2 Product description
2.2 Function parameterization
XI/ON: XNE-1SWIRE
09/2011 MN05002016Z-EN
www.eaton.com
15
The system behaves as follows if a modification to the bus or a slave failure is
detected:
•
If the
«Moeller Conformance»
function is
activated
, the system retains data
exchange with the functional SWIRE slaves..
•
If the
«Moeller Conformance»
function is
deactivated
, SWIRE communication
on the entire SWIRE bus is aborted. The physical structure is then compared
cyclically with the configuration stored in the XNE-1SWIRE.
• The SWIRE bus starts operation as soon as matching configurations are
detected:
• After the physical structure was stored in the XNE-1SWIRE:
• Automatically (if the automatic SWIRE configuration is activated)
• Or manually (if the automatic SWIRE configuration is deactivated),
by pressing the CFG button (only functions if the SW LED is flashing).
• After the physical structure is corrected.
• According to the parameter settings, the data exchange is then started or the
operation is aborted:
• The data exchange is resumed immediately if the PLC configuration check
is deactivated.
• If the PLC configuration check is activated and the configuration check is
set to
Bus-oriented
, data exchange is only restarted if the configuration
stored in the XNE-1SWIRE matches the SET configuration stored in the
PLC. The operation for the entire SWIRE bus is aborted if they do not
match completely.
• If the PLC configuration check is activated and the configuration check is
set to
Slave-oriented
, the configuration stored in the XNE-1SWIRE is
compared with the SET configuration stored in the PLC:
• The SWIRE slaves that match resume data exchange.
• The operation is aborted for the SWIRE slaves that do not match.