3 Integration of the module in PROFIBUS-DP
3.1 Data mapping under PROFIBUS-DP
36
XI/ON: XNE-1SWIRE
09/2011 MN05002016Z-EN
www.eaton.com
Tab. 16 Meaning of the parameter bits
Byte 2
TYPE
ERR
Group error -Configuration error-
Activate slave diagnostics TYPE
ERR
. As soon as only one slave on the bus is
incorrectly configured, this is indicated as a group error depending on the
parameter setting.
0*
Active
Group diagnostics is activated.
1
Inactive
Group diagnostics is not activated.
U
AUXERR
Error message -U
AUX
-
Activate system diagnostics U
AUXERR
. U
AUXERR
will generate an error
message as soon as the power supply goes below a level at which the func-
tion of the relays is not guaranteed.
0*
Active
Error message U
AUXERR
activated.
1
Inactive
Error message U
AUXERR
not activated.
Byte 3
reserved
Byte 4
reserved
(lifeguarding
time up to
version
VN 01-03)
Was up to version VN 01-03
: Lifeguarding time of the SWIRE slaves.
0x02-
0xFF
0x64*
Setting of lifeguarding time, timeout time up to automatic reset of the slaves
in the event of communication failure. (n × 10 ms) (Default 1s)
0xFF: Lifeguarding off
Byte 5,6 SC
DIAG
Sx
Input bit communication error, slave x
Slave diagnostics message from Byte 1 / Bit 7 is accepted in the feedback
interface as Bit 4.
0*
Active
SC
DIAG
Sx is accepted.
1
Inactive
SC
DIAG
Sx is not accepted.
Byte 7,8 reserved
Byte 9-24Device ID,
slave x
TYPE setting for the SWIRE slave at position x on the SWIRE bus.
0x20
SWIRE-DIL (Moeller)
0x21
SWIRE-4DI-2DO-R (Moeller)
0x01
PH9285.91 (Dold)
0x02
PH9285.91/001 (Dold)
0x03
PH9285.91/002 (Dold)
0xFF
Basic setting (no slave)
Byte
Designa-
tion
Status
Comment