7 Configuration of the XNE-1SWIRE with MXpro
7.3 Configuration of the XNE-1SWIRE as a remote module on the XN-GWBR-CANopen
XI/ON: XNE-1SWIRE
09/2011 MN05002016Z-EN
www.eaton.com
61
Fig. 17 Parameterization of module properties via service data objects
The following takes place after the program is loaded and started on the XN-PLC-
CANopen:
•
The XNE-1SWIRE on the XN-GWBR-CANopen is ready for data exchange (RDY
LED lit).
•
The physical structure of the SWIRE bus is scanned and compared with the
configuration stored in the XNE-1SWIRE.
• The SWIRE bus starts operation if the physical structure of the SWIRE bus
matches the SWIRE configuration stored in the XNE-1SWIRE (SW LED lit).
• The SWIRE bus does not start operation if the physical structure of the
SWIRE bus does
not
match the configuration stored in the XNE-1SWIRE (SW
LED flashing). If the CFG button of the XNE-1SWIRE is then pressed, the
physical structure of the SWIRE bus is scanned, each slave is assigned an
address and stored in the respective slave and the configuration is stored in
the XNE-1SWIRE.
•
RDY LED and SW LED flash shortly and are then permanently lit.
•
DIA LED goes out since the SWIRE bus is in operation and therefore starts data
exchange with the PLC.