5 Installation
5.4 Mounting
MICRO PANEL XV400 10.4"/12.1"/15"
12/2010 MN04802010Z-EN
www.eaton.com
49
5.4.4
Mounting a device with stainless steel front
1
Select the mounting position of the device as described in Chapter 5.2.3 Requirements for the
mounting position,
26.
2
Prepare a mounting cutout for the device at the selected position:
Mounting cutout:
10.4" devices: 329
×
238 mm (±1 mm)
12.1" devices: 344
×
262 mm (±1 mm)
15" devices: 410
×
315 mm (±1 mm)
Material thickness at the mounting cutout 2…5 mm
10.4" and 12.1" devices with a stainless steel front:
can be mounted horizontally or vertically.
can be used in the potentially explosive atmospheres of the following zones (accord-
ing to ATEX 94/9/EC):
-
Zone 22
-
Zone 1, category 2G or Zone 2, category 3G.
Requirement: The device must be mounted in a pressurized housing.
Max. permissible pressure: 10 mbar continuous.
15" devices with a stainless steel front:
-
must only be mounted horizontally.
-
can be used in potentially explosive atmospheres, Zone 22.
-
require an additional set of retaining brackets for mounting in accordance with IP65
and for use in potentially explosive atmospheres. Please contact your supplier.
Fig. 36 Mounting cutout for 10.4" devices
Fig. 37 Mounting cutout for 12.1" devices
329.0
+1/-1
238.0
+1/-1
344.0
+1/-1
262.0