BD-150 OWNERS MANUAL 

                                                                             Page 5 of 12 

Drawing No.  :-  TPC161 
Issue :- 

Date :- 

23/06/03

ROUTINE MAINTENANCE 

 
 

WARNING:  

ENSURE THAT THE POWER CORD TO THE MACHINE 

 HAS BEEN  DISCONNECTED BEFORE CARRYING OUT 
 ROUTINE MAINTENANCE. 

 

 

 
To ensure continued full efficiency of the dehumidifier, maintenance procedures should be 
performed as follows: 
 

 

 

 

1. 

Replace or clean the inlet air grille as required.  Clean the surface of the evaporator 
and condenser coils by blowing the dirt out from behind the fins with compressed air.  
Hold the nozzle of the air hose away from the coil to avoid damaging the fins.  
Alternatively, vacuum clean the coils. 

 
 
 

WARNING:  

DO NOT STEAM CLEAN REFRIGERATION COILS. 

 

 

 

 
 

2. 

Check that the fan is firmly secured to the motor shaft and that the fan rotates freely.  

The fan motor is sealed for life and therefore does not need oiling.

 

 

 

3. 

To check the refrigerant charge, run the unit for 15 minutes and briefly remove the 
top cover.  The evaporator coil should be evenly frost coated across its surface.  At 
temperatures above 70

°

F, the coil may be covered with droplets of water rather than 

frost.  Partial frosting accompanied by frosting of the thin capillary tubes, indicates 
loss of refrigerant gas or low charge. 

 
 

4. 

Check all wiring connections.  

 

 

 
 

 
 

I

F ANY OF THE PRECEDING PROBLEMS OCCUR

,

 CONTACT THE 

E

BAC 

S

ERVICE 

C

ENTER PRIOR TO 

CONTINUED OPERATION OF THE UNIT TO PREVENT PERMANENT DAMAGE

Summary of Contents for BD-150

Page 1: ...BD 150 OWNERS MANUAL Page 1 of 12 Drawing No TPC161 Issue 2 Date 23 06 03 EBAC MODEL BD 150 1024500 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL...

Page 2: ...s on the evaporator coil and is collected in the condensate tray which is equipped with a permanent drain The cooled air then passes through the hot condenser coil where it is reheated using the same...

Page 3: ...Drawing No TPC161 Issue 2 Date 23 06 03 SPECIFICATIONS MODEL BD 150 HEIGHT 36 WIDTH 24 DEPTH 25 WEIGHT 165 lb AIRFLOW 1114 CFM POWER SUPPLY 115V 60Hz 1 ph FINISH Powder coated Epoxy OPERATING RANGE 4...

Page 4: ...e B Press the start button DO NOT hold in this button for more than 1 second The unit will run C Check that air is being delivered through the front outlet grille and the compressor is running D After...

Page 5: ...vely vacuum clean the coils WARNING DO NOT STEAM CLEAN REFRIGERATION COILS 2 Check that the fan is firmly secured to the motor shaft and that the fan rotates freely The fan motor is sealed for life an...

Page 6: ...he side of the refrigerant compressor The charging stub should be crimped and rebrazed after servicing NEVER allow permanent service valves to be fitted to any part of the circuit Service valves may l...

Page 7: ...3 Loss of refrigerant gas 1 Check all of the above 2 Contact the Factory Service Center 3 Contact the Factory Service Center Little or no defrost when required 1 Faulty timer 2 Faulty by pass valve 1...

Page 8: ...020727 1 5 Evaporator Coil 3020732 1 6 Filter Dryer 3020904 1 7 Fan Motor Assembly 3035774 1 8 By pass Valve 3020810 1 9 Electronic Timer 1600500 1 10 Rotary Switch 3030555 1 11 Terminal Block 3031460...

Page 9: ...EACH OF ANY WRITTEN OR IMPLIED WARRANTY WITH RESPECT TO THE FOREGOING DESCRIBED MERCHANDISE For Your Records Model ____________________ S N ______________________ Date Received ______________ SAVE THI...

Reviews: