refrigerant compressor fitted to the dehumidifier is a durable unit that should 

give many years of service.  Compressor failure can result from the machine losing its 
refrigerant gas.  The compressor can be replaced by a competent refrigeration 
technician.   

 
 

 

Failure of the compressor can be confirmed by the following procedure: 

 
 

 

a.  Establish that power is present at the compressor terminals using a voltmeter. 

 

 

 

b.  With the power disconnected, check the continuity of the internal winding by 

using meter across the compressor terminals.  An open circuit indicates that the 
compressor should be replaced. 

 

 

 

c.  Check that the compressor is not grounded by establishing that a circuit does not 

exist between the compressor terminals and the shell of the compressor. 

Summary of Contents for BD-150

Page 1: ...BD 150 OWNERS MANUAL Page 1 of 12 Drawing No TPC161 Issue 2 Date 23 06 03 EBAC MODEL BD 150 1024500 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL...

Page 2: ...s on the evaporator coil and is collected in the condensate tray which is equipped with a permanent drain The cooled air then passes through the hot condenser coil where it is reheated using the same...

Page 3: ...Drawing No TPC161 Issue 2 Date 23 06 03 SPECIFICATIONS MODEL BD 150 HEIGHT 36 WIDTH 24 DEPTH 25 WEIGHT 165 lb AIRFLOW 1114 CFM POWER SUPPLY 115V 60Hz 1 ph FINISH Powder coated Epoxy OPERATING RANGE 4...

Page 4: ...e B Press the start button DO NOT hold in this button for more than 1 second The unit will run C Check that air is being delivered through the front outlet grille and the compressor is running D After...

Page 5: ...vely vacuum clean the coils WARNING DO NOT STEAM CLEAN REFRIGERATION COILS 2 Check that the fan is firmly secured to the motor shaft and that the fan rotates freely The fan motor is sealed for life an...

Page 6: ...he side of the refrigerant compressor The charging stub should be crimped and rebrazed after servicing NEVER allow permanent service valves to be fitted to any part of the circuit Service valves may l...

Page 7: ...3 Loss of refrigerant gas 1 Check all of the above 2 Contact the Factory Service Center 3 Contact the Factory Service Center Little or no defrost when required 1 Faulty timer 2 Faulty by pass valve 1...

Page 8: ...020727 1 5 Evaporator Coil 3020732 1 6 Filter Dryer 3020904 1 7 Fan Motor Assembly 3035774 1 8 By pass Valve 3020810 1 9 Electronic Timer 1600500 1 10 Rotary Switch 3030555 1 11 Terminal Block 3031460...

Page 9: ...EACH OF ANY WRITTEN OR IMPLIED WARRANTY WITH RESPECT TO THE FOREGOING DESCRIBED MERCHANDISE For Your Records Model ____________________ S N ______________________ Date Received ______________ SAVE THI...

Reviews: